Klein Tools ET450T User manual

INSTRUCTION MANUAL
Advanced Circuit TracerKit
ENGLISH ET450
• TRACE ENERGIZED OR
DE-ENERGIZED WIRES
AND BREAKERS
• ADJUSTABLE
RECEIVER
SENSITIVITY
LEVELS
• AUDIBLE BEEP
ON RECEIVER
FOR SIGNAL
STRENGTH
• FLASHLIGHT ON
RECEIVER FOR
VIEWING IN LOW-
LIGHT AREAS
• TRACE WIRES
BEHIND
DRYWALL,
CEMENT BLOCK
WALL, OR
UNDERGROUND
• TRACE CONDUIT OR
PIPES
• TRACE A SINGLE WIRE
IN A BUNDLE
5001748
CAT III
600V
FRANÇAIS p. 33
ESPAÑOL pg. 17
2m

2
GENERAL SPECIFICATIONS
The Klein Tools ET450 Advanced Circuit Tracer kit is a professional tracer for
energized and de-energized breakers, fuses, and wires. When the Transmitter
is connected to a circuit, the Receiver’s sensitivity can easily be adjusted to
detect the transmitted signal on breakers, fuses, and wire through drywall,
cement block, and underground.
• Environment: Indoor. DO NOT expose to moisture, rain, or snow.
• Operating Altitude: 6562 ft. (2000 m)
• Relative Humidity: <85% non-condensing
• Operating Temp: 32°to 122°F (0°to 50°C)
• Storage Temp: -4°to 140°F (-20°to 60°C)
• Calibration: Accurate for one year
• Standards: IEC EN 61010-1, 61010-2-030.
Conforms to UL STD.61010-1, 61010-2-030;
Certified to CSA STD.C22.2 No.61010-1, 61010-2-030.
• Pollution degree: 2
• Drop Protection: 6.6 ft. (2m)
• Safety Rating: ET450T:
CATIII 600V
ET450R:
CAT III 600V, CAT II 1000V, Class II, Double insulation
CAT III: Measurement category III is applicable to test and measuring
circuits connected to the distribution part of the building’s low-voltage
MAINS installation.
CAT II: Measurement Category II is applicable to test and measuring
circuits connected directly to utilization points (socket outlets and similar
points) of the low-voltage MAINS installation.
• Electromagnetic Environment: IEC EN 61326-1. This equipment
meets requirements for use in basic and controlled electromagnetic
environments like residential properties, business premises, and light-
industrial locations.
Specifications subject to change.
ENGLISH
WARNINGS - GENERAL
To ensure safe operation and service of the meter, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
• Risk of electric shock and burn. Contact with live circuits could result in death or
serious injury.
• NEVER use the tester on a circuit with voltages that exceed the category-based
rating of this tester.
• Inspect the meter and test leads before use. DO NOT use if they appear
damaged or malfunctioning in any way
• Ensure leads are fully seated, and use caution when connecting to live circuits
• DO NOT use testers during electrical storms or in wet weather.
• Turn off testers and disconnect test leads before attempting to replace batteries.
• Turn off testers and disconnect test leads before attempting to replace the fuse.
•
To avoid electrical shock, do not operate the tester while battery door is
removed.
• DO NOT open the case, other than the battery compartment.
• Use caution when working with voltages above 25V AC RMS, or 60V DC. Such
voltages pose a shock hazard.
• ALWAYS adhere to local and national safety codes. Use personal protective
equipment to prevent shock and arc blast injury where hazardous live
connectors are exposed.
5001748

