KYORITSU KEW SNAP 2434 User manual

Other KYORITSU Test Equipment manuals

KYORITSU KEW4105DL User manual

KYORITSU

KYORITSU KEW4105DL User manual

KYORITSU KEW 6010B User manual

KYORITSU

KYORITSU KEW 6010B User manual

KYORITSU KEW 4105A User manual

KYORITSU

KYORITSU KEW 4105A User manual

KYORITSU KEW FORK User manual

KYORITSU

KYORITSU KEW FORK User manual

KYORITSU 3132A User manual

KYORITSU

KYORITSU 3132A User manual

KYORITSU kew 4300 User manual

KYORITSU

KYORITSU kew 4300 User manual

KYORITSU KEW FORK 2300 R User manual

KYORITSU

KYORITSU KEW FORK 2300 R User manual

KYORITSU 6011A User manual

KYORITSU

KYORITSU 6011A User manual

KYORITSU KEW 3022 User manual

KYORITSU

KYORITSU KEW 3022 User manual

KYORITSU KEW6201A User manual

KYORITSU

KYORITSU KEW6201A User manual

KYORITSU KEW3552 User manual

KYORITSU

KYORITSU KEW3552 User manual

KYORITSU 5406A User manual

KYORITSU

KYORITSU 5406A User manual

KYORITSU KEW3431 User manual

KYORITSU

KYORITSU KEW3431 User manual

KYORITSU KEW 3121A User manual

KYORITSU

KYORITSU KEW 3121A User manual

KYORITSU 6017 User manual

KYORITSU

KYORITSU 6017 User manual

KYORITSU 8031 User manual

KYORITSU

KYORITSU 8031 User manual

KYORITSU KEW8031F User manual

KYORITSU

KYORITSU KEW8031F User manual

KYORITSU 3165 User manual

KYORITSU

KYORITSU 3165 User manual

KYORITSU KEW6024PV User manual

KYORITSU

KYORITSU KEW6024PV User manual

KYORITSU KEW 8146 User manual

KYORITSU

KYORITSU KEW 8146 User manual

KYORITSU KEW3125A User manual

KYORITSU

KYORITSU KEW3125A User manual

KYORITSU 3321A User manual

KYORITSU

KYORITSU 3321A User manual

KYORITSU 3021A User manual

KYORITSU

KYORITSU 3021A User manual

KYORITSU 6050 User manual

KYORITSU

KYORITSU 6050 User manual

Popular Test Equipment manuals by other brands

Ambit P.F. Series instruction manual

Ambit

Ambit P.F. Series instruction manual

Megger BMM500 Series user guide

Megger

Megger BMM500 Series user guide

RJG Lynx Sensor Tester operating instructions

RJG

RJG Lynx Sensor Tester operating instructions

Mark-10 TT02 Series user guide

Mark-10

Mark-10 TT02 Series user guide

Martel 3001 Operator's manual

Martel

Martel 3001 Operator's manual

ElproSys DiagProg4 instruction manual

ElproSys

ElproSys DiagProg4 instruction manual

Redtech TRAILERteck T05 user manual

Redtech

Redtech TRAILERteck T05 user manual

Venmar AVS Constructo 1.0 HRV user guide

Venmar

Venmar AVS Constructo 1.0 HRV user guide

Test Instrument Solutions SafetyPAT operating manual

Test Instrument Solutions

Test Instrument Solutions SafetyPAT operating manual

Hanna Instruments HI 38078 instruction manual

Hanna Instruments

Hanna Instruments HI 38078 instruction manual

Kistler 5495C Series instruction manual

Kistler

Kistler 5495C Series instruction manual

Waygate Technologies DM5E Basic quick start guide

Waygate Technologies

Waygate Technologies DM5E Basic quick start guide

StoneL DeviceNet CK464002A manual

StoneL

StoneL DeviceNet CK464002A manual

Seica RAPID 220 Site preparation guide

Seica

Seica RAPID 220 Site preparation guide

Kingfisher KI7400 Series Training manual

Kingfisher

Kingfisher KI7400 Series Training manual

