KNX Module LC-S.1 User manual

module-electronic.ru
KNX LINE COUPLER
LC-S.1
Application Program: ver. 1.0
User Manual: ver. 1.0
User Manual

CONTENT
Content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1 Basic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Appearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Installation and connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Operational description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 TP coupler application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 TP repeater application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 KNX network installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Individual addres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.2 KNX topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.4 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.1 Programming button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.2 Individual address assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5 Special function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.1 Manual function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.2 Factory reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.3 LED status display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3 ETS database parameters coupler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2 Main line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3 Subline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 ETS database parameters repeater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Main line. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.3 Subline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5 State of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.1 Default factory setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
page 2
module-electronic.ru

1 BASIC INFORMATION
The KNX line coupler provides a bi-directional data connection between two KNX TP lines or areas and
works as a KNX network. KNX TP main line and KNX TP subline are coupled having a galvanic isolation in
between.
• Various routing filter for group and individual telegrams
• Temporary disabling of routing filter via button
• Long telegrams with up to 240 bytes APDU length are supported
• LED status indication
• Galvanic isolation of connected lines
• Integrated ACK generator
• Power supply via KNX bus
• Low power consumption
• DIN rail 35mm mounting
LC-S.1
page 3
module-electronic.ru

1.1 SPECIFICATION
Device model
LC-S.1
KNX interfaces (Main, Sub)
Specification
TP-256
Available application soware
ETS 4 and later
KNX connector
4-wire EIB connector (PUSH WIRE spring clips) for standard cable TP1 0,8мм Ø
KNX physical address by default
15.15.0
Power supply
via KNX bus: 21...30В DC
Consumption on the KNX bus (29V DC)
< 10mA
< 300mW
Operation temperature
-5°C ... + 45°C
Operation humidity
5 ... 95% (no condensation)
Degree of protection
IP 20, clean environment
Mounting type
DIN rail 35mm
Dimensions
36 х 90 х 71mm (2TE)
Weight
62 g
page 4
module-electronic.ru

1.2 APPEARANCE
90mm
36mm 71mm
B
7
D
A
4
2
1
3
C
56
A. Function button B. Programming button C. KNX TP main line connector D. KNX TP subline connector
1. LED bus state KNX TP (main line) 2. LED bus state KNX TP (subline) 3. LED telegram traffic KNX TP (main line)
4. LED telegram traffic KNX TP (subline) 5. LED group address routing 6. LED physical address routing
7. Programming LED
1. Bus state KNX TP (main line)
Green: Main line OK
Orange: Manual function active
2. Bus state KNX TP (subline)
Green: Subline OK
OFF: Subline not connected
3. Telegram traffic KNX TP (main line)
Green (blinking): Telegram traffic
Red (blinking): Transmission error
OFF: No telegram traffic
4. Telegram traffic KNX TP (subline)
Green (blinking): Telegram traffic
Red (blinking): Transmission error
OFF: No telegram traffic
5. Group address routing*
Green: Filter table active
Orange: Route all
Red: Block all
OFF: Routing of group telegrams is different on main line and subline
6. Physical address routing
Green: Filter table active
Orange: Route all
Red: Block all
OFF: Routing of physical telegrams is different on main line and subline
7. Programming
Red: Programming mode active
OFF: Programming mode not active
page 5
module-electronic.ru

+
-
KNX bus (Sub)
MAIN SUB
+
-
KNX bus (Main)
1.3 INSTALLATION AND CONNECTION
INSTALLATION
WIRING DIAGRAMS
Attaching to DIN rail
Removing from DIN rail
ATTENTION! Installation and connection of the device to the mains must only be carried
out by qualified personnel! Be sure to turn off the power before installing or removing the
device! Even when the device is turned off, the output terminals can be live! Do not
connect to the outputs a load that exceeds the recommended values! The design of the
device meets the requirements of electrical safety according to GOST 12.2.007.0-75.
page 6
module-electronic.ru

