POWER & COMMUNICATION
The status LEDs indicate power connection and
network communication.
NOTE: If neither the green READY LED nor
the amber COMM LED is ON, check
the transformer fuse, power, and
connections to the router.
GREEN READY LED
12
The green READY LED flashes once per
second, indicating running.
AMBER BACnet MS/TP COMM LED
13
The amber COMM LED flashes at a one-half-
second rate when looking for other devices to
pass the token.
The amber COMM LED flickers as it receives
and passes the token over the BACnet MS/TP
network.
ETHERNET LEDs
The Ethernet status LEDs indicate network
connection and communication speed.
NOTE: If neither the green Ethernet LED
nor the amber Ethernet LED is ON,
check the power and network cable
connections.
GREEN ETHERNET LED
14
The green Ethernet LED stays lit when the
router is connected to the network.
The green Ethernet LED is OFF when the router
is not powered or not communicating with the
network.
12
13
© 2015 KMC Controls, Inc. Specifications and design subject to change without notice 922-019-01B
AMBER ETHERNET LED
15
The amber Ethernet LED flashes when the
router is communicating with the network.
The amber Ethernet LED is OFF when the
controller is communicating with the network
at 10 Mbps.
ROUTER SET UP
Set up and conguration of the router is done
through a web browser (Internet Explorer version
9 or later or an HTML5 supported web browser)
using the routers IP address (192.168.111.252).
Refer to the Router Application Guide for more
conguration information.
REPLACEMENT PARTS ................ PART NUMBER
Replacement Pack of Conquest controller
terminal blocks and DIN clips.................HPO-9901
IMPORTANT NOTICES
The material in this document is for information
purposes only.
The contents and the product it describes are
subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document.
In no event shall KMC Controls, Inc. be liable for
any damages, direct, or incidental, arising out of or
related to the use of this document.
The KMC logo is a registered trademark of KMC
Controls, Inc. All rights reserved.
TEL: 574.831.5250
FAX: 574.831.5252