Kurth Electronic CCTS-03 operating manual

Kurth Electronic

Kurth Electronic CCTS-03 operating manual

SMART KANAAD SBT XTREME 3G Series user manual

SMART

SMART KANAAD SBT XTREME 3G Series user manual

Agilent Technologies BERT Serial Getting started

Agilent Technologies

Agilent Technologies BERT Serial Getting started

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTRUCTIONMANUAL
KEWSNAP 2434
KEWSNAP Series
LEAKAGECURRENTTESTER
KYORITSUELECTRICALINSTRUMENTSWORKS,LTD.,
TOKYO,JAPAN
1.SAFETYWARNINGS
ThisinstrumenthasbeendesignedandtestedaccordingtoIEC
Publication61010: Safety Requirements for Electronic Measuring
Apparatus. This instruction manual containswarnings and safety
ruleswhichmustbeobservedbytheusertoensuresafeoperation
ofthe instrumentandtoretainitinsafecondition.Therefore,read
throughthese operatinginstructionsbeforestartingusing the
instrument.
WARNING
●Readthroughandunderstandinstructions contained in this
manualbeforestartingusingtheinstrument.
●Save and keep the manual at hand to enable quick reference
whenevernecessary.
●Besuretousethe instrument only in its intended applications
andtofollowmeasurementproceduresdescribedinthe
manual.
●Besuretounderstandandfollowallsafetyinstructions
containedinthemanual.
Notfollowingtheaboveinstructionsmaycauseinjury,instrument
damageand/ordamagetoequipmentundertest.
Thesymbol indicated on the instrument means that theuser
mustrefertorelatedpartsofthemanualforsafeoperationofthe
instrument. Be sure to carefully read theinstructionsfollowing
each symbolinthismanual.
DANGER isreservedforconditionsandactionsthatarelikely
tocauseseriousorfatalinjury.
WARNING isreservedforconditions and actionsthatcan
causeseriousorfatalInjury.
CAUTION isreservedforconditionsandactionsthatcancause
minorinjuryorInstrumentdamage.
DANGER
●Nevermake measurementona circuithavingpotential of
300VACorgreater.
●Donotattemptto makemeasurementinthepresenceof
flammable gasses.  Otherwise, the use of the instrument may
causesparking,whichleadstoanexplosion.
●Thetransformerjawsaremadeofmetalandtheir tips are not
completely insulated. Be especially careful about the possible
shortingwheretheequipmentundertesthasexposedmetalparts.
●Neverattempttousetheinstrumentifitssurfaceoryourhandiswet.
●Do not exceed the maximum allowable input of any
measurementrange.
●Neveropenthebatterycompartmentcoverwhenmaking
measurement.
●Nevertrytomakemeasurementifanyabnormalconditions,
suchasbrokenTransformerjawsorcaseisnoted.
●Theinstrumentistobeusedonlyinitsintendedapplicationsor
conditions.Otherwise,safetyfunctionsequippedwiththe
instrumentdoesn'twork,andinstrumentdamage or serious
personalinjurymaybecaused.
Followingsymbolsareusedontheinstrumentandintheinstructionmanual.
Attentionshouldbepaidtoeachsymboltoensureyoursafety.
Refertotheinstructionsinthemanual.
Indicatesaninstrumentwithdoubleorreinforcedinsulation.
Indicatesthatthisinstrumentcanclamponbareconductorswhen
measuringavoltagecorrespondingtotheapplicableMeasurement
category,whichismarkednexttothissymbol.
IndicatesAC(AlternatingCurrent).
IndicatesEarth.
WARNING
●Neverattemptto makeanymeasurement,ifany abnormal
conditionsarenoted,suchasbrokencase,crackedtestleads
andexposedmetalparts.