2 OPERATIONAL DESCRIPTION
In network installations LC-S.1 can be used as KNX TP area/line coupler or KNX TP line repeater. Aer
connecting the main line, LC-S.1 operates with its default settings. Setting the correct Individual Address
is necessary. Only Individual Addresses x.y.0 are allowed.
Figure 1. TP coupler application program
When LC-S.1 receives telegrams (for example during commissioning) that use Individual Addresses as
destination addresses, it compares the Individual Addresses of the receiver with its own Individual
Address and decides on that whether it has to route the telegrams or not.
When LC-S.1 receives telegrams that use group addresses as destination addresses, it reacts in
accordance with the parameter settings. During normal operation (with Group Telegram routing set to
filter), LC-S.1 only routes telegrams whose group addresses are entered in its filter table.
If a telegram is routed by LC-S.1 without receiving the corresponding acknowledgement, i.e. due to a
missing receiver or to a transmission error, the telegram will be repeated up to three times (depending on
the ETS setting). With the parameters «Repetitions if errors...», this function can be configured separately
for each line and both kinds of telegrams. It is recommended to use the default parameter setting.
If not already configured as «Line Coupler», the ETS application program «TP Coupler» has to be
downloaded to the device. Under the Information tab the configuration setting can be changed by the
drop-down menu «Change Application Program». Aer changing the configuration setting the filter table
entries can be added manually. Updating the application program version can also be done here.
2.1 TP COUPLER APPLICATION
page 7
module-electronic.ru

2.2 TP REPEATER APPLICATION
Any received telegram is routed to all lines irrespective of in which line it is processed. Line repeaters
make no use of a filter table. It is therefore not important whether the telegram is generated within a line
or whether it is sent from an upper line to a lower line via a coupler.
If a telegram is routed by LC-S.1 without receiving the corresponding acknowledgement, i.e. due to a
missing receiver or to a transmission error, the telegram will be repeated up to three times (depending on
the ETS setting). With the parameters «Repetitions if errors...», this function can be configured separately
for each line and both kinds of telegrams. It is recommended to use the default parameter setting.
If not already configured as Line/Area/BB Repeater, the ETS application program
«TP repeater» has to be downloaded to the device. Under the Information tab the configuration setting
can be changed by the drop-down menu «Change Application Program». Aer changing the configuration
setting the filter table entries can be added manually. Updating the application program version can also
be done here.
Figure 2. TP repeater application program
page 8
module-electronic.ru

2.3 KNX NETWORK INSTALLATION
For line coupler functionality in a KNX network LC-S.1 has to use the correct Individual Address of a line
coupler (x.y.0, 1≤ x & y ≤15). In ETS up to 225 addresses can be defined (from 1.1.0 to 15.15.0).
For area coupler functionality in a KNX network LC-S.1 has to use the correct Individual Address of an area
coupler (x.0.0, 1≤ x ≤15). In ETS up to 15 areas can be defined.
If LC-S.1 is used in a KNX system for both purposes, it is only necessary to ensure that the LC-S.1 used as a
line coupler has a line coupler address assigned from a free addressing area. Following figure illustrates
the LC-S.1 router topology for KNX lines and KNX areas.
2.3.1 INDIVIDUAL ADDRESS
Figure 3. LC-S.1 network
Example: If an area coupler with address 1.0.0 already exists on the backbone no line coupler with
address 1.x.0, 1≤ x ≤15 can be added here. Even if no line coupler with address 1.1.0 exists on
the subline of the 1.0.0 area coupler. Vice versa, if a line coupler with address 1.1.0 already
exists in the installation no area coupler with address 1.0.0 can be added.
page 9
module-electronic.ru

2.3.2 KNX TOPOLOGY
Via a line/area coupler up to 15 lines can be connected to a main line called an area. It is possible to have
up to 64 bus devices on one line. With use of line repeaters a line can theoretically be extended to 255 bus
devices. This means up to four line segments form a single KNX TP line. But it is common practice on
exceeding 64 bus devices to insert a new line instead of extending the originating one.
The free tree structure of the KNX topology prevents problems caused by circling telegrams and heavy
bus load. To maintain this condition, interconnection between lines or line segments is strictly forbidden.
Figure 4. LC-S.1 network topology
Each line segment requires its own KNX power supply unit.
Using repeaters on the backbone and main lines is not allowed.
Interconnections are not allowed.
page 10
module-electronic.ru

2.4 PROGRAMMING
To download the desired Individual Address or an ETS setting the Programming Mode must be activated.
Successive pressing the Programming Button will turn on and off the Programming Mode. LED 7 lighting
in red colour indicates Programming Mode is active. When Programming Mode is activated, the ETS is
able to download the Individual Address.
2.4.1 PROGRAMMING BUTTON
To configure the device an interface connection (IP, USB) to the KNX bus system is required. The device is
supplied with the Individual Address 15.15.0. The KNX product database entry can be downloaded from
the website and from the KNX Online Catalog.
The Individual Address can be assigned to the device by setting the desired address in the properties
window of the ETS. Aer starting the ETS download and then pressing the Programming Button the
device restarts itself.
2.4.2 INDIVIDUAL ADDRESS ASSIGNMENT
Figure 5. ETS properties window
page 11
module-electronic.ru

