SSS-1000 Series 1 Installation Guide
2-3/4” (70 mm)
3-1/2”
(89 mm)
7/16”
(11 mm)
1/4”
(6 mm)
thick foam gasket
1-1/2”
(38 mm)
for SSS-101x
or
1-1/4”
(32 mm)
for SSS-100x
3-5/32”
(80 mm) for SSS-10x2
5-13/32”
(137 mm) for SSS-10x3
7-21/32” (195 mm) for SSS-10x4
9-29/32”
(252 mm) for SSS-10x5
1/4" nipple
(SSS-100x)
for 3/8" OD
polyethylene
tubing or
3/16" nipple
(SSS-101x) for
1/4" OD tubing
Mounting Holes, 3/16” (5 mm)
Installation Guide
Differential Pressure Flow Pickup Tubes
SSS-1000 Series
Mounting for Differential Pressure Flow
To mount the pickup tubes for differential pressure:
1. Determine the duct’s ow direction and install the
pickup tubes based on the ow arrow imprint.
NOTE: The pickup tubes must be mounted with the
FLOW arrow imprint pointing in the direction of
the air ow.
2. Cut a 7/8" (22 mm) hole in the duct to accept the pickup
tubes.
3. Attach the pickup tubes to the duct using two self-
tapping screws inserted through the 3/16" (5 mm)
mounting holes.
Connections
Use appropriately sized polyethylene tubing to connect the
pickup tubes to the controller:
• For connecting SSS-10xx pickup tubes with CSC-3000
series, CSP-4000/5000 series, KMD-7000 series, and
BAC-7000/8000/9000 series controllers, use a barb
union adapter and tubing sized appropriately to the
pickup tubes and controller. For maximum accuracy in
the CSP-5000 series, KMD-7000 series, and BAC-7000
series controllers, the 3/8" OD tubing between the
pickup tubes and the adapter should be as short as
possible, and the 1/4" OD tubing from the adapter to
the controller should be 24" long (on both the High and
the Low sides).
• OR use the equivalent SSS-101x pickup tubes and just
1/4" OD tubing (no adapter is necessary). For maximum
accuracy in the CSP-5000 series, KMD-7000 series, and
BAC-7000 series controllers, the 1/4" OD tubing from
the pickup tubes to the controller should be 24" long
(on both the High and the Low sides).
NOTE: For other controllers, the length of the tubing
should not be longer than necessary.
NOTE: CSC-2000 series controllers have ports for 3/8"
tubing (the same as the SSS-10xx pickup tubes).
Check that there are no sharp bends in the tubing at any
connection. Bends and creases may leak as tubing ages.
1. Connect the Port “H” to the “High” input on the VAV
controller.
2. Connect the Port “L” to the “Low” input on the VAV
controller.
1-3/8” (35 mm) 1-3/8” (35 mm)
Drill two holes for self-tapping screws inserted through
the pickup tubes’3/16” (5 mm) mounting holes.
Cut 7/8”
(22 mm)
diameter
NOTE: This installation guide is for installing SSS-10xx models. For guidance in installing SSS-111x models,
see the KMC Conquest Airow Measurement System Installation Guide.
SSS-1000 Series 2 Installation Guide
Connections
Using appropriately sized polyethylene tubing, connect
either the H or L port on the pickup tubes to the High port
on the controller.
NOTE: The other port of the pickup tubes is left
unconnected and open to air.
NOTE: Tubing should be free of kinks and restrictions.
Mounting for Static Pressure
To mount the pickup tubes for static pressure:
1. Determine the duct’s ow direction and install the
pickup tubes so that the FLOW arrow imprint is
perpendicular to the direction of the air ow.
NOTE: The FLOW arrow imprint on the pickup tubes can
point either up or down.
NOTE: It is recommended that an indication or marking
be applied to the SSS-10xx probe to indicate the
intended orientation.
2. Cut a 7/8" (22 mm) hole in the duct to accept the pickup
tubes.
3. Attach the pickup tubes to the duct using two self-
tapping screws inserted through the 3/16" (5 mm)
mounting holes.
NOTE: If mounting SSS-10xx pickup tubes perpendicular
to a relatively small diameter round duct,
take care not to break the pickup tubes by
overtightening the screws and overexing the
plastic mount.
CSP-4702
24 VAC
Bypass Damper
To Low Pressure Port
on Pitot Tube
OR
to H or L Port on
SSS-101x Pickup Tubes
(Mounted Perpendicular
to Air Flow)
To HI Port on CSP-4702 1/4" Tubing
Optional Remote Setpoint Input to Building Automation System
Optional Pressure Reading Output to Building Automation System
SSS-101x Pickup Tubes
Air Handler Unit (AHU)
or
Roof Top Unit (RTU)
Supply Air
Return Air
2-3/4” (70 mm)
3-1/2”
(89 mm)
7/16”
(11 mm)
1/4”
(6 mm)
thick foam gasket
1-1/2”
(38 mm)
for SSS-101x
or
1-1/4”
(32 mm)
for SSS-100x
3-5/32”
(80 mm) for SSS-10x2
5-13/32”
(137 mm) for SSS-10x3
7-21/32” (195 mm) for SSS-10x4
9-29/32”
(252 mm) for SSS-10x5
1/4" nipple
(SSS-100x)
for 3/8" OD
polyethylene
tubing or
3/16" nipple
(SSS-101x) for
1/4" OD tubing
Mounting Holes, 3/16” (5 mm)
1-3/8” (35 mm) 1-3/8” (35 mm)
Drill two holes for self-tapping screws inserted through
the pickup tubes’3/16” (5 mm) mounting holes.
Cut 7/8”
(22 mm)
diameter
SSS-1000 Series 3 Installation Guide
© 2022 KMC Controls, Inc. 655-019-01P
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
[email protected]
Select Specications
Material Light gray (SSS-100x) or almond
(SSS-101x) ABS/polycarbonate
(UL94-5V)
Connection 1/4" nipple (SSS-100x) for 3/8" OD
polyethylene tubing or 3/16" nipple
(SSS-101x) for 1/4" OD tubing
K Factors Refer to the data sheet for addi-
tional information!
Maintenance
The air pickup orices must be kept free of dust accumula-
tion or debris. The pickup tubes are designed for depend-
able, long-term reliability and performance.
Important Notices
The KMC logo and KMC Controls are registered trademarks
of KMC Controls, Inc.
All rights reserved. No part of this publication may be
reproduced, transmitted, transcribed, stored in a retrieval
system, or translated into any language in any form by any
means without the written permission of KMC Controls, Inc.
The material in this document is for information purposes
only. The contents and the product it describes are subject
to change without notice. KMC Controls, Inc. makes no
representations or warranties with respect to this docu-
ment. In no event shall KMC Controls, Inc. be liable for any
damages, direct or incidental, arising out of or related to the
use of this document.
More Information
For additional K factor and other information, see the data
sheet for the SSS-1000 series on the KMC web site (www.
kmccontrols.com).
“Cubic Feet Per Minute (CFM)” K Factors
Round
Duct Size
(Diameter)
KCFM Factor
SSS-10x2 SSS-10x3 SSS-10x4 SSS-10x5
4 301 NA NA NA
5 470 NA NA NA
6 677 648 NA NA
7 922 882 NA NA
8 1204 1152 1117 NA
9 1524 1458 1414 NA
10 1882 1800 1745 1745
12 2710 2592 2513 2513
14 3688 3528 3421 3421
16 4817 4608 4468 4468
18 6097 5832 5655 5655
22 9107 8711 8447 8447
24 10838 10367 10053 10053
“Feet Per Minute” K Factors
Pickup Tube Model KFPM
SSS-10x2 3450
SSS-10x3 3300
SSS-10x4 3200
SSS-10x5 3200
NOTE: The appropriate “K” factor for the pickup tubes
depends upon the type of setup required by the
VAV controller with which it will be used:
• For VAV controllers that require KCFM for setup, refer to
the “Cubic Feet Per Minute (CFM)” chart below and
the device documentation for additional information.
For rectangular ducts, KCFM = KFPM x (W" x H"/144) (with
duct cross-section measurements in inches).
• For VAV controllers that require KFPM for setup, refer
to the “Feet Per Minute” chart below and the device
documentation for additional information.