●Do not install substitute parts or make any modification to the
instrument.ReturntheinstrumenttoKyoritsuoryourdistributor
forrepairorre-calibration.
CAUTION
●Makesurethattherangeselectorswitchissettoanappropriate
positionbeforemakingmeasurement.
●Donotexposetheinstrumenttothedirectsun,extreme
temperaturesordewfall.
●Besure to set the range selector switchto the "OFF" position
afteruse.Whentheinstrumentwillnotbeinuseforalong
periodoftime,placeitinstorageafterremovingthebatteries.
●Useadampclothanddetergentforcleaningtheinstrument.Do
notuseabrasivesorsolvents.
●Alwaysswitchofftheinstrumentbeforeopeningthe battery
compartmentcoverforbatteryreplacement.
2.FEATURES
●DigitalclamptesterforACleakagecurrentmeasurement.
●Leastaffectedbyexternalmagneticfield,providingwide
measuringrangefromverysmalltolargecurrents.
●DesignedtosafetystandardIEC61010-2-032:measurementCAT.
Ⅲ,300Vandpollutiondegree2.
●Dataholdfunctiontoallowforeasyreadingsindimlylitorhard-to-
reachlocations.
●Providesfilteringfunctiontoremovehighfrequencygeneratedby
suchequipmentasinverters.
●Sleepfunctionpreventsunnecessarypowerconsumption.
●Dynamicrangeof4000countsfullscale.
●Largeeasy-to-readLCDdisplaywithletterheightof13mm.
●Transformerjawsfittedwithguardtofurtherimprovesafety.
Measurementcategories(Over-voltagecategories)
Toensuresafeoperationofmeasuringinstruments,IEC61010establishes
safetystandardsforvariouselectricalenvironments,categorizedasCATIto
CATIV, and calledmeasurement categories. Higher-numberedcategories
correspondtoelectricalenvironmentswithgreatermomentaryenergy,soa
measuringinstrumentdesignedforCATIIIenvironmentscanenduregreater
momentaryenergythanonedesignedforCATII.
CAT.I:Secondary electrical circuits connected to an AC electrical outlet
throughatransformerorsimilardevice.
CAT.II:Primaryelectricalcircuitsofequipment connectedtoanAC
electricaloutletbyapowercord.
CAT.III:Primary electrical circuits of the equipment connected directly to
thedistributionpanel,andfeedersfromthedistributionpaneltooutlets.
CAT.IV:Thecircuit from the service drop to theservice entrance,and to
thepowermeterandprimary over-current protectiondevice
(distributionpanel).
Incoming wire
CAT.IV
Interior wiring
Transformer
CAT.I
CAT.II
CAT.III
S
ocke
t
3.SPECIFICATIONS
Measuringrangesandaccuracy
Measuringmethod: DualIntegration
Display: Liquid crystal display with maximum reading
of3999
Lowbatterywarning: "BATT"markappearsonthedisplay
OverrangeIndication: "OL"appearsonthedisplaywhenupperlimit
ofmeasuringrangeisexceeded
ResponseTime: Approx.2seconds
SampleRate: Approx.2.5timespersecond
Locationforuse Indooruse,Altitudeupto2000m
Accuracy-insured 23℃±5℃,relativehumidity85%orless
Temperatureand (withoutcondensation)
HumidityRanges:
OperatingTemperature 0-40℃,relativehumidity85%orless
andHumidityRanges: (withoutcondensation)
StorageTemperature -20-60℃,relativehumidity85%orless
andHumidityRanges: (withoutcondensation)
PowerSource: Two1.5VR03(UM-4)batteries
CurrentConsumption: Approx.4mA
MeasurementTime: Approx.150hours
SleepFunction: Automaticallypowereddowninabout10
minutesafterthelastswitchoperation
SafetyStandard: IEC61010-1,IEC61010-2-032
measurementCAT.Ⅲ300V, pollutiondegree
2IEC61326(EMC)
OverloadProtection: 120Armsmax.for10seconds