2.5 SPECIAL FUNCTION
The Function Button activates LC-S.1´s special functions. Manual Function and Factory Reset can be
activated. It depends on time the Function Button is being pressed.
2.5.1 MANUAL FUNCTION
During normal operation a rather short press (≈ 3 sec) activates and deactivates the Manual Function.
When the Manual Function is active, either all Physical Telegrams or all Group Telegrams or both pass the
LC-S.1 without filtering. Aer the Switch-off time period has elapsed, LC-S.1 automatically switches back
to normal operation. To configure the Manual Function and set the Switch-off time use the General
parameter tab like shown in chapters 3.1 and 4.1. Aer switching back from Manual Function to normal
operation the latest downloaded parameter setting / filter table entries are active again.
2.5.2 FACTORY RESET
A long press (≈ 15 sec) of the Function Button soon followed by a short press (≈ 3 sec) executes the Factory
Reset. Aer the first press, the LED display lights like described in Table 2. Aer the second press, all
parameters will be set to factory default (incl. Individual Address). Subsequently, LEDs show the normal
operation display again.
page 12
module-electronic.ru

2.5.3 LED STATUS DISPLAY
Number
LED
Colour
Comment
1
Bus state KNX TP
(main line)
orange
2
Bus state KNX TP
(subline)
green
LED is <off> if not connected
5
Group address
routing
green:
orange:
red:
filter
route all
block all
6
Individual address
routing
Table 1. LED status display for manual function
Number
LED
Colour
Comment
1
Bus state KNX TP
(main line)
orange
2
Bus state KNX TP
(subline)
orange
LED lights red if not
connected
5
Group address
routing
green:
orange:
red:
filter
route all
block all
6
Individual address
routing
Table 2. LED status display for factory reset aer first button press
page 13
module-electronic.ru

3.1 GENERAL
3 ETS DATABASE PARAMETERS COUPLER
All screen shots are related to the LC-S.1 database V3.1 in ETS5.
Figure 6. General tab parameters
ETS Parameter
Setting
{Factory Default}
Comment
Manual function
disabled
pass all telegrams
pass all physical telegrams
pass all group telegrams
{pass all telegrams}
Configuration setting for telegram routing when
the Manual Function is active.
Switch-off time
for manual function
10 min, 1 hour, 4 hours, 8 hours
{1 hour}
Aer expiry of this time period the Manual
Function is switched off automatically.
Table 3. General tab parameters
page 14
module-electronic.ru

3.2 MAIN LINE
For Group Telegrams and Physical Telegrams the setting «transmit all» is intended only for testing
purposes. Please do not use for normal operation.
If the parameter «Send confirmation on own telegrams» is set to «yes», the LC-S.1 systematically
sends an ACK on any own routed telegram.
Figure 7. Main line tab parameters
page 15
module-electronic.ru

ETS Parameter
Setting
{Factory Default}
Comment
Telegram routing
Group: filter, Physical: block
Group and Physical: filter
Group: route, Physical: filter
Group and Physical: route
configure
{Group and Physical: filter}
block:
no telegrams are routed
filter:
telegrams entered in the filter
table are routed
route:
all telegrams are routed
configure:
the following parameters must
be set manually
Group telegrams:
Main group 1...13
transmit all (not recommended)
block
filter
{filter}
џGroup telegrams (main group 0…13)
are all routed.
џGroup telegrams (main group 0…13)
are all blocked.
џGroup telegrams (main group 0…13)
are routed if entered in the filter table.
Group telegrams:
Main group 14...31
transmit all (not recommended)
block
filter
{filter}
џGroup telegrams (main group 14…31)
are all routed.
џGroup telegrams (main group 14…31)
are all blocked.
џGroup telegrams (main group 14…31)
are routed if entered in the filter table.
Physical telegrams
transmit all (not recommended)
block
filter
{filter}
џPhysical telegrams are all routed.
џPhysical telegrams are all blocked.
џDepending on the Individual Address
Physical telegrams are routed.
Physical telegrams:
Repetition if errors
on main line
no
up to 3 repetitions
only one repetition
{up to 3 repetitions}
Aer main line transmission error (e.g. due to
missing receiver) Physical telegrams
џare not repeated.
џare repeated max. 3 times.
џare repeated once.
Group telegrams:
Repetition if errors
on main line
no
up to 3 repetitions
only one repetition
{up to 3 repetitions}
Aer main line transmission error (e.g. due to
missing receiver) Group telegrams
џare not repeated.
џare repeated max. 3 times.
џare repeated once.
Telegram confirmation
on main line
if routed
always
{if routed}
џRouted telegrams to the subline are confirmed
by an ACK on the main line.
џEach telegram on the mainline is confirmed by
an ACK.
Send confirmation
on own telegrams
yes
no
{no}
џTelegrams sent out to the mainline are
confirmed by added ACK.
џNo ACK confirmation.
Table 4. Main line tab parameter settings
page 16
module-electronic.ru

