Weinzierl KNX IP LineMaster 760 Specification sheet

WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 1/6
KNX IP LineMaster 760
Operating and installation manual
Application
The KNX LineMaster combines the essential functions of
a KNX bus line: Power supply with choke, IP Router and
IP Interface.
In addition to the bus voltage the power supply offers an
auxiliary voltage of 24 V. The IP Router in the LineMaster
allows forwarding of telegrams between different lines
through a LAN (IP) as a fast backbone. Using the em-
bedded IP Interface, the KNX line can be connected
directly to a PC (e.g. by ETS).
This device works according to the KNXnet/IP
speci-fication using the core, the device management, the
tunneling and the routing part. The router included in the
KNX LineMaster 760 has a filter table and is able to buff-
er up to 150 telegrams.
Coupler function (KNXnet/IP routing)
The KNX IP LineMaster 760 can operate as a line and/or
backbone coupler. In both cases, the LAN (IP) acts as a
backbone.
Switch
LAN
EIB/KNX
1.2.1
1.2.6
1.2.5
1.2.4
1.2.3
1.2.2
1.2.7
1.2.12
1.2.11
1.2.10
1.2.9
1.2.8
KNX / IP
LineMaster
KNX LineMaster
760
KNX LineMaster
760
1.1.0
1.2.0
EIB/KNX
1.1.1
1.1.6
1.1.5
1.1.4
1.1.3
1.1.2
1.1.7
1.1.12
1.1.11
1.1.10
1.1.9
1.1.8
Fig. 1: KNX IP LineMaster as a line coupler
Switch
LAN
EIB/KNX
1.1.0 1.2.0
1.2.1
1.2.6
1.2.5
1.2.4
1.2.3
1.2.2
1.1.1
1.1.6
1.1.5
1.1.4
1.1.3
1.1.2
KNX / IP
LineMaster
KNX LineMaster
760
KNX LineMaster
760
1.0.0
2.0.0
EIB/KNX
2.1.0
2.2.0
2.2.1
2.2.6
2.2.5
2.2.4
2.2.3
2.2.2
2.1.1
2.1.6
2.1.5
2.1.4
2.1.3
2.1.2
Fig. 2: KNX IP LineMaster as a backbone coupler
Switch
LAN
EIB/KNX
1.1.0 1.2.0
1.2.1
1.2.6
1.2.5
1.2.4
1.2.3
1.2.2
1.1.1
1.1.6
1.1.5
1.1.4
1.1.3
1.1.2
KNX IP
Router
2.1.0
EIB/KNX
2.1.1
2.1.6
2.1.5
2.1.4
2.1.3
2.1.2
2.1.7
2.1.12
2.1.11
2.1.10
2.1.9
2.1.8
KNX / IP
LineMaster
KNX LineMaster
760
KNX LineMaster
760
1.0.0
2.1.0
Fig. 3: KNX IP LineMaster as a backbone and line cou-
pler
The physical address assigned to the KNX IP LineMaster
760 determines whether the device operates as a line or
backbone coupler. If the physical address is in the form of
x.y.0 (x, y: 1..15), the LineMaster operates as a line cou-
pler. If it is in the form of x.0.0 (x: 1..15), the LineMaster
acts as a backbone coupler.
Attention:
If the KNX IP LineMaster 760 is used as a backbone
coupler (x.0.0), there must be no KNX IP LineMaster in
the topology beneath it. For example, if a KNX IP Line-
Master has the physical address of 1.0.0, there must be
no KNX IP LineMaster with the address 1.1.0.
If the KNX IP LineMaster 760 is used as a line coupler
(x.y.0), there must be no KNX IP LineMaster in the topol-
ogy above it. For example, if a KNX IP LineMaster has

