Kodio EM-5105 User manual

INSTRUCTION MANUAL
EM-5105
Emergency Paging Microphone Panel
EMERGENCY PAGING PANEL
MIC
SIREN SWITCH
SIREN
FIRE
EMERGENCY / SIREN ACTIVE
Version 1/17
IMPROVED

Parts Identification
PAGE 2
Front View:
Rear View:
12
4
3
5
6
7
8
9 10 11 12 13
1. FIRE INDICATOR
2. SIREN SWITCH
3. HANDHELD PAGING MICROPHONE
Pressing the microphone switch shall have priority over other inputs such as Siren, External Message input as well as
normal paging or BGM feeds. To page, just pick up the handset, press the button and start talking. Releasing the switch,
the previous operating mode shall resume.
Press the siren button shall activate the siren. FIRE indicator shall lit and the MIC switch relay contact (7) shall close.
Press the siren switch again will turn Off the siren.
Whenever siren or external activation device is triggered, the FIRE indicator shall flash alongside with siren audio
broadcast. Activate the paging microphone will also turn on the flashing.
EMERGENCY PAGING PANEL
MIC
SIREN SWITCH
SIREN
FIRE
EMERGENCY / SIREN ACTIVE
4. 24V INPUT
The unit operates on 24V DC. It is preferred that the unit to be supplied directly from the uninterrupted power source. ie.
power supplies linked to back up batteries.
Note: Do not connect directly to the terminals of back up battery. It shall damage the equipment.
EM-5105 | EMERGENCY PAGING MICROPHONE PANEL
EM 5105

EM-5105 | EMERGENCY PAGING MICROPHONE PANEL PAGE 3
Parts Identification
7. RELAY CONTACT
Triggering the front panel mic switch message or siren shall activate an internal relay. This ports provide a dry contact which
can be used to connect E/M overriding signal or to activate ALL CALL at speaker zone selector. The recommended rating
for the contact is 3A. In case higher rating is required, please use external relay or contactor to accommodate the high
current requirement.
6. REMOTE TRIGGER PORT FOR SIREN
External sensor device such as heat detector or fire alarm interface device can be connected to this unit to activate the
siren. The external device or switch must be voltage free to avoid damage to the unit. Two ways for the external switch to
turn On/Off the siren :
1) A <2s close-then-open to turn On; a <2s close-then-open to turn Off
2) A >2.5s close to turn On, an open to turn Off
5. EXTERNAL MESSAGE TRIGGER PORT
External message player can be linked to it and can be broadcasted to the speakers when this port is triggered. A voltage
free contact is recommended to trigger the message playback.
9. HANDHELD MIC LEVEL CONTROL
This is to adjust the front paging mic volume. It is recommended that the setting is made during testing and commissioning
works.
10. SIREN OUTPUT LEVEL CONTROL
Adjust the siren output to an optimum level during testing and commissiong works.
11. EXTERNAL MESSAGE AUDIO INPUT
The external message playback signal shall be balanced line level. ( e.g: audio from MR1301 )
12. PRE-AMPLIFIER INPUT JACK
Output from pre-amplifier mixer (balanced line level ) is connected to the unit which is normally closed when the unit is not
activated. Triggering the panel shall bypass the signal to allow higher priority audio to the PA system.
13. DATA AUDIO OUTPUT
Audio output from the decoder is balanced line output level. RJ45 connector consists of audio, data and power with the follow-
ing pin configuration:-
Pin 1 - Data A
Pin 2 - Data B
Pin 3 - NC
Pin 4 - Ground
Pin 5 - +24V Supply
Pin 6 - Audio -ve output
Pin 7 - Ground
Pin 8 - Audio +ve Output
8. RS485 PORT
External controls or interface devices shall be able to communicate with the unit.

