Technical Support is available Monday through Friday, 7:00 a.m. to 5:00 p.m. CST, at
(800) 334-6011. Use the guide on the following page to help find and correct system faults.
Contact Technical Support before replacing the control or for additional troubleshooting.
TROUBLESHOOTING
EXTERNAL CONTROL
When the control detects an internal error, it
will stop controlling, deactivate the dehumidifier
output, and the LCD will display the Error Code.
See Figure 19. The control will attempt to recover
from the error every 10 minutes. The Error Code
will continue to be displayed as long as the error
condition exists. Button presses are not registered
when in Error Mode. Cycling power to the control
will not clear the code and the control will need to
be replaced.
REMOTE CONTROL
When there is a dehumidifier or control communication fault, all dehumidifier outputs will turn
off and the Model 76 LCD will display an Error Code. See Figure 20 for an example. The faults
can either be critical or non-critical. Any fault will
result in all dehumidification outputs turning off.
A critical fault is cleared by repairing the fault
and cycling power using the on/off switch on
the dehumidifier. A non-critical fault is cleared
by repairing the fault and cycling power to the
dehumidifier is not required. See Table 2 for the
error codes and required action.
ERROR CODES
FIGURE 19 – External Control
Error Code Screen
FIGURE 20 – Remote Control
Error Code Screen
90-1645
90-1645
TABLE 2 – Error Codes
Error Code Failure Mode Action Reset
E1 Internal Humidity
or Temperature
Sensor Open or
Shorted
1. Check the connection between the sensor board
and control board.
2. If connection okay, replace sensor board, Part No.
5460.
Cycle Power
E2 High Refrigeration
Pressure
1. Verify that the fan works, the backflow damper
swings freely and there is no blocked or
restricted ductwork.
2. If the fault persists, call Technical Support.
Cycle Power
E3 Model 76
Remote Control
Communication
Loss
1. Check connections between Model 76 and
dehumidifier control board. Terminals should be
fully inserted and secured in the control board
and Model 76 control terminals.
2. If connections are correct and secure, turn off
the dehumidifier and remove the Model 76. Use
a short section of 4-wire cable to reconnect
the Model 76 to the control board. Turn the
dehumidifier back on and increase the dryness
level setting on the Model 76. If the dehumidifier
turns on, the problem is with the wiring between
the dehumidifier and control.
3. If the dehumidifier does not turn on, call
Technical Support.
Self-Correcting
E4 Insufficient
Capacity
1. Check the frost sensor connection at the power
board. Terminal should be fully seated on the
power board pins.
2. Remove the side access panel and verify that the
sensor is secured to the suction line.
3. If the sensor is connected and secured to the
refrigeration line proceed to the next step.
4. Reset the fault by cycling power to the
dehumidifier.
5. Turn the humidity setting down (below room/
home humidity level) to make a dehumidification
call.
6. Allow the fan and compressor to run for
approximately 10-15 minutes and then enter
diagnostic test mode by simultaneously pressing
the UP ARROW and MODE buttons for 3 seconds.
The LCD will display the temperature measured
by the internal sensor while also displaying AIR
SAMPLING and ON, the humidity measured by
the internal sensor while also displaying %RH
and ON, and the frost sensor temperature while
also displaying ON. Scroll through these values
and by using the UP/DOWN arrow buttons.
7. Record values and call Technical Support.
Cycle Power
2120