KNX IP LineMaster 760
WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 2/6
the physical address of 1.1.0, there must be no KNX IP
LineMaster with the address 1.0.0.
The KNX IP LineMaster has a filter table and thus con-
tributes to reducing bus load. The filter table is automati-
cally generated by the ETS.
Because of the speed difference between the Ethernet
(10 Mbit/s) and KNX (9.6 kbit/s), a far greater number of
telegrams can be transmitted on IP. If several consecu-
tive telegrams are transmitted on the same line, they
must be buffered in the LineMaster to avoid telegram
loss. The KNX IP Linemaster 760 has a memory for 150
telegrams (from IP to KNX).
Bus access function (KNXnet/IP Tunneling)
The KNX IP Linemaster 760 can be used as an interface
to KNX. KNX can be accessed from any point in the LAN.
For this purpose, a second physical address must be
assigned as described in the ETS Connection Manager
section.
ETS database
The following parameters can be set on the ETS:
General:
Device name:
The KNX IP LineMaster 760 can be assigned a name of
your choice. The device name should be descriptive (e.g.
Line TF). It is used to search for and recognize a device.
Monitoring bus voltage failure:
If a KNX failure is detected, it is reported on the IP. Re-
turn of the bus voltage is also reported.
Parameters: disable, enable
IP address assignment:
Automatic
(DHCP): The IP address is automatically assigned
on the DHCP, i.e. additional settings are
not required. To be able to use this func-
tion, there must be a DHCP server in the
LAN (many DSL routers have an inte-
grated DHCP server).
Manual: In this case, the IP address, the subnet
and the gateway IP address must be en-
tered manually.
IP configuration:
IP Routing Multicast Address:
This address is used for routing telegrams on IP. The
multicast IP address 224.0.23.12 was reserved
(KNXnet/IP) at the IANA (Internet Assigned Numbers
Authority) for this purpose. If a different multicast IP ad-
dress is required, it must lie within the range of 239.0.0.0
to 239.255.255.255.
IP address:
This is the IP address of the KNX IP LineMaster 760.
IP subnet:
Enter the subnet mask here. The device uses the values
entered in this mask to determine whether there is a
communications partner in the local network. If there is no
partner in the local network, the device will not send the
telegrams directly to the partner but to the gateway that
routes the telegram.
IP gateway address:
Enter the IP address of the gateway here.
Note: If the KNX IP LineMaster will only used in the local
LAN, the entry of 0.0.0.0 can remain unchanged.
Example of assigning IP addresses:
A PC is to be used to access the KNX IP LineMaster 760.
IP address of the PC: 192.168.1.30
Subnet of the PC: 255.255.255.0
The KNX IP LineMaster 760 is located in the same local
LAN, i.e. it uses the same subnet. The subnet constrains
the IP addresses that can be assigned. In this example,
the IP address of the IP LineMaster must be
192.168.1.xx, where xx can be a number from 1 to 254
(with the exception of 30, which is already in use). It must
be ensured that no numbers are assigned twice.
IP address of the IP LineMaster: 192.168.1.31
Subnet of the IP LineMaster: 255.255.255.0

KNX IP LineMaster 760
WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 3/6
Routing (KNX -> IP)
Group telegrams (main group 0 to 13):
Block: No group telegrams of this main group
are routed to IP.
Route: All group telegrams of this main group
are routed to IP independent of the filter
table. This setting is for testing purposes
only.
Filter: The filter table is used to check whether
or not the received group telegram
should be routed to IP.
Group telegrams (main groups 14 and 15):
Block: No group telegrams of main groups 14
and 15 are routed to IP.
Route: All group telegrams of main groups 14
and 15 are routed to IP.
Group telegrams (main groups 16 to 31):
Block: No group telegrams of these main groups
are routed to IP.
Route: An additional page appears on which the
routing of main groups 16 to 31 can be
disabled or enabled in pairs.
Note:
The group addresses of main groups 16 to 31 are re-
served addresses that can be used for special applica-
tions (e.g. in Easy Mode). These group addresses are not
available in the ETS.
Physically addressed telegrams:
Block: No physically addressed telegrams are
routed to IP.
Route: All physically addressed telegrams are
routed to IP.
Filter: The physical address is used to check
whether the received physically ad-
dressed telegram should be routed to IP.
Broadcast telegrams:
Block: No received broadcast telegrams are
routed to IP.
Route: All received broadcast telegrams are
routed to IP.
Acknowledge (ACK) of group telegrams:
Always: An acknowledge is generated for every
received group telegram (from KNX).
Only if
routed: An acknowledge is only generated for
received group telegrams (from KNX) if
they are routed to IP.
Acknowledge (ACK) of physically addressed telegrams:
Always: An acknowledge is generated for every
received physically addressed telegram
(from KNX).
Only if
routed: An acknowledge is only generated for
received physically addressed group tel-
egrams (from KNX) if they are routed to
IP.
Answer with
NACK: Every received physically addressed
telegram (from KNX) is responded to with
NACK (not acknowledge). This means
that communication with physically ad-
dressed telegrams on the corresponding
KNX line is not possible. Group commu-
nication (group telegrams) is not affected.
This setting can be used to block at-
tempts at manipulation.
Attention:
The setting Answer with NACK disables parameterisation
with ETS via the subline (KNX).
To reenable parameterisation via the subline (KNX), the
device has to be set into delivery status.
Routing (IP -> KNX)
Group telegrams (main groups 0 to 13):
Block: No group telegrams of these main groups
are routed to KNX.
Route: All group telegrams of this main group
are routed to KNXG independent of the
filter table. This setting is used for testing
purposes only.
Filter: The filter table is used to check whether
the received group telegram should be
routed to KNX.
Group telegrams (main groups 14 and 15):
Block: No group telegrams of main groups 14
and 15 are routed to KNX.
Route: All group telegrams of the main groups
14 and 15 are routed to KNX.
Group telegrams (main groups 16 to 31):
Block: No group telegrams of these main groups
are routed to KNX.
Route: An additional page appears on which the
routing of main groups 16 to 31 can be
disabled or enabled in pairs.
Physically addressed telegrams:
Block: No physically addressed telegrams are
routed to KNX.
Route: All physically addressed telegrams are
routed to KNX.