PAGE 4 EM-5105| EMERGENCY PAGING MICROPHONE PANEL
PUBLIC ADDRESS POWER AMPLIFIER
SIGNAL -40 dB
SIGNAL -10 dB
POWER
PROTECT
CLIP
O
I
POWER
OFF SELECT
TUNER
CD
CASS
OFF
MASTER
MUSIC SOURCE
SIG IN
BASS
MAXMIN
EXT INPUT
MAX MAXMIN
SOURCE
MIN
SIG IN
CHIME MIXER TREBLE
MAXMIN
TONE CTRL
CH5 CH6CH4
SIG INSIG IN SIG IN
MAXMIN MAXMIN MIN
CH3CH1 CH2
SIG INSIG IN
MAXMIN MAXMIN MAXMIN MAX
AUX
SIG IN
INPUT SOURCES (PAGING MICS, BGM PLAYERS ETC)
24V DC
24V DC
24V DC
24V DC
POWER AMPLIFIERS
ZS SPEAKER ZONE
SELECTOR
SPK VOLUME
CONTROLLERS
SPEAKERS
audio out - balanced
audio out - balanced
100V line audio output
100V line output
24V E/M
override
24V E/M
override
100V line output
SY-P1000 PRE-AMP
MIXER
EM5105EMERGENCY
PANEL
dry contact to activate
ALL CALL and 24V
E/M override signal
Schematic Diagram
The schematic shown above is typical for most conventional installations. Audio output from mixer shall go through EM-5105prior to
amplifier inputs to enable emergengy paging being highest priority.
EMERGENCY PAGING PANEL
MIC
SIREN SWITCH
SIREN
FIRE
EMERGENCY / SIREN ACTIVEz

EM-5105| EMERGENCY PAGING MICROPHONE PANEL PAGE 5
Connecting The Unit
24V DC POWER
SUPPLY / BACK UP
SUPPLY
TRIGGERING PORT TO ACTIVATE
EXTERNAL PLAYBACK DEVICE
EXTERNAL AUDIO INPUT (BALANCED
LINE SIGNAL) FROM MESSAGE
PLAYBACK DEVICE
OUTPUT FROM PRE-AMPLIFIER
MIXER (BALANCED LINE LEVEL)
TO POWER AMPLIFIER
INPUT (BALANCED LINE)
EXTERNAL SIREN
ACTIVATION CONTACT
(VOLTAGE FREE) ie. FIRE
CONTROL CENTER / SMOKE
DETECTORS, ETC
DRY CONTACT (NORMALLY
OPEN)
CONNECT TO ZONE
SELECTORS FOR E/M
OVERRIDING SIGNAL
ACTIVATION VOLUME
RJ45 PORT WITH POWER,
DATA AND AUDIO TO ENABLE
EASY LINK TO MxP2288
* To link to iPX5155 please refer
to page 8
EM 5105

PAGE EM-5105| EMERGENCY PAGING MICROPHONE PANEL
Connecting The Unit - Matrix System
VOLUME
12 x 8 EHTERNET MATRIX CONTROLLER
MENU
ENTER
PREV NEXT
ACTIVITY
STATUS
FAULT
MONITOR SPEAKER
POWER
O
I
Wireless router /
Network Switch Wifi
Speaker Zone Selector (Optional),
VR7000 Rack Mount VC,
LS4600 Line Surveillance
Wifi
- Audio Streaming
- Controls
Tab / smart phone
AX3800
Amp
Amp
Audio
100V
81
MR1301
EM5105
Paging Mic Input
Total 8
Audio
100V
Amp
Audio
100V
Speaker
PD Series
Paging Mic
MxP2288
Microphone
Media Player
Media Player
Zone 2 Zone 1
EMERGENCY PAGING PANEL
MIC
SIREN SWITCH
SIREN
FIRE
EMERGENCY / SIREN ACTIVE
AUTO STANDBY AMPLIFIER CHANGEOVER
BUZZER
CH 1 CH 1 CH 1 CH 1 CH 1 CH 1 CH 1 CH 1
NORMAL : GREEN
FAULT: RED
STANDBY
CHANGEOVER
STANDBY
AMPLIFIER
PILOT TONE
FAULT
*See Note
REMOTE
PAGING MIC
M P 2288
12 x 8 EHTERNET MATRIX CONTROLLER
x
EP1200
CONNECTION
24V DC IN ; 1 A
+ -
REMOTE
PANEL 1
REMOTE
PANEL 2
COM
NO
COM
NO
COM
NO
COM
NO
EM / AC
CONT (NO)
RS485
A B
ETHERNET
PORT
MESSAGE PLAYER
IN ( LINE BAL ) MxP2288
- PC Paging
- PC Audio Streaming
- Controls
Note:
Show
rear
connecting
of
E
M5105
and MxP2288
EM5105
cat5e
C
C
O
H
N
1
FIGURA
C
B
H
L
2
E REM
C
O
H
T
3
E TRIG
C
G
H
E
4
R