3
WARNINGS - NCV FUNCTION
• When NCV Function is initiated, a blinking or steady green glow and an audible
beep indicate voltage present. If no indication, voltage could still be present.
• Before and after each use of the NCVT, verify operation by testing a known
working circuit that is within the rating of this unit.
• Never assume neutral or ground wires are de-energized. Neutrals in multi-wire
branch circuits may be energized when disconnected and must be retested
before handling.
• The NCV tester WILL NOT detect voltage if:
• The wire is shielded.
• The operator is not grounded or is otherwise isolated from an effective earth
ground.
• The voltage is DC.
• The NCV tester MAY NOT detect voltage if:
• The user is not holding the tester.
• The user is insulated from the tester with a glove or other materials.
• The wire is partially buried or in a grounded metal conduit.
• The tester is at a distance from the voltage source.
• The field created by the voltage source is blocked, dampened, or otherwise
interfered with.
• The frequency of the voltage is not a perfect sine wave between 50 and 500Hz.
• The tester is outside of operation conditions (listed in Specifications section).
• Operation may be affected by differences in socket design and insulation
thickness and type; tester may not be compatible with some types of standard
or tamper resistant (TR) electrical outlets.
• Do not apply to uninsulated hazardous live conductors.
• Detection above 50V is specified under “normal” conditions as specified below.
The tester may detect at a different threshold at different conditions, or may not
detect at all unless:
• The tip of the tester is within 0.25" of an AC voltage source radiating
unimpeded.
• The user is holding the body of the tester with his or her bare hand.
• The user is standing on or connected to earth ground.
• The air humidity is nominal (50% relative humidity).
• The tester is held still.

4
TRANSMITTER SPECIFICATIONS
• Transmitting Frequency: 33kHz
• External Voltage Indicators: 12V, 48V, 120V, 240V, 480V
• Voltage Type Indicators: DC Positive, DC Negative, AC
• AC Frequency: 45Hz to 65Hz
• Energized/ELV Indicator: >25V AC/DC (solid), >480V AC/DC (blinking)
• Dimensions: 7.05" × 3.90" × 1.84" (179.2 × 99.1 × 46.7 mm)
• Weight (including batteries): 16.5 oz (470 g)
• Battery Type: 6 × 1.5V AA Alkaline
• Battery Life: Approximately 24 hours
• Fuse Type: 600V, 0.5A, 6 mm × 32 mm
• Auto-Power Off: After 4 hours of inactivity
Specifications subject to change.
TRANSMITTER FEATURE DETAILS
1. Power On/Off Button 7. Battery Cover with kickstand
2. External Voltage Indicators 8. "COM" Jack
3. AC/DC / Polarity Indicators 9. "+ 600V" Jack
4. Transmitting Indicator 10. Attachment Point for Optional
Magnet Holder
5. Energized/ELV Indicator
6. Low Battery Indicator
7
1
4
6
52
3
FRONT BACK
8 9
NOTE: No user-serviceable parts inside.
SYMBOLS ON TRANSMITTER
Warning Risk of electric shock
Double insulated Read Instructions
Fuse Battery orientation
Independently tested by Intertek
and meets applicable standards WEEE – Electronics disposal
Conformité Européenne:
Conforms with European
Economic Area directives
UKCA - United Kingdom
Conformity Assessment
ENGLISHENGLISHENGLISHENGLISHENGLISHENGLISHENGLISHENGLISHENGLISH
10

5
RECEIVER SPECIFICATIONS
• Detecting Frequency: 33kHz
• Sensitivity: 8 levels
• Signal Strength: 0-99 on LCD, 0-10 bar display
• Signal Indicator: Audible (tone) and visual (LED)
• Tracing depth: 0' – 1.64' (0 – 0.5 m), depending on medium/application
• NCV: 80 to 1000V AC, 50/60Hz
• Flashlight: 6 Lumens
• Dimensions: 8.72" × 2.07" × 1.51" (221.5 × 52.8 × 38.5 mm)
• Weight (including batteries): 11 oz. (312g)
• Battery Type: 4 × 1.5V AA Alkaline
• Battery Life: Approximately 28 hours
• Auto-Power Off: After 10 minutes of inactivity
Specifications subject to change.
SYMBOLS ON RECEIVER
Warning Risk of electric shock
Double insulated Read Instructions
Conformité Européenne:
Conforms with European
Economic Area directives
UKCA - United Kingdom
Conformity Assessment
Independently tested by Intertek
and meets applicable standards
WEEE – Electronics disposal Battery orientation
RECEIVER FEATURE DETAILS
6.Battery Cover
7.Crosshair Grooves
8.
NCV Signal / Tracing Signal Indicator
9.Flashlight
10.Lanyard Hole
11.Numerical Signal Strength (0-99)
12.Bar graph (Signal Strength)
13.Sensitivity Level (1-8)
14.Non-Contact Voltage Indicator
15.Hazardous Voltage Indicator
16.Auto-Power Off (APO) Indicator
17.Battery Status Indicator
18.Mute Indicator
1. Power On/Off / Backlight Button
2. Flashlight/Mute Button
3. NCV Button
4. Increase Sensitivity Button
5. Decrease Sensitivity Button
1
2
3
5
4
8
FRONTBACK
6
10
LCD
15
13
1716 18
14
11
12
TOP
7
9
NOTE: No user-serviceable
parts inside.