WithstandVoltage: 3700Vrms(50/60Hz)for1minutebetween
metalpartoftransformer jaws and housing
case(excepttransformerjawcase)
InsulationResistance: 10MΩ orgreaterat1000V between metal
partoftransformerjawsand housing case
(excepttransformerjawcase)
ConductorSize: Approx.28mmindiametermax.
Dimensions: 169(L)×75(W)×40(D)mm
Weight: Approx.220gincludingbatteries
Accessories: TwoR03(UM-4)batteries
CarryingcaseModel9052
Instructionmanual
OptionalAccessories: Multi-TranModel8004and8008
Whenmeasuringcurrentwhichpulseelementissuperposed,differencesof
theindicatedvalue may becausedbetweenranges, if thepeakvalue
exceedsthemeasurementrangetoalargeextent.Inthiscase,thereading
atthebiggerrangeshouldbetakenasarightvalue.
SensitivetransformerjawsareusedforLeakageclampmeter.Becauseof
thecharacteristicsoftransformerjaws,whichcanbeopenedandclosed,it
isimpossible toeliminatetheinterferenceofexternalmagnetic field
completely.Iftherearesomething,whichgeneratinglargemagneticfield,at
anearbysite,currentvaluecanbedisplayed(0 cannotbedisplayed.)
beforeclamping onthe conductor.For suchacase,pleaseusethe
instrumentatalocationfarfromthething,whichgeneratingmagneticfield.
Followingarethetypicalthingsgeneratingmagneticfield.
Conductorfedlargecurrent,Motor,Equipmentwhichhasmagnet,
Integratingwattmeter
Range
400mA
4A
100A
MeasuringRange
0〜399.9mA
0〜3.999A
0〜100.0A
Accuracy(Frequencyrange)
±2.0%rdg±4dgt(50/60Hz)
±3.0%rdg±5dgt(40〜400Hz)
4.INSTRUMENTLAYOUT
5.PREPARATIONSFORMEASUREMENT
5-1CheckingBatteryVoltage
SettheRange Selector Switch to any position otherthanthe OFF
position.Ifthemarksonthedisplayisclearlyvisiblewithout"BATT"
markshowing,batteryvoltageisOK.Ifthedisplayblanksor"BATT"
isindicated,replace the batteries according to section 8: Battery
Replacement.
NOTE
Whenthe instrumentisleftpoweredon, theSleepfunction
automatically shut the power off; The display blanks even if the
RangeSelectorSwitchis set to a position other than the OFF
positioninthisstate.Topowerontheinstrument,turntheRange
SelectorSwitchorpressanybutton.Ifthedisplaystillblanks,the
batteriesarecompletelyexhausted.Replacethebatteries.
5-2CheckingSwitchSetting
MakesurethattheRangeSelectorSwitchissettotheappropriate
range.
Alsomakesurethatdataholdfunctionisnotenabled.If
inappropriaterangeisselected,desired measurement cannot be
made.
TransformJaws
Trigger
RangeSelectorSwitch
HandStrap
Display
FrequencySelectorButton
DataHoldButton
●LCD
LowBatteryWarning
FrequencyResponse:
Wide
FrequencyResponse:
50/60Hz
DataHoldIndication
Unit
Barrier
92
―
1509A04
―
12
DISTRIBUTOR
Kyoritsu reserves the rights to change specifications or designs
describedinthismanualwithoutnoticeandwithoutobligations.
3-phase3-wiresystem
(In4-wiresystemwithneutral,
clampontoall4wires)
Single-phase2-wiresystem
(in3-wiresystemwithneutral,
clampontoall3wires)
Load
Load
6.OPERATINGINSTRUCTIONS
DANGER
●Inordertoavoidpossibleshockhazard,nevermakemeasurement
oncircuitshavingapotentialof300VACorgreater.
●Thetransformer jaws aremadeofmetalandtheirtipsarenot
completelyinsulated.Be especially carefulaboutthepossible
shortingwheretheequipmentundertesthasexposedmetalparts.
●Nevermake measurement with the battery compartment cover
removed.