3.3 SUBLINE
For Group Telegrams and Physical Telegrams the setting «transmit all» is intended only for testing
purposes. Please do not use for normal operation.
Figure 8. Subline tab parameters
page 17
module-electronic.ru

Table 5. Subline tab parameter settings
ETS Parameter
Setting
{Factory Default}
Comment
Telegram routing
Group: filter, Physical: block
Group and Physical: filter
Group: route, Physical: filter
Group and Physical: route
configure
{Group and Physical: filter}
block:
no telegrams are routed
filter:
telegrams entered in the filter
table are routed
route:
all telegrams are routed
configure:
the following parameters must
be set manually
Group telegrams:
Main group 1...13
transmit all (not recommended)
block
filter
{filter}
џGroup telegrams (main group 0…13)
are all routed.
џGroup telegrams (main group 0…13)
are all blocked.
џGroup telegrams (main group 0…13)
are routed if entered in the filter table.
Group telegrams:
Main group 14...31
transmit all (not recommended)
block
filter
{filter}
џGroup telegrams (main group 14…31)
are all routed.
џGroup telegrams (main group 14…31)
are all blocked.
џGroup telegrams (main group 14…31)
are routed if entered in the filter table.
Physical telegrams
transmit all (not recommended)
block
filter
{filter}
џPhysical telegrams are all routed.
џPhysical telegrams are all blocked.
џDepending on the Individual Address
Physical telegrams are routed.
Physical telegrams:
Repetition if errors
on subline
no
up to 3 repetitions
only one repetition
{up to 3 repetitions}
Aer subline transmission error (e.g. due to
missing receiver) Physical telegrams
џare not repeated.
џare repeated max. 3 times.
џare repeated once.
Group telegrams:
Repetition if errors
on subline
no
up to 3 repetitions
only one repetition
{up to 3 repetitions}
Aer subline transmission error (e.g. due to
missing receiver) Group telegrams
џare not repeated.
џare repeated max. 3 times.
џare repeated once.
Telegram confirmation
on subline
if routed
always
{if routed}
џRouted telegrams to main line are confirmed
by an ACK on the subline.
џEach telegram on the subline is confirmed by
an ACK.
Send confirmation
on own telegrams
yes
no
{no}
џTelegrams sent out to the subline are
confirmed by added ACK.
џNo ACK confirmation.
Configuration
from subline
allow
block
{allow}
If blocked an ETS download to the LC-S.1 can
occur only via main line.
page 18
module-electronic.ru

4 ETS DATABASE PARAMETERS REPEATER
All screen shots are related to the LC-S.1 database file R3-0f in ETS5.
4.1 GENERAL
Figure 9. General tab parameters
ETS Parameter
Setting
{Factory Default}
Comment
Manual function
disabled
pass all telegrams
pass all physical telegrams
pass all group telegrams
{pass all telegrams}
Configuration setting for telegram routing when
the Manual Function is active.
Switch-off time
for manual function
10 min, 1 hour, 4 hours, 8 hours
{1 hour}
Aer expiry of this time period the Manual
Function is switched off automatically.
Table 6. General tab parameter settings
page 19
module-electronic.ru

4.2 MAIN LINE
For Group Telegrams and Physical Telegrams the setting «transmit all» is intended only for testing
purposes. Please do not use for normal operation.
If the parameter «Send confirmation on own telegrams» is set to «yes», the LC-S.1 systematically
sends an ACK on any own routed telegram. Since the repeater does not use a filter table, it is useful
to have an ACK sent along with routed telegrams.
Figure 10. Main line tab parameters
page 20
module-electronic.ru
Table of contents
Other KNX Network Hardware manuals
Popular Network Hardware manuals by other brands

Panasonic
Panasonic PIN Diodes MA2SP060G Specifications

Nokia
Nokia XS-2426G-B Product guide

Matrix Switch Corporation
Matrix Switch Corporation MSC-HD44DEL product manual

Brickcom
Brickcom NR-04A user manual

nvent
nvent SCHROFF CPCI PSB System Subrack 10 U user manual

Patton electronics
Patton electronics 2888 Product brief