6
ENGLISH
A. Blade Prongs (Red ×1, Black ×1)
B. Ground Prong
C. Alligator Clips (Red ×1, Black ×1)
D. 3' (0.9 m) Lead Adapters (Red ×1, Black ×1)*
E. 20' (6 m) Lead Adapter*
F. AC Plug Leads
TEST LEAD KIT AND ACCESSORIES
A. B. C.
*NOTE: Lead Adapters
D
and
E
can all be connected end-to-end
for additional length when needed.
D.
E.
F.

7
TRANSMITTER FUNCTION BUTTONS
ON/OFF
To power ON the Transmitter, long-press the ON/OFF button
1
.
The Transmitting Indicator
4
will blink, indicating that it is transmitting, and
the Energized/ELV Indicator
5
and the External Voltage Indicators
2
will
illuminate in the presence of voltage greater than 25V AC/DC. By default, the
Transmitter will automatically power off after 4 hours of inactivity. To power
OFF the Transmitter, long-press the ON/OFF button
1
for 2 seconds.
If the Energized/ELV Indicator
5
is blinking, voltage greater
than 480V AC/DC is detected. DISCONNECT TRANSMITTER FROM
CIRCUIT IMMEDIATELY.
RECEIVER FUNCTION BUTTONS
ON/OFF
To power ON the Receiver, long-press the ON/OFF Button
1
. To power OFF
the Receiver, long-press the ON/OFF Button
1
.
The Auto-Power Off icon will be visible on the display. By default, the tester will
automatically power off after 10 minutes of inactivity.
BACKLIGHT
Short-press the
ON/OFF Button
1
to turn the LCD backlight on/off.
SENSITIVITY LEVELS
Press the Increase Sensitivity
4
and Decrease Sensitivity
5
buttons to
select one of the Receiver’s 8 sensitivity levels (level 8 is highest sensivity,
level 1 is lowest).
NOTE: Energized circuits typically use sensitivity levels 1-3, and
de-energized circuits may need higher sensitivity levels 4-8.
NCV
Power on the Receiver, and press the NCV Button
3
to put the Receiver
into NCV mode. Place the tip of the Receiver near the target area, or place the
wire on the tip of the Receiver to determine if the wire is energized. When an
energized wire is detected, the Bar Graph
12
will illuminate in relation to the
signal strength, the Green indicator LED will illuminate, and the speaker will
emit an audible signal.
NOTE: The Transmitter is not needed for NCV Mode.
MUTE
Long-press and hold the Flashlight/Mute Button
2
to mute/unmute audible
signals.
FLASHLIGHT
Short-press the Flashlight/Mute Button
2
to turn the flashlight on/off.

8
ENGLISH
OPERATING INSTRUCTIONS
Before testing, verify the Receiver is functioning properly by placing
it near the powered Transmitter. With the Receiver set to Sensitivity
Level 8, a numerical reading of 99, all 10 signal strength bars lit up,
and a strong audible signal confirms the system is working. The
Receiver will produce a variable beep proportional to the sensitivity
value. The higher the signal strength, the faster it will beep.
NOTE: A continuous beep or solid-on LED indicates strongest
possible signal of 99 and the Receiver is saturated.
NOTE: If the Transmitter is powered up normally but the Receiver
detects a very low signal level, even when set to the highest
sensitivity level, the internal protection fuse in the Transmitter
should be checked, as it may be blown.
CONNECTING TEST LEADS
Connect test leads by inserting the black lead into the "COM" jack and
the red lead into the "+ 600V" jack. Do not test if leads are improperly
seated. Results could cause intermittent display readings. To ensure
proper connection, firmly press leads into the input jack completely.
NOTE: Test leads used must have a CAT III 600V safety rating.
INCORRECT
CORRECT

