LBS Dragon Power 2 User manual

USER MANUAL

Safety precautions
Operation
1. Before using this product, please read "safety precautions" carefully to ensure correct and
safe use, and please keep the manual properly.
2. During operation, please pay attention to all warning signs and operate as required.
3. Do not use the device in direct sunlight, rain or the humid environment.
4. This equipment should not be installed near the heat source area or similar equipment such
as electric heater and hot stove.
5. A safe distance and ventilation should be reserved around the UPS. Please refer to the
manual for installation.
6. Please use dry cleaning tools for wiping or cleaning the UPS.
7. In case of fire, please use the dry powder extinguisher correctly. There is a risk of electric
shock if a liquid fire extinguisher is used.
Electrical safety
1. The battery life is shortened with the increase of ambient temperature. Regular battery
replacement can ensure the UPS to work normally and provide sufficient backup time.
2. Battery maintenance can only be carried out by personnel with battery expertise.
3. There is a risk of electric shock and short circuit in the batteries. To avoid personal injury
caused by electric shock, please observe the following warnings when replacing batteries:
A. Do not wear watches, rings or similar metal objects;
B. Use insulated tools;
C. Wear rubber shoes and gloves;
D. Do not place metal tools or similar parts on the battery.
E. Disconnect the load from the batteries before removing the battery connection terminal.
4. Please do not expose the battery to the fire for avoiding explosion and endangering the
safety of life.
5. Non-professionals should not open or damage the battery, because the electrolyte in the
battery contains dangerous substances such as strong acid, which can cause harm to the skin
and eyes. If you accidentally touch the electrolyte, immediately wash it with plenty of water
and go to the hospital for examination.
6. Please do not short-circuit the positive and negative poles of the battery, which may cause
electric shock or fire.
Use and maintenance
1. The use environment and preservation method have influence on the service life and
reliability of this product. Please do not use it in the following working environment:
A. High, low temperature and humid places exceeding the technical
specifications(temperature 0-40℃, relative humidity 20%-90%).
B. Places with vibration and vulnerable to collision.
C. Places with metal dust, corrosive substance, salt and combustible gas.
2. If it is not used for a long time, the UPS(without battery) must be stored in a dry
environment at the temperature range: -15-60℃. Before starting UPS, the ambient
temperature must be warmed to 0℃above and maintained for more than 3 hours.

Content
1. Introduction .....................................................................................................................................1
1.1 Symbol ..................................................................................................................................1
1.2 Rear view..............................................................................................................................2
1.3 Specification .........................................................................................................................3
1.4 Electromagnetic compatibility............................................................................................4
2. Installation........................................................................................................................................5
2.1 Unpacking inspection..........................................................................................................5
2.2 Wiring schedule ................................................................................................................... 5
2.3 UPS connection ....................................................................................................................5
2.4 External battery connection of long back up type UPS.................................................... 6
2.5 Connection to the computer .............................................................................................. 7
3. Control Panel ....................................................................................................................................8
3.1 Panel display........................................................................................................................ 8
3.2 Function of button...............................................................................................................9
3.3 UPS working status table of LCD display..........................................................................10
3.4 Parameter query ................................................................................................................11
3.5 Function setting.................................................................................................................12
4. Warning code/fault code and solution ........................................................................................15
4.1 Warning code and solution...............................................................................................15
4.2 Fault code and solution .....................................................................................................16
4.3 Common faults and trouble shooting ..............................................................................18
5. Control and communication.........................................................................................................19
5.1 SNMP Card......................................................................................................................... 19
5.2 Dry Contact........................................................................................................................ 19
5.3 EPO ..................................................................................................................................... 20
6. Battery Maintenance & Repair .....................................................................................................21

1
1. Introduction
This series of UPS is an online sine wave uninterruptible power supply system with bypass
maintenance switch, which can provide reliable and high-quality AC power for your precision
equipment. It can be used in a wide range, from computer equipment, communication system
to industrial automatic control equipment. Because of its online design, it is different from the
backup ups. It continuously adjusts and filters the input voltage. When the power supply is
interrupted, it will provide the backup power from the backup battery without time
interruption. In case of overload or inverter failure, the UPS switches to the bypass state and
be powered by the mains. If the overload is cleared, the UPS will automatically switch back to
the inverter power supply state.
This manual is applicable to the follow products, including:
6KS: Standard UPS with built-in output isolation transformer and batteries.
6KL: Long backup time UPS with built-in output transformer, which connects external batteries.
10KS: Standard UPS with built-in output isolation transformer and batteries;
10KL: Long backup time UPS with built-in output transformer, which connects external
batteries.
1.1 Symbol
Symbols and Meanings
Symbols Meanings
Attention
Danger
AC (alternating current)
DC (direct current)
Protective earth conductor
Protective connecting conductor
Loop
Do not place with sundries
Overload
Battery
ON/OFF Switch