KNX IP LineMaster 760
WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 4/6
Filter: The physical address is used to check
whether the received physically ad-
dressed telegram should be routed to
KNX.
Broadcast telegrams:
Block: No received broadcast telegrams are
routed to KNX.
Route: All received broadcast telegrams are
routed to KNX.
Resending of group telegrams:
Disable: Group telegrams are not resent to KNX in
case of a fault.
Enable: Group telegrams are resent up to three
times in case of a fault.
Resending of physically addressed telegrams:
Disable: Physically addressed telegrams are not
resent to KNX in case of a fault.
Enable: Physically addressed telegrams are re-
sent up to three times in case of a fault.
Resending of broadcast telegrams:
Disable: Broadcast telegrams are not resent to
KNX in case of a fault.
Enable: Broadcast telegrams are resent up to
three times in case of a fault.
ETS Connection Manager
The KNX IP LineMaster 760 can only act as an interface
to KNX when the IP-configuration is valid.
The following configuration steps are required:
Select the button ‘Settings’ on the tab ‘Communication’ in
the main window of ETS4. All available connections are
listed under ‘Discovered connections’. Select the desired
connection.
The KNX IP LineMaster 760 supports up to 5 simultane-
ous tunneling connections. Each connection uses its own
physical address. The address of the first tunneling con-
nection can be changed within the ‘Local Interface Set-
tings’.
Physical addresses of the additional tunneling connec-
tions can be assigned directly on the device.
This is done by pressing the programming key on the
device (2) longer than one second. After that, the Learn-
LED will start blinking, which indicates that the assign-
ment of the additional addresses was successful.
The additional addresses are assigned as follows:
Tunneling connection 2 receives the next higher address
than tunneling connection 1, tunneling connection 3 the
next higher address than tunneling connection 2 etc..
For example:
Device address: 1.1.0 (address within ETS topology)
Connection 1: 1.1.250 (address within local settings)
Connection 2: 1.1.251 (assigned by programming key)
Connection 3: 1.1.252 (assigned by programming key)
Connection 4: 1.1.253 (assigned by programming key)
Connection 5: 1.1.254 (assigned by programming key)
All addresses have to be unique and valid within the
LineMaster’s sub line. Note: be careful not to assign the
same address as the device address for a connection.
The device address can be changed within the topology
view of the ETS software.
For new devices (i.e. in the factory settings state), only
the additional individual address of the first connection is
active with the address 15.15.250. To support multiple
concurrent connections additional address assignment is
required.
Installation and connection
The KNX IP LineMaster 760 is designed for installation in
a rack with a depth of 7 units (126 mm). It contains the
following display and control elements:
KNX LineMaster
760
1
2
3
4
5
1: LAN socket (RJ45, for Ethernet patch cable)
2: Programming key and programming – LED
3: Bus connection (KNX clamp)
4: Input for mains voltage, 230V AC / 50 Hz, L / N / PE
5: Output auxiliary voltage, 24V DC

KNX IP LineMaster 760
WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 5/6
Operation (Settings at the device)
Basic settings of the display
KNX LineMaster
IP Router & Power S.
Normal Operation
Diagnostics >
The following may be read off and set on the display
of the KNX Linemaster:
•
Reset of a line
•
Recall of the data memory with operating hours,
overcharge, external electrical surge, internal elec-
trical surge, short circuit and excess temperature
•
Recall of the operating data bus voltage, bus cur-
rent and temperature
•
Language of display
The background lighting of the display will switch off
automaticly if the temperature in the housing exceeds
50°C. This avoids an excessive thermal stress of the
device.
Line Reset
Basic setting
KNX LineMaster
IP Router & Power S.
Normal Operation
Diagnostics >
The section „Diagnostics“ will be shown when the
button is pressed once.
Line Reset > #
Data Memory >
Operating Data >
Languague >
The section „Line Reset“ will be shown when the but-
ton is pressed twice.
Reset: Yes #
No
30 seconds
Reset not active!
The cursur (flashing rectangle at right edge) can be
moved to the desired setting with the buttons or . It
can be confirmed with button.
Yes: Reset is activated. The line is
switched to neutral and short-
ed. The basic setting displays:
“Reset is active!”
No: Reset not activated. The pow-
er supply system works in
normal operation.
30 seconds: A reset of 30 seconds is start-
ed. Afterwards, the line is sup-
plied with voltage as usual.
During the reset state, which
lasts 30 seconds, the basic
setting displays: “Reset active:
XX sec” (countdown).
The button returns to the previous menu level.
Data memory
Basic setting
KNX LineMaster
IP Router & Power S.
Normal Operation
Diagnostics >
The section „Diagnostics“ will be shown when the
button is pressed once.
Line Reset >
Data Memory >#
Operating Data >
Language >
Move the cursor (flashing rectangle at right edge) to the
“Data memory” menu with the buttons and and and
confirm with key .
Hours ofOperation >#
Overload >
Ext. Overvoltage >
Int. Overvoltage >
Short circuit >
Excess Temperat. >
The cursur (flashing rectangle at right edge) can be
moved to the desired setting with the buttons and . .
It can be confirmed with button.
Operating hours
Run time: 0 years
0 day 0 hrs.
<= Back
The operating hours of the power supply system are
displayed in years, days and hours.
The button returns to the previous menu level.
Overload
Overload detected
0 times. Duration:
0 day. 0 hrs. 0 min
<= Back
The number of overload incidents and the total time in
days, hours and minutes are displayed.
The button returns to the previous menu level.
External Overvoltage
External Overvoltage
was detected
0 times.
<= Back
The number of external overvoltage incidents is dis-
played.
The button returns to the previous menu level.