9
OPERATING INSTRUCTIONS
TRANSMITTER DIRECT AND REMOTE GROUND CONNECTION METHODS
DIRECT GROUND: In a direct ground connection, a plug or clips can
be connected to the hot and neutral wires on the same circuit.
NOTE: While locating a breaker, the wires will not be as traceable due
to the cancellation effects of the wires running parallel.
REMOTE GROUND: Preferred for optimum signal strength. To optimize
the transmitted signal and avoid cancellation effects which occur in a
direct ground connection, a remote ground connection should be used.
Attach the Ground Prong
B
to the 20' (6 m) Lead Adapter
E
and
connect to the ground of an outlet on a different circuit. Attach the red
Blade Prong
A
to the red test lead
D
and connect to the hot wire of
the circuit you are tracing.
NOTE: This Remote Ground connection method will trip GFCI receptacles.
Several workarounds are available: Use the Direct Ground method,
connect directly to wires with alligator clips
C
, or de-energize circuit by
turning off breaker at the panel.
B
A
E D
F

10
ENGLISH
OPERATING INSTRUCTIONS
RECEIVER ORIENTATION
The orientation of the Receiver in relation to the wire being traced is very
important. The vertical Crosshair Groove
7
on the tip of the Receiver
indicates the preferred direction of the wire for the strongest signal
detection. While tracing a wire, rotate the Receiver to always ensure the
highest signal value is displayed. The signal may not be detected if the
Receiver tip is not properly aligned to the wire. If the signal drops, the wire
may have changed direction (horizontal to vertical or vertical to horizontal).
Whenever possible, keep the Receiver at least 3' (0.9 m) away from the
Transmitter and test leads to reduce signal interference.
APPLICATIONS
Circuit Breaker Finder (energized and de-energized)
1. Connect the Transmitter to the circuit to be identified using either the direct
ground or remote ground connection and power the Transmitter on. The
direct ground and remote ground connection methods can be used on both
energized and de-energized circuits, but an energized circuit produces a higher
signal strength.
2. Verify that the Energized Indicator on the Transmitter is illuminated if
connected to a circuit with voltage above 25V AC/DC and is not illuminated for
de-energized circuits.
3. Go to the electrical panel and power on the Receiver. If there is more than one
panel, touch the tip of the Receiver to each panel cover to identify the panel
with the highest signal level. Use the Increase Sensitivity
4
and Decrease
Sensitivity
5
buttons to adjust the Receiver sensitivity level to identify the
panel with the highest reading.
4. Once the panel has been identified, open the cover.
5. Orient the Receiver facing left or right and perpendicular to the breakers (See
below). Slowly move the Receiver up and down in front of each breaker. Use
the Increase Sensitivity
4
and Decrease Sensitivity
5
buttons to adjust the Receiver sensitivity levels as
needed to locate the breaker with the highest reading.
After any sensitivity level changes, rescan all the
breakers to find the breaker with
the highest reading.
NOTE: Energized circuits typically use
sensitivity levels 1-3, and de-energized circuits may need
higher sensitivity levels 4-8.
NOTE: If two or more breakers have the same signal value,
remove the panel cover and place the tip of the Receiver on
the individual wires to help in determining the correct breaker.
NOTE: Ensure the wire is held in the proper orientation in
relation to the tip of the Receiver.
WIRE
7