●Keep your fingers and hands behind the barrier during
measurement.
CAUTION
●Takesufficientcaretonottoapplyshock,vibrationor
excessiveforceto thejawtips. Otherwise,preciselyadjusted
TransformerJawtipswillbedamaged.
●Whenaforeign substanceisstuckin thejawtips orthey
cannotproperlyengage, thetransformerjawsdo notfully
close.Insuchacase,donotreleasethejawtriggerabruptlyor
attempttoclosethe transformer jawsbyapplyingexternal
force.Make surethatthejawsclose bythemselvesafter
removingtheforeignsubstanceormakingthemfreetomove.
●Themaximumsizeofaconductortobetested is 28mm in
diameter.Accuratemeasurementcannotbemadeona
conductorlarger thanthis,becausethetransformerjaws
cannotfullyclose.
●Whenmeasuringlargecurrent,thetransformerjawsmaybuzz.
Thishasnoeffectontheinstrument'sperformanceorsafety.
6-1LeakageCurrentMeasurement
(1)SettheRange Selector Switchtothedesiredposition. Current
tomeasureshouldbewithintheselectedmeasuringrange.
(2)Measuringoutofbalanceleakagecurrent(SeeFig.1):
Clamp onto all conductors except a grounded wire.  Measured
currentvalueisshownonthedisplay.
(3)Measuringearthleakagecurrent(SeeFig.2):
Clampontoagroundedwire.Measuredcurrentvalueisshownon
thedisplay.
Fig.1Measuringoutofbalanceleakagecurrent
6-2HowtoUseFrequencySelectorButton
Whenhighfrequenciesfromsuchequipmentasinvertersare
presentinthecircuitundertest, theinstrumentmeasuresAC
currentofnotonly50Hzor60Hzoffundamentalfrequencybutalso
ofthesehighfrequenciesandharmonics.
Toeliminatetheeffectof such high frequency noise andmeasure
ACcurrent of 50Hz or 60Hzfundamental frequency, a "high-cut"
filter circuit in incorporated into the instrument which works when
"50/60Hz"frequencyresponse isselectedwiththeFrequency
SelectorButton. Cut-off frequency of the"high-cut" filter is about
160Hzwithattenuationcharacteristicofapprox.-24dB/octave.
WhentheFrequencySelectorButtonispressed,"50/60Hz"markis
shownontheleftsideofthedisplay.WhentheFrequencySelector
Buttonispressed again, frequency response is switchedtoWIDE
with"WIDE"markshownonthedisplay.
Note:
Characteristicof-24dB/octiavemeansthatsignalmagnitude
declinestoaboutonesixteenthofthatattheinitialfrequencywhen
frequencydoubles.KEWSNAP2434havethefollowingtwo
settingsfortheFrequencySelectorButton.
WIDE(40Hz-):Permitsmeasurementofcurrentsof fundamental
frequenciesaswell as currents of high frequencies
generatedbysuchequipmentasinverters
50/60Hz(40-approx.160Hz):Filtersouthighfrequencycurrentsand
measurescurrentoffundamental
frequencyonly
Fig.3KEWSNAP2434FrequencyCharacteristic
OutputcharacteristicareshowninFig.3.
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
;;;;
100%
50%
20%
10%
5%
5k1k 2k500100 200502010
ー30
ー20
ー10
 0
Attenuation〔dB〕
 10
Frequency〔Hz〕
Percentage
Typicalcharacteristic:
400mA/4ARange
Typicalcharacteristic:
WIDEfrequencyresponse
Typicalcharacteristic:
50/60Hzfrequencyresponse
high-cutfilter-24dB/oct
Typicalcharacteristic:
100ARange
Fig.2Measuringearthleakagecurrent
Load
Groundedwire
Recentlytherehasbeenincreaseduseofpowerthroughinverters,
switchingregulators,etc.Whenthehighfrequencynoisefromsuch
appliancesleaks or flows into the ground throughcapacitors not
filteringcompletely,theearthleakagebreakermaytripeventhough