Other KMC Controls Measuring Instrument manuals

KMC Controls 2000-2 User manual

KMC Controls

KMC Controls 2000-2 User manual

KMC Controls TRUEFIT MEP-4552 User manual

KMC Controls

KMC Controls TRUEFIT MEP-4552 User manual

KMC Controls BAC-19 FlexStat Series User manual

KMC Controls

KMC Controls BAC-19 FlexStat Series User manual

KMC Controls rc allen instruments RCA 2610-P Series Original operating instructions

KMC Controls

KMC Controls rc allen instruments RCA 2610-P Series Original operating instructions

Popular Measuring Instrument manuals by other brands

Leica FlexLine plus quick guide

Leica

Leica FlexLine plus quick guide

Hanna Instruments HI770 instruction manual

Hanna Instruments

Hanna Instruments HI770 instruction manual

WIKA A-AI-1 operating instructions

WIKA

WIKA A-AI-1 operating instructions

Maico MA 25 Quick user guide

Maico

Maico MA 25 Quick user guide

Skil 1928 Original instructions

Skil

Skil 1928 Original instructions

Macnaught ERST-RM instructions

Macnaught

Macnaught ERST-RM instructions

DENT Instruments powerscout 3037 Operator's guide

DENT Instruments

DENT Instruments powerscout 3037 Operator's guide

SkyTraxx 3.0 Short guide

SkyTraxx

SkyTraxx 3.0 Short guide

Pulsar NOVA user manual

Pulsar

Pulsar NOVA user manual

Eurochron 1544543 quick guide

Eurochron

Eurochron 1544543 quick guide

Honeywell Home resideo EW701 Operating and installation instructions

Honeywell Home

Honeywell Home resideo EW701 Operating and installation instructions

Endress+Hauser Levelflex M FMP45 operating instructions

Endress+Hauser

Endress+Hauser Levelflex M FMP45 operating instructions

Keysight Technologies M9602A Configuration guide

Keysight Technologies

Keysight Technologies M9602A Configuration guide

Wohler DC 2000 manual

Wohler

Wohler DC 2000 manual

Solight 1T04A instructions

Solight

Solight 1T04A instructions

FMT Swiss AG Digital In-Line Meter operating instructions

FMT Swiss AG

FMT Swiss AG Digital In-Line Meter operating instructions

JUMO meroTRON 104 manual

JUMO

JUMO meroTRON 104 manual

Broadley James SingleSense SU800 Operation manual

Broadley James

Broadley James SingleSense SU800 Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.