11
OPERATING INSTRUCTIONS
TRACING WIRES
1. Connect the Transmitter to the circuit to be traced and power on
the Transmitter.
NOTE: The direct ground and remote ground connection methods
can be used on both energized and de-energized circuits, but an
energized circuit produces a higher signal strength.
2. Power on the Receiver, and use the Increase Sensitivity button
4
to set the Sensitivity Level to 8 (highest level).
3. Starting a few feet from the Transmitter, slowly move the Receiver
around to locate the direction of the strongest signal. The wires may
be located behind the wall, in the ceiling, or underneath the floor.
NOTE: If the signal strength displays “99”, the signal is saturated.
Use the Decrease Sensitivity button
5
to reduce the sensitivity level.
NOTE: If the signal strength is too weak, use the Remote Ground
connection method (if not done already) to strengthen the signal.
4. Continue to follow the location of the highest signal strength until
the destination is reached.
NOTE: If the circuit is de-energized, the Transmitter can be
connected to the neutral and ground wires, which will create a
stronger closed loop signal, as neutral and ground are bonded
together at the panel.
TRACING LOW VOLTAGE AND DATA CABLES
Follow the same steps outlined for Tracing wire above, with the wires
de-energized and utlizing a remote ground connection method.
NOTE: For shielded cables, connect the red test lead to the shield
of the cable being traced. Ground the far end of the cable shield if
possible.
FINDING OPENS/BREAKS
Follow the same steps outlined for Tracing wire above, except make
sure to ground any other wires running in parallel with the wire being
traced. Follow the signal strength until you observe it starting to drop
off. Use the sensitivity arrow keys to lower the sensitity level to pin
point the location of the open/break.

12
ENGLISH
OPERATING INSTRUCTIONS
TRACING WIRES INSIDE METAL CONDUIT
Due to metal conduit shielding the wire being traced, the Receiver
will be prevented from picking up the signal from the Transmitter. To
trace wire inside of metal conduit:
1. Connect the Transmitter to the circuit to be traced and power on
the Transmitter.
2. Power on the Receiver, and use the Increase Sensitivity button
4
to set the Sensitivity Level to 8 (highest level).
3. Hold the Receiver in front of junction boxes to check for the signal
being transmitted from the Transmitter.
4. If there is no signal detected, the junction box may need to be opened
so that the tip of the Receiver can be held in front of each wire.
5. Continue along each junction box until the destination is reached
or until the end of the circuit.
NOTE: If the conduit is non-metallic, the standard wire tracing
steps can be followed.
MAPPING A CIRCUIT
1. Turn off the breaker of the circuit being traced.
2. Remove the hot wire from the circuit breaker and connect the red
test lead of the Transmitter to the wire.
3. Connect the black test lead of the Transmitter to a remote ground
(see the Direct and Remote Ground connection methods sections)
and then power on the Transmitter.
4. Starting a few feet from the Transmitter, use the tip of the Receiver
to scan face plates of receptacles, wires, and other loads.
NOTE: If the signal strength displays “99”, the signal is saturated.
Use the Decrease Sensitivity button
5
to reduce the sensitivity level.
NOTE: If the signal strength is too weak, use the Remote Ground
connection method (if not done already) to strengthen the signal.
Any locations which indicate a signal are connected to the specific
breaker.

13
OPERATING INSTRUCTIONS
IDENTIFYING SINGLE CONDUCTOR (SORTING BUNDLED WIRES)
1. Attach the red Blade Prong
A
to the red test lead
D
and connect
to the known end of the wire to be traced.
2. Connect the black test lead
D
to a remote ground using the
Ground Prong
B
or black alligator clip
C
(see Remote Ground
connection method section), then power on the Transmitter.
3. Power on the Receiver, and use the Increase Sensitivity
4
and
Decrease Sensitivity
5
buttons to set the Sensitivity Level to 1-3.
4. Go to the other end of the cable, and one by one, pull each wire
away from the others, and touch the tip of the Receiver to the
wire. Ensure the wire is held in the proper orientation in relation
to the tip of the Receiver.
NOTE: If the signal strength displays “99”, the signal is saturated.
Use the Decrease Sensitivity button
5
to reduce the sensitivity level.
NOTE: If the signal strength is too weak, use the Remote Ground
connection method (if not done already) to strengthen the signal.
5. If multiple wires have the same sensitivity reading, pull back the
wires to separate them more if possible.
6. The highest signal value indicates the correct wire.
C
D