EM-5105 | EMERGENCY PAGING MICROPHONE PANEL PAGE 7
INPUT
OUTPUT
PI N 8-COM
PI N 7-24V
PI N 6-Z 6
PI N 5-Z 5
PI N 4-Z 4
PI N 3-Z 3
PI N 2-Z 2
PI N 1-Z 1
PI N 8-COM
PI N 7-24V
PI N 6-Z 12
PI N 5-Z 11
PI N 4-Z 10
PI N 3-Z 9
PI N 2-Z 8
PI N 1-Z 7
+
DC 24V
CON
RLY
TRIG
RLY
PR
ZS
SY-P1000
EM5105
PA5480
EX2800
TD6240
ZS5312
RM5024
MR1301
Audio
Audio
RS485 & Audio
AMP Output
Audio
Cat5e
Cat5e
Connecting The Unit - Conventional System
DC 24V
+
Trigger
SPEAKER
From MR1301 (Trigger)
To E
M5
10
5
EM 5105

PAGE 8 EM-5105 | EMERGENCY PAGING MICROPHONE PANEL
iPX5151
iPX5151
LAN
iPX5101
iPX5151 /
iPX5155
PI N 8-COM
PI N 7-24V
PI N 6-Z 6
PI N 5-Z 5
PI N 4-Z 4
PI N 3-Z 3
PI N 2-Z 2
PI N 1-Z 1
PI N 8-COM
PI N 7-24V
PI N 6-Z 12
PI N 5-Z 11
PI N 4-Z 10
PI N 3-Z 9
PI N 2-Z 8
PI N 1-Z 7
+
DC 24V
CON
RLY
TRIG
RLY
PR
ZS
EM5105
PD2800
SY-P1000
PA5480
ZS5312
TD6240
SPEAKER
Cat5e
Cat5e
Cat5e
Cat5e
Audio + RS485 (AB) Data
Cat5e
Audio
AMP Output
Cat5e Cat5e
Connecting The Unit: IP Setup
EM5105, which is installed at main rack for a large system using IP as communication interface, shall be able to override remote
buildings / system as similar to single rack installation.
Audio
Pin 1, 2 Data
6, 7, 8 Audio
Connect RS485
and audio only
EM 5105

EM-5105 | EMERGENCY PAGING MICROPHONE PANEL PAGE 9
Configuring ALL CALL And E/M Overriding
E
M51
0
5
P IN 8 -COM
P IN 7 -24V
P IN 6 -Z 6
P IN 5 -Z 5
P IN 4 -Z 4
P IN 3 -Z 3
P IN 2 -Z 2
P IN 1 -Z 1
+
DC 24V
CON
RLY
TRIG PR
ZS
E
M5105
PS5424 PSU
PM SERIES
PAGING MIC
ZS5312 ZONE SELECTOR
Volume Controller
TO SPEAKERS
FR. ZONE SELECTOR 100V LINE OUTPUT
24V E/M
Overriding
Signal
Connect this to allow
EM
5105
to trigger internal
relay of Zone Selector
+-
The above diagram shows detailed connections for using EM5105to override volume control and activating ALL CALL at
zone selector.

PAGE 10 EM-5105| EMERGENCY PAGING MICROPHONE PANEL
Technical Specifications
Summary Of Features
Power requirement 24V DC
Power consumption 3.5W
MICROPHONE
Mic sensitivity -72 dB Omni directional
Impedance 600 Ohm
Frequency response 300 ~ 8 KHz
SIREN
Siren frequency Continuous at 8 KHz
Siren duration Continuous when activated
Siren activation Front test switch / remote contact
Input channel Pre-amplifier output, message recorder
Output level Balanced line out (1.2V)
Priority sequence Paging mic - message - siren - pre amp in
Indicators Front FIRE with backlight illumination
Dimension (WxHxD) 482 x 88 x 180 mm
Weight 3.0 kg
Built in siren tone generator (constant signal)
Visual FIRE indicator
External voice message activation
Dual mode siren tone activation
Dry contact when paging mic is activated
Priority paging via front panel microphone, bypassing all other audio sources
Output level controls for siren and message / paging microphone
Table of contents