INSTRUCTIONMANUAL
KEWSNAP 2434
KEWSNAP Series
LEAKAGECURRENTTESTER
KYORITSUELECTRICALINSTRUMENTSWORKS,LTD.,
TOKYO,JAPAN
1.SAFETYWARNINGS
ThisinstrumenthasbeendesignedandtestedaccordingtoIEC
Publication61010: Safety Requirements for Electronic Measuring
Apparatus. This instruction manual containswarnings and safety
ruleswhichmustbeobservedbytheusertoensuresafeoperation
ofthe instrumentandtoretainitinsafecondition.Therefore,read
throughthese operatinginstructionsbeforestartingusing the
instrument.
WARNING
●Readthroughandunderstandinstructions contained in this
manualbeforestartingusingtheinstrument.
●Save and keep the manual at hand to enable quick reference
whenevernecessary.
●Besuretousethe instrument only in its intended applications
andtofollowmeasurementproceduresdescribedinthe
manual.
●Besuretounderstandandfollowallsafetyinstructions
containedinthemanual.
Notfollowingtheaboveinstructionsmaycauseinjury,instrument
damageand/ordamagetoequipmentundertest.
Thesymbol indicated on the instrument means that theuser
mustrefertorelatedpartsofthemanualforsafeoperationofthe
instrument. Be sure to carefully read theinstructionsfollowing
each symbolinthismanual.
DANGER isreservedforconditionsandactionsthatarelikely
tocauseseriousorfatalinjury.
WARNING isreservedforconditions and actionsthatcan
causeseriousorfatalInjury.
CAUTION isreservedforconditionsandactionsthatcancause
minorinjuryorInstrumentdamage.
DANGER
●Nevermake measurementona circuithavingpotential of
300VACorgreater.
●Donotattemptto makemeasurementinthepresenceof
flammable gasses. Otherwise, the use of the instrument may
causesparking,whichleadstoanexplosion.
●Thetransformerjawsaremadeofmetalandtheir tips are not
completely insulated. Be especially careful about the possible
shortingwheretheequipmentundertesthasexposedmetalparts.
●Neverattempttousetheinstrumentifitssurfaceoryourhandiswet.
●Do not exceed the maximum allowable input of any
measurementrange.
●Neveropenthebatterycompartmentcoverwhenmaking
measurement.
●Nevertrytomakemeasurementifanyabnormalconditions,
suchasbrokenTransformerjawsorcaseisnoted.
●Theinstrumentistobeusedonlyinitsintendedapplicationsor
conditions.Otherwise,safetyfunctionsequippedwiththe
instrumentdoesn'twork,andinstrumentdamage or serious
personalinjurymaybecaused.
Followingsymbolsareusedontheinstrumentandintheinstructionmanual.
Attentionshouldbepaidtoeachsymboltoensureyoursafety.
Refertotheinstructionsinthemanual.
Indicatesaninstrumentwithdoubleorreinforcedinsulation.
Indicatesthatthisinstrumentcanclamponbareconductorswhen
measuringavoltagecorrespondingtotheapplicableMeasurement
category,whichismarkednexttothissymbol.
IndicatesAC(AlternatingCurrent).
IndicatesEarth.
WARNING
●Neverattemptto makeanymeasurement,ifany abnormal
conditionsarenoted,suchasbrokencase,crackedtestleads
andexposedmetalparts.
●Do not install substitute parts or make any modification to the
instrument.ReturntheinstrumenttoKyoritsuoryourdistributor
forrepairorre-calibration.
CAUTION
●Makesurethattherangeselectorswitchissettoanappropriate
positionbeforemakingmeasurement.
●Donotexposetheinstrumenttothedirectsun,extreme
temperaturesordewfall.
●Besure to set the range selector switchto the "OFF" position
afteruse.Whentheinstrumentwillnotbeinuseforalong
periodoftime,placeitinstorageafterremovingthebatteries.
●Useadampclothanddetergentforcleaningtheinstrument.Do
notuseabrasivesorsolvents.
●Alwaysswitchofftheinstrumentbeforeopeningthe battery
compartmentcoverforbatteryreplacement.
2.FEATURES
●DigitalclamptesterforACleakagecurrentmeasurement.
●Leastaffectedbyexternalmagneticfield,providingwide
measuringrangefromverysmalltolargecurrents.
●DesignedtosafetystandardIEC61010-2-032:measurementCAT.
Ⅲ,300Vandpollutiondegree2.
●Dataholdfunctiontoallowforeasyreadingsindimlylitorhard-to-
reachlocations.
●Providesfilteringfunctiontoremovehighfrequencygeneratedby
suchequipmentasinverters.
●Sleepfunctionpreventsunnecessarypowerconsumption.
●Dynamicrangeof4000countsfullscale.
●Largeeasy-to-readLCDdisplaywithletterheightof13mm.
●Transformerjawsfittedwithguardtofurtherimprovesafety.
Measurementcategories(Over-voltagecategories)
Toensuresafeoperationofmeasuringinstruments,IEC61010establishes
safetystandardsforvariouselectricalenvironments,categorizedasCATIto
CATIV, and calledmeasurement categories. Higher-numberedcategories
correspondtoelectricalenvironmentswithgreatermomentaryenergy,soa
measuringinstrumentdesignedforCATIIIenvironmentscanenduregreater
momentaryenergythanonedesignedforCATII.