14
OPERATING INSTRUCTIONS
TRACING UNDERGROUND
1. Connect the Transmitter to the circuit to be traced and power on
the Transmitter.
NOTE: The Receiver may not detect and trace easily through metal
conduit/pipe or shielded cables. If the conduit is metal, or the wire
is shielded, connect to the shield or conduit instead.
NOTE: For the strongest signal, the remote ground connection
method should be used.
NOTE: Leaving the circuit energized provides a stronger signal and
assists in tracing.
2. Power on the Receiver, and use the Increase Sensitivity button
4
to set the Sensitivity Level to 8 (highest level).
3. Starting a few feet from the Transmitter, hold the Receiver
perpendicular to the ground and slowly move it around using a
sweeping motion to locate the highest signal value. Pay close
attention to the orientation of the Receiver in relation to the wire
being traced. The signal may not be detected if the Receiver tip is
not properly aligned to the wire. If the signal drops, the wire may
have changed direction.
NOTE: If the signal strength displays “99”, the signal is saturated.
Use the Decrease Sensitivity button
5
to reduce the sensitivity level.
NOTE: If the signal strength is too weak, use the Remote Ground
connection method (if not done already) to strengthen the signal.
ENGLISH
B E
D
C

15
BATTERY REPLACEMENT
TRANSMITTER
When the Low Battery Indicator
6
illuminates, the batteries must be
replaced:
1. Loosen 2 screws and remove Battery Cover
7
.
2. Remove and recycle spent batteries.
3. Install 6 new AA 1.5V batteries (4 inside battery door, 2 inside unit
housing), noting proper polarity.
4. Replace Battery Cover and tighten screws. Do not overtighten.
RECEIVER
When the Battery Status Indicator
17
shows only 1 bar, the batteries
must be replaced.
1. Loosen screw and remove Battery Cover
7
.
2. Remove and recycle spent batteries.
3. Install 4 new AA 1.5V batteries, noting proper polarity.
4. Replace Battery Cover and tighten screws. Do not overtighten.
FUSE REPLACEMENT
A fuse may blow if more than 600V energized is applied to the ET450
Transmitter. To access fuse:
1. Loosen 2 screws and remove Battery Cover
7
.
2. Replace blown fuse with 500mA/600V fast-blow, interrupting
rating 50kA.
3. Replace Battery Cover and tighten screws. Do not overtighten.
To avoid risk of electric shock:
•
Disconnect leads from any voltage source before removing
battery cover.
•
Do not operate while battery cover is removed.

16
ENGLISH
CLEANING
Be sure tester is turned off and wipe with a clean, dry lint-free
cloth.
Do not use abrasive cleaners or solvents.
STORAGE
Remove batteries when the equipment is not in use for a prolonged period
of time. Do not expose to high temperatures or humidity. After a period
of storage in extreme conditions exceeding the limits mentioned in the
General Specifications section, allow the tester to return to normal operating
conditions before using.
WARRANTY
www.kleintools.com/warranty
DISPOSAL /RECYCLE
Do not place equipment and its accessories in the trash.
Items must be properly disposed of in accordance with local
regulations. Please see www.epa.gov/recycle for additional
information.
CUSTOMER SERVICE
KLEIN TOOLS, INC.
450 Bond Street Lincolnshire, IL 60069
1-800-553-4676
www.kleintools.com

17
MANUAL DE INSTRUCCIONES
Kit de rastreador
avanzadodecircuitos
ESPAÑOL ET450
5001748
CAT III
600 V
• RASTREE CABLES ENERGIZADOS
O DESENERGIZADOS Y
CORTACIRCUITOS
• NIVELES
AJUSTABLES DE
SENSIBILIDAD
DELRECEPTOR
• PITIDO AUDIBLE EN
EL RECEPTOR PARA
LA INTENSIDAD
DESEÑAL
• LINTERNA EN EL
RECEPTOR PARA
VER EN LUGARES
CON POCA LUZ
• RASTREE CABLES
DETRÁS DE PLACAS
DE YESO, PAREDES
DE BLOQUES
DE CEMENTO, O
DEBAJO DEL SUELO
• RASTREE TUBOS CONDUIT
OTUBERÍAS
• RASTREE UN ÚNICO CABLE
ENUNGRUPO
2m

