89
In the event of a trip
1. Switch o the power supply and then check if the reason for the
tripping is apparent and If possible correct the issue.
2. Allow at least 60 seconds aer it has tripped and do not reset the trip
with the mains power switched on.
3. Press the centre of the button back into the trip. When re-set the
button will stay pressed in when you release your nger.
4. Restore power to the power cassette and check that the trip remains
set.
5. If the trip operates again you should rst switch o the mains and then
switch o or unplug everything in the locker sockets.
6. Re-set the trip (steps 2 and 3 above)
7. Restore power to the power cassette and check that the trip remains
set.
8. Then, one by one, re-plug everything into the locker sockets, switch on
and check that the trip remains set.
If the trip will not re-set or it continues to trip, there may still be a fault
somewhere or the trip may have developed a fault so please contact our
customer support desk: 01787 226166 OR 0800 130 3456
Power Cassette (when fitted)
The power cassette on the top of your FLEX™ Locker Tower may get warm
when it is managing a higher electrical load for a period of time and
because of this possibility the ventilation holes in the cassette should not
be obstructed.
In the United Kingdom the detachable mains lead to the power cassette
will carry a fuse in the wall plug for the protection of users. In the event
that your FLEX™ Locker Tower has been installed with no wall plug the
power cassette also has a resettable trip which is alongside the mains
input socket. This trip acts in much the same way as a fuse to protect users
and it can be re-set. When the has operated, the centre of the button will
extend by approximately 12mm.