KNX IP LineMaster 760
WEINZIERL ENGINEERING GmbH EN
2014-07-01 Page 6/6
Internal Overvoltage
Internal Overvoltage
was detected
0 times.
<= Back
The number of internal overvoltage incidents is displayed.
The button returns to the previous menu level.
Short Circuit
A short at the bus
was detected
0 times
<= Back
The number of short circuit incidents at the bus is dis-
played.
The button returns to the previous menu level.
Excess Temperature
Excess Temperature
on the board
was detected
0 times!
The number of excess temperature incidents on the cir-
cuit board of the device is displayed.
The button returns to the previous menu level.
Operating data
Basic setting
KNX LineMaster
IP Router & Power S.
Normal Operation
Diagnostics >
The section „Diagnostics“ will be shown when the
button is pressed once.
Line Reset >
Data Memory >
Operating Data >#
Language >
Move the cursor (flashing rectangle at right edge) to the
“Operating Data” menu with the and buttons and
and confirm with button.
Bus Voltage 29,4 V
Bus Current 320 mA
Temperature 42.1°C
The current values of
•
Bus voltage
•
Bus current
•
Temperature on the circuit board of
the device
are displayed.
The button returns to the previous menu level.
Language
Basic setting
KNX LineMaster
IP Router & Power S.
Normal Operation
Diagnostics >
The main section will be shown when the button is
pressed once.
Line Reset >
Data Memory >
Operating Data >
Language >#
Move the cursor (flashing rectangle at right edge) to the
“Language” menu with the and buttons and and
confirm with the button.
Sprache: Deutsch #
Language: English
Idioma: Espanol
Taal: Hollands
Move the cursor to the desired language with the and
buttons and press the button. The display auto-
matically jumps to the previous menu in the desired lan-
guage. With key you get back by one menu level to the
basic setting.
Factory reset
Factory default configuration:
Physical device address:
15.15.0
Number of configured tunneling connections:
1
Physical address of tunneling connection 1:
15.15.250
IP address allocation:
DHCP
It is possible to reset the device to its factory settings.
Resetting to the factory state:
•
Disconnect the power cable to
the device 230V~ (4)
•
Press and hold down the programming key (2).
•
Reconnect the power to the device.
•
Hold down the programming key (2) for at least
6 seconds.
•
A blinking programming-LED indicates the suc-
cessful restore of the factory configuration.
Weinzierl Engineering GmbH
DE-84508 Burgkirchen
E-Mail: info@weinzierl.de
Web: www.weinzierl.de
This manual suits for next models
1
Table of contents
Other Weinzierl Controllers manuals

Weinzierl
Weinzierl 5374 Specification sheet

Weinzierl
Weinzierl KNX IO 532 Specification sheet

Weinzierl
Weinzierl KNX IO 534 (4D) Specification sheet

Weinzierl
Weinzierl KNX IO 510.1 secure Specification sheet

Weinzierl
Weinzierl KNX IO 511 Specification sheet

Weinzierl
Weinzierl KNX TP Push Button 420 secure Specification sheet
Popular Controllers manuals by other brands

Federal Signal Corporation
Federal Signal Corporation SignalMaster 331105 SMC5 instructions

Avonic
Avonic AV-CON100 user manual

Newport
Newport New Focus 3502 user manual

EMUS
EMUS BMS Mini user manual

elsner elektronik
elsner elektronik KNX RF S1R-B2 compact Installation and adjustment

LYSON
LYSON HE-02N instruction manual