18
ESPAÑOL
ESPECIFICACIONES GENERALES
El kit de rastreador avanzado de circuitos ET450 de Klein Tools es un rastreador
profesional para cortacircuitos, fusibles y cables energizados y desenergizados.
Cuando se conecta el transmisor a un circuito, la sensibilidad del receptor se puede
ajustar fácilmente para detectar la señal transmitida en cortacircuitos, fusibles y
cables a través de placas de yeso, bloques de cemento y por debajo del suelo.
• Entorno: interiores. NO exponga a la humedad, lluvia o nieve.
• Altitud de funcionamiento: 6562' (2000 m)
• Humedad relativa: <85%, sin condensación
• Temperatura de funcionamiento: 32 a 122°F (0 a 50°C)
• Temperatura de almacenamiento: -4 a 140°F (-20 a 60°C)
• Calibración: precisa durante un año
• Normas: IECEN61010-1, 61010-2-030.
Cumple con las normas UL STD.61010-1, 61010-2-030;
Certificado según STD STD.C22.2 n.ºNo.61010 -1 -1, 61010-2-030.
• Grado de contaminación: 2
• Protección ante caídas: 6,6'(2m)
• Clasicación de seguridad:
ET450T: CATIII, 600V
ET450R:
doble aislamiento CAT III 600 V, CAT II 1000 V, clase II
CAT III: La categoría III de medición es aplicable a los circuitos de
medición y prueba conectados a la distribución de la instalación de redes
eléctricas de bajo voltaje de un edificio.
CAT II: La categoría II de medición es aplicable a los circuitos de medición
y prueba conectados directamente a puntos de utilización (tomacorrientes
y puntos similares) de la instalación de red de bajo voltaje de un edificio.
• Entorno electromagnético: IEC EN 61326-1. Este equipo cumple con
los requisitos para su uso en entornos electromagnéticos básicos y
controlados, como propiedades residenciales, establecimientos comerciales
e instalaciones de industria ligera.
Especificaciones sujetas a cambios.
ADVERTENCIAS GENERALES
Para garantizar un funcionamiento y servicio seguros del multímetro,
siga estas instrucciones. El incumplimiento de estas advertencias puede
provocar lesiones graves o la muerte.
• Riesgo de choque eléctrico y quemaduras. El contacto con los circuitos activos
podría provocar lesiones graves o mortales
• NUNCA debe utilizar este probador en un circuito con voltajes que excedan la
clasificación correspondiente a la categoría del probador.
• Inspeccione el multímetro y los cables de prueba antes de su uso. NO los utilice si en
apariencia están dañados o si de algún modo tienen un funcionamiento incorrecto.
• Asegúrese de que los cables estén correctamente ubicados y proceda con
precaución cuando se conecte a circuitos activos.
• NO utilice el probador durante tormentas eléctricas o en clima húmedo.
• Apague el probador y desconecte los cables de prueba antes de intentar
reemplazar las baterías.
• Apague el probador y desconecte los cables de prueba antes de intentar
reemplazar el fusible.
• Para evitar choques eléctricos, no haga funcionar el probador sin colocar la tapa
del compartimiento de las baterías.
• NO abra la carcasa, excepto el compartimiento de las baterías.
• Proceda con precaución cuando trabaje con voltajes superiores a 25 V CA RMS
o 60 V CD. Esos voltajes implican un riesgo de choque eléctrico.
• Cumpla SIEMPRE con los códigos de seguridad locales y nacionales. Utilice
equipo de protección personal para prevenir lesiones por choque y arco
eléctrico en los lugares donde haya conectores activos peligrosos expuestos.
5001748