CAT.I:Secondary electrical circuits connected to an AC electrical outlet
throughatransformerorsimilardevice.
CAT.II:Primaryelectricalcircuitsofequipment connectedtoanAC
electricaloutletbyapowercord.
CAT.III:Primary electrical circuits of the equipment connected directly to
thedistributionpanel,andfeedersfromthedistributionpaneltooutlets.
CAT.IV:Thecircuit from the service drop to theservice entrance,and to
thepowermeterandprimary over-current protectiondevice
(distributionpanel).
Incoming wire
CAT.IV
Interior wiring
Transformer
CAT.I
CAT.II
CAT.III
t
3.SPECIFICATIONS
Measuringrangesandaccuracy
Measuringmethod: DualIntegration
Display: Liquid crystal display with maximum reading
of3999
Lowbatterywarning: "BATT"markappearsonthedisplay
OverrangeIndication: "OL"appearsonthedisplaywhenupperlimit
ofmeasuringrangeisexceeded
ResponseTime: Approx.2seconds
SampleRate: Approx.2.5timespersecond
Locationforuse Indooruse,Altitudeupto2000m
Accuracy-insured 23℃±5℃,relativehumidity85%orless
Temperatureand (withoutcondensation)
HumidityRanges:
OperatingTemperature 0-40℃,relativehumidity85%orless
andHumidityRanges: (withoutcondensation)
StorageTemperature -20-60℃,relativehumidity85%orless
andHumidityRanges: (withoutcondensation)
PowerSource: Two1.5VR03(UM-4)batteries
CurrentConsumption: Approx.4mA
MeasurementTime: Approx.150hours
SleepFunction: Automaticallypowereddowninabout10
minutesafterthelastswitchoperation
SafetyStandard: IEC61010-1,IEC61010-2-032
measurementCAT.Ⅲ300V, pollutiondegree
2IEC61326(EMC)
OverloadProtection: 120Armsmax.for10seconds
WithstandVoltage: 3700Vrms(50/60Hz)for1minutebetween
metalpartoftransformer jaws and housing
case(excepttransformerjawcase)
InsulationResistance: 10MΩ orgreaterat1000V between metal
partoftransformerjawsand housing case
(excepttransformerjawcase)
ConductorSize: Approx.28mmindiametermax.
Dimensions: 169(L)×75(W)×40(D)mm
Weight: Approx.220gincludingbatteries
Accessories: TwoR03(UM-4)batteries
CarryingcaseModel9052
Instructionmanual
OptionalAccessories: Multi-TranModel8004and8008
Whenmeasuringcurrentwhichpulseelementissuperposed,differencesof
theindicatedvalue may becausedbetweenranges, if thepeakvalue
exceedsthemeasurementrangetoalargeextent.Inthiscase,thereading
atthebiggerrangeshouldbetakenasarightvalue.
SensitivetransformerjawsareusedforLeakageclampmeter.Becauseof
thecharacteristicsoftransformerjaws,whichcanbeopenedandclosed,it
isimpossible toeliminatetheinterferenceofexternalmagnetic field
completely.Iftherearesomething,whichgeneratinglargemagneticfield,at
anearbysite,currentvaluecanbedisplayed(0 cannotbedisplayed.)
beforeclamping onthe conductor.For suchacase,pleaseusethe
instrumentatalocationfarfromthething,whichgeneratingmagneticfield.
Followingarethetypicalthingsgeneratingmagneticfield.
Conductorfedlargecurrent,Motor,Equipmentwhichhasmagnet,
Integratingwattmeter
Range
400mA
4A
100A
MeasuringRange
0〜399.9mA
0〜3.999A
0〜100.0A
Accuracy(Frequencyrange)
±2.0%rdg±4dgt(50/60Hz)
±3.0%rdg±5dgt(40〜400Hz)
4.INSTRUMENTLAYOUT
5.PREPARATIONSFORMEASUREMENT
5-1CheckingBatteryVoltage
SettheRange Selector Switch to any position otherthanthe OFF
position.Ifthemarksonthedisplayisclearlyvisiblewithout"BATT"
markshowing,batteryvoltageisOK.Ifthedisplayblanksor"BATT"
isindicated,replace the batteries according to section 8: Battery
Replacement.
NOTE
Whenthe instrumentisleftpoweredon, theSleepfunction
automatically shut the power off; The display blanks even if the
RangeSelectorSwitchis set to a position other than the OFF
positioninthisstate.Topowerontheinstrument,turntheRange
SelectorSwitchorpressanybutton.Ifthedisplaystillblanks,the
batteriesarecompletelyexhausted.Replacethebatteries.
5-2CheckingSwitchSetting
MakesurethattheRangeSelectorSwitchissettotheappropriate
range.
Alsomakesurethatdataholdfunctionisnotenabled.If
inappropriaterangeisselected,desired measurement cannot be
made.
TransformJaws
Trigger
RangeSelectorSwitch
HandStrap
Display
FrequencySelectorButton
DataHoldButton
●LCD
LowBatteryWarning
FrequencyResponse:
Wide
FrequencyResponse:
50/60Hz
DataHoldIndication
Unit
Barrier