thereisno"actual"leakage.Insuchacase,theinstrumentdonot
giveleakagecurrentreading if "50/60Hz" frequency response is
selected.
Takecurrent readingswiththe 50/60HzandWIDE frequency
responsesrespectivelytomakeeffective use of the Frequency
SelectorButton.
6-3LoadCurrentMeasurement
(1)SettheRangeSelectorSwitchtothedesiredposition. Currentto
measureshouldbewithintheselectedmeasuringrange.
(2)Measuringloadcurrent(SeeFig.4):
Pressthejawtriggertoopenthetransformerjawsandclose
themover oneconductoronly.Measured currentvalueis shown
onthedisplay.
7.OTHERFUNCTIONS
7-1SleepFunction
Thisisafunctiontopreventtheinstrumentfrombeingleftpowered
oninordertoconservebatterylife.
Theinstrumentautomaticallyenters the Sleep (powered-down)
Modeabout10minutesafterthelastswitchoperation.
ToexittheSleepMode,presstheDataHoldorFrequencySelector
ButtonorturntheRangeSelectorSwitchtoOFF,thentoanyother
position.
HowtoExittheSleepMode:
TurntheRange SelectorSwitchfromOFF to anotherposition
withtheData HoldButtonpressed.Then, P.OFF isshownon
thedisplay.ThisdisablestheSleepfunctionandenables
continuoususeoftheinstrument.
ToenabletheSleepfunction,turntheRangeSelectorSwitchback
toOFF,thentoanyotherposition.
Note:
TheinstrumentconsumessmallamountofcurrentintheSleep
Mode.Whentheinstrumentisnotinuse,makesuretosetthe
RangeSelectorSwitchtoOFF.
7-2DateHoldFunction
Thisisafunctiontofreezethereadingsonthedisplay.Whenthe
DataHoldButtonispressedonce,thecurrentreadingisheldeven
thoughcurrent under test varies. "H"mark is shown on the upper
rightcornerofthedisplay.
Toexitthedataholdmode,presstheDataHoldButtonagain.
Note:WhentheSleepfunctionworkswhiletheinstrumentisinthe
dataholdmode,dataholdiscancelled.
Fig.4Measuringloadcurrent
Load
8.BATTERYREPLACEMENT
CAUTION
●Donotmixnewandoldbatteries.
●Install batteries in the orientation as shown inside the battery
compartment,observingcorrectpolarity.
●Inordertoavoidpossibleshockhazard,alwayssettheRange
SelectorSwitchtotheOFFpositionbeforetryingtoreplacethe
batteries
Whenthe batteryvoltagewarningmark"BATT"isshownon the
top left corner of the LCD, replace the batteries.  Note that the
displayblanksand"BATT"markisnotshownifthebatteriesare
completelyexhausted.
(1)SettheRangeSelectorSwitchto"OFF."
(2)Loosenthebattery-compartment-cover-fixingscrewonthelower
backoftheinstrument.
(3)ReplacethebatterieswithtwonewR03(UM-4)1.5V
batteries.
(4)Putthebatterycompartment
cover back in place and
tightenthescrew.
Note:Use alkaline batteries to
performmeasuringforlong
9.OPTIONALACCESSORIES
Model8004and8008(Multi-Tran)
ThesemodelshelpKEWSNAP2434tomeasurecurrentgreaterthan
1000Aortomakemeasurementonalargebus-barorconductor.
(1)SettheRangeSelectorSwitchto"100A".
(2)Asshown,openthejawsandclosethemoverthepickupcoil
ofModel8004orModel8008.
(3)ClamponaconductorwithModel8004orModel8008.
(4)Takethereadingandmultiplyitby10.
Note: Model 8004 and Model 8008 cannot be used for leakage current
measurement.Fordetailedspecifications,refertothe
instructionmanualforModel8004orModel8008.
KEW2434
M-8004
M-8008
PickupCoil
Conductor
Transformer
jaws
10
 
 
:
 
 
1


M-8004
M-8008
Max.ConductorSize
60mmindiameter
100mmindiameter
Measuring
Range
0〜1000A
CurrentTransformation
Ratio
10:1
Screw Battery
Compartment
Cover
Batteries