19
ADVERTENCIAS SOBRE LA FUNCIÓN NCV
• Cuando la función NCV está activa, una luz verde intermitente o continua y un
indicador audible alertan de que hay voltaje. Aun cuando el instrumento no lo
indique, es posible que haya voltaje.
• Antes y después de cada uso del NCVT, verifique el funcionamiento realizando
una prueba en un circuito activo que se encuentre dentro de la capacidad de
esta unidad.
• Nunca suponga que los cables neutro y de puesta a tierra están desenergizados.
Los neutros en circuitos derivados de cables de múltiples alambres pueden
estar energizados aunque estén desconectados y deben volver a probarse antes
de manipularlos.
• El probador NCV NO detectará voltaje en las siguientes situaciones:
• Si el cable está blindado.
• Si el operador no está conectado a tierra o está aislado de alguna manera de
una toma de tierra eficaz.
• Si el voltaje es de CD.
• Es posible que el probador NCV NO detecte voltaje en las siguientes
situaciones::
• Si el usuario no sostiene el probador.
• Si el usuario está aislado del probador mediante un guante u otro material.
• Si el cable está parcialmente enterrado o en un conducto de metal conectado
a tierra.
• Si el probador se encuentra a cierta distancia de la fuente de voltaje.
• Si el campo creado por la fuente de voltaje está bloqueado, amortiguado o
sometido a interferencia de alguna otra manera.
• Si la frecuencia de voltaje no es una onda sinusoidal perfecta entre 50 y
500Hz.
• Si el probador se encuentra fuera de las condiciones de funcionamiento
(descritas en la sección Especificaciones).
• El funcionamiento puede llegar a verse afectado por las diferencias en el diseño
del enchufe y el tipo y grosor del aislamiento. Es posible que el probador no sea
compatible con algunos tipos de soportes o tomacorrientes inviolables.
• No utilice en conductores activos peligrosos sin aislamiento.
• La detección por encima de 50 V se especifica en condiciones "normales"
como se indica más adelante. El probador puede detectar voltaje en un umbral
distinto, en diferentes condiciones, o puede no detectar voltaje en absoluto a
menos que:
• La punta del probador está dentro de 0,25" de una fuente de voltaje de CA que
irradia sin impedimento.
• El usuario sostiene el cuerpo del probador con la mano descubierta.
• El usuario está parado sobre una toma de tierra o conectado a ella.
• La humedad del aire es nominal (50 % de humedad relativa).
• El probador se sostiene firmemente para mantenerlo inmóvil.

20
ESPECIFICACIONES DEL TRANSMISOR
• Frecuencia de transmisión: 33kHz
• Indicadores de voltaje externo: 12V, 48V, 120V, 240V, 480V
• Indicadores de tipo de voltaje: CD positiva, CD negativa, CA
• Frecuencia CA: 45Hz a 65Hz
• Indicador de Energizado/ELV: >25VCA/CD (sólido), >480VCA/CD (intermitente)
• Dimensiones: 7,05" × 3,90" × 1,84" (179,2 × 99,1 × 46,7mm)
• Peso (incluye baterías): 16,5oz (470g)
• Tipo de batería: 6×1,5VAA alcalina
• Vida útil de la batería: aproximadamente 24horas
• Tipo de fusible: 600V, 0,5A, 6mm×32mm
• Función de apagado automático: después de 4horas de inactividad
Especificaciones sujetas a cambios.
DETALLES DE LAS CARACTERÍSTICAS DEL TRANSMISOR
1.Botón de encendido y apagado 7.Cubierta del compartimiento de
2.Indicadores de voltaje externo las baterías con pie de apoyo
3.Indicadores de polaridad 8.Conector “COM” (Común)
deCA/CD 9.Conector “+600V”
4.Indicador de transmisión 10.Punto de ajuste para soporte
5.Indicador de Energizado/ELV magnético opcional
6.Indicador de batería baja
VISTA FRONTAL VISTA TRASERA
NOTA: No contiene en su interior piezas que el usuario pueda reparar.
SÍMBOLOS EN EL TRANSMISOR
Advertencia Riesgo de choque eléctrico
Doble aislamiento Lea las instrucciones
Fusible Orientación de la batería
Sometido a pruebas de forma
independiente por Intertek;
cumple con las normas aplicables
WEEE – Eliminación de
elementos electrónicos
Conformité Européenne:
Cumple con las normas del
Espacio Económico Europeo
UKCA - Conformidad
evaluada por el Reino Unido
7
1
4
6
52
3
8 9
ESPAÑOL
10
This manual suits for next models
3
Table of contents
Languages:
Other Klein Tools Circuit Tester manuals