manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. KLINGER
  6. •
  7. Measuring Instrument
  8. •
  9. KLINGER ULM User manual

KLINGER ULM User manual

Other KLINGER Measuring Instrument manuals

KLINGER CMF V Series User manual

KLINGER

KLINGER CMF V Series User manual

KLINGER E-ST User manual

KLINGER

KLINGER E-ST User manual

KLINGER Minimag User manual

KLINGER

KLINGER Minimag User manual

KLINGER US201 User manual

KLINGER

KLINGER US201 User manual

KLINGER PS116 User manual

KLINGER

KLINGER PS116 User manual

KLINGER KSCIFBCD User manual

KLINGER

KLINGER KSCIFBCD User manual

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.klinger.dk
Side 1
Ultrasonic Level Meter
Operation Manual
Ultrasonic Level Meter
Type ULM
Operation Manual
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.klinger.dk
Side 2
Ultrasonic Level Meter
Operation Manual
Content
1.General Information ....................................................................................… 3
2.Technical Data..............................................................................................… 9
3.Mechanical Installation……..…….….…..….…..…..…..…………...……...………………… 10
4.Electrical wiring and Setup ..........................................................................… 35
5.Programming...................................................................….….…………………….. 41
6.Faults …….………….……………………………………….…………………………………………… 52
7.Level Difference Masurement ………………………………………………………………… 53
8.Warranty Card ……………………………………..………….….………………………………….. 58
8.Using the Echo pattern …………………………………………………………….….…………. 60
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 3
Ultrasonic Level Meter
Operation Manual
Operating Instructions for Simple Settings of
Ultrasonic Level Meter Menus
Notes: as the product is renewed continuously, it cannot be ensured that the product
manual and installation manual are in line with the latest product.
The Company cannot inform every client of the change (if any) in product itself and its
operation instructions. Please directly contact the corporate sales personnel for any
needs. The change includes but is not limited to the following:
Product blind area, performance parameters, functions, structure, shape, color, etc.
Software functions, structure, display mode, operating habit, etc. Any operation on the
hardware must be conducted after power off.
Failures, like short circuit, caused by power-on operation are beyond the range of warranty.
The uncapping operations must be conducted after power off and no liquid is allowed to
enter in the meter. Any failure caused by the entering in of liquid is beyond the range
of warranty.
Normally the ultrasonic level meter produced by the company shall be installed as per
the installation requirements of the manual and after that, the equipment can be normally
used only after the following several parameters are set.
There are three buttons on the panel, via which the meter can be adjusted. The measured
values are displayed on the LCD screen after the adjustment.
SET
Button Button
◇Enter menu item ◇Move cursor
◇Confirm menu item ◇Choose menu item
◇Confirm parameter modification ◇Modify parameter
(1)After power-on display of the meter, long press the set button (SET) for 2s to enter in
the main menu.
The menu modes include expert setting mode and simply setting mode.
The menu query table of simple setting mode is as shown in the table below.
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 4
Ultrasonic Level Meter
Operation Manual
你
The menu query table of expert setting mode is shown in “VI. Menu
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 5
Ultrasonic Level Meter
Operation Manual
Interface & Operating Instructions: ”.
(2) Select measuring mode:
Measuring modes are divided into distance measuring mode and material
level measuring mode. And the factory default is material level
measurement.
(3)Input probe height value to “reference zero point” (probe height is the
distance from probe emitting surface to tank bottom or pool bottom).
①Under distance measuring mode, setting of reference zero point is
meaningless and the positions of maximum of measuring range and
minimum of measuring range are as shown in Fig. 1.1.
②Under material level measuring mode, the positions of reference zero
point, maximum of measuring range and minimum of measuring range are
as shown in Fig. 1.2.
Fig. 1.1 Diagram of Distance Measurement
Fig. 1.2 Diagram of Material Measurement Level
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 6
Ultrasonic Level Meter
Operation Manual
你
Minimum of measuring range: it is the value of distance between the reference
plane to the position, which is positive when the minimum of measuring range is
above the reference plane and negative when the minimum of measuring range is
below the reference plane. The output current is 4mA when the liquid level is at
such position.
Maximum of measuring range: it is the value of distance between the reference
plane to the position, which is positive when the maximum of measuring range is
above the reference plane and negative when the maximum of measuring range is
below the reference plane. The output current is 20mA when the liquid level is at
such position.
(4)Operating with relay: enter in the alarm settings and set three parameters:
①Alarm mode: select high level alarm, low level alarm or off.
②Alarm value: high level alarm: alarm given when the liquid level is above the alarm
value
Low value alarm: alarm given when the liquid level is below the alarm value
③Return difference value: it is used to prevent the repeated switching of alarm switch
near the alarm point caused by measurement error.
High level alarm state: alarm cancelled when the liquid level is less than (alarm value
- return difference value)
Low level alarm state: alarm cancelled when the liquid level is greater than (alarm
value + return difference value)
(5)Please set the options of probe selection, parameter correction and algorithm selection
under the instruction of professional technicians.
(6)The installed equipment must be grounded truthfully and independently and shall not
share the public grounding with electrical cabinet or meter box.
(7)Suggestions: when the ultrasonic level meter is connected with the frequency
converter, PLC and other equipment with interference, the power supply part
shall be added with isolation transformer, signal part shall be added with signal
isolator and reliable grounding shall be provided.
★The signal line shall not be wired in the same trunking with the power line and it shall
be installed independently through metal tube or far away from the power line. If the
signal line is not installed through tube independently, it shall be kept at least 1m away
from the power line.
Diagram description:
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 7
Ultrasonic Level Meter
Operation Manual
★This is an important prompt which shall be carefully read and
strictly followed as per the requirements.
▲This is a common prompt which needs to be carefully read to
avoid troubles during use.
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 8
Ultrasonic Level Meter
Operation Manual
你
I. Product Introduction
Ultrasonic level meter (for material and liquid level measurement) is a
non-contact highly reliable and cost-effective material level measuring
instrument which is easily installed and maintained. It can meet most of the
material level measurement requirements without touching the medium. It is
a new generation ultrasonic level meter with fully independent property
rights developed by the company via years of hard work.
II. Commissioning
As the meter installation site environment is different, the basic information
of measurement to be done must be learnt before the operation of the ultrasonic
level meter, such as the measuring range, zero point, full scale and site
conditions. Therefore, the meter must be set before measurement and the
specific settings are detailed in “Operating Instructions for Simple Settings
of Ultrasonic Level Meter Menus” in Page 1.
Others: please do not modify probe selection, parameter correction and
algorithm selection without permission.
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 9
Ultrasonic Level Meter
Operation Manual
III. Main Technical Indicators
KLINGER Denm ark A/S | Nyager 12-14 | DK-2605 Brøndby | +45 43 64 66 11 | salesinstrumentation@kl inger.dk | www.kl inger.dk
Side 10
Ultrasonic Level Meter
Operation Manual
Remarks: this series of ultrasonic probe can also be customized as per client's
demand and the customized probes are probes with special specification
requirements, such as resistance to high pressure, resistance to high
temperature, small diameter and small blind area.
IV. Installation Guide
4.1 Installation dimension of level meter
⑴Standard separate-type ultrasonic level meter:
Object Picture Structural Drawing
(2)Enhanced integrated-type ultrasonic level meter