2
1.2 Rear view
6KL/10KL (ISO) 6KS/10KS (ISO)
① Computer interface
② Smart slot (optional)
③ External battery connection
④ USB port
⑤ Input breaker
⑥ Maintenance bypass breaker
⑦ Terminal block
⑧ Parallel kit (optional)
⑨ EPO
⑩ Output breaker
⑪ Battery breaker

3
1.3 Specification
Model
3K
6KS 6KL 10KS 10KL
Capacity 6kVA/6kW 10kVA/10kW
Input
Nominal Voltage 208/220/230/240VAC, L1+L2+PE
Voltage Range 100-300VAC
Frequency 40-70Hz
Power Factor >0.99
THDi ≤5% (linear load); ≤8% (non-linear load)
Output
Nominal Voltage 208/220/230/240VAC or 110/115/120VAC, L1+N1+L2+N2+PE
Voltage Regulation ±1%
Frequency 50/60Hz±0.1%
Crest Ratio 3:1
Voltage Harmonic Distortion ≤2% (linear load); ≤5%(non-linear load)
Transfer Time Line mode to battery mode,0ms; inverter to bypass ,4ms (typical)
Waveform Pure sine wave
Overload time
Line mode: Battery mode:
30 min@102%-110% load 10 min@102%-110% load
10 min@110-130% load 1 min@110-130% load
30s@130%-150% load 10s@130%-150% load
200ms@>150% load 200ms@>150% load
Efficiency
Line Mode 93.5%
Battery Mode 91.5%
ECO Mode 98%
Battery
Type Sealed lead acid maintenance free
Voltage 192VDC/240VDC
Battery Number 12V 7Ah*16/20pcs External 12V 7Ah*16/20pcs External
Charging Current 1A 1-12A,settable 1A 1-12A,settable
ee
Charging Mode Two/Three period charging
Management
Intelligent port RS232/USB port/SNMP card (optional)/Dry contact kit (optional)
Environment
Operation Temperature 0-40℃
Relative Humidity 0-95%(non-condensing)
Audible Noise <50dB@1 meter
Altitude The altitude should not exceed 1000m, and the height above 1000m
should be reduced to a maximum of 4000m. Refer to IEC 62040

4
Load at high altitude=Rated power *Derating factor (corresponding to altitude)
Altitude(m) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating factor 100% 95% 91% 86% 82% 78% 74% 70% 67%
Notice: If the machine is used at above 1000m, diminishing ratings output must be used,
please refer to above table for derating factor.
1.4 Electromagnetic compatibility
Safety
IEC/EN 62040-1-1
EMI
Conducted Emission……IEC/EN 62040-2 Class A
Radiated Emission.........IEC/EN 62040-2 Class A
EMS
ESD.................................IEC/EN 6100-4-2 Level 4
RS...................................IEC/EN 6100-4-3 Level 3
EFT..................................IEC/EN 6100-4-4 Level 4
SURGE............................IEC/EN 6100-4-5 Level 4
Low Frequency Signals……IEC/EN 6100-2-2
Warning: This is a product for commercial and industrial application in the second
environment-installation restriction or additional measures may be needed to prevent
disturbances.
NOTICE:
This is a product for restricted sales distribution to informed partners. Installation restrictions
or additional measures may be needed to prevent radio interference.
Operate the UPS in an indoor environment only in an ambient temperature range of
0-40℃(32-104℉). Install it in a clean environment, free from moisture, flammable liquids,
gases and corrosive substance.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS ON/OFF
push buttons do not electrically isolate internal parts. Under no circumstance attempt to gain
access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the panel indications are not accordance with these
operating instructions or the UPS performance alters in use. Reflect all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and the precautions.
Keep unauthorized personnel away from the batteries. Proper disposal of batteries is required.
Refer to your local laws and regulations for disposal requirement.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the
UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryer or any appliance
using half-wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn off and isolate the UPS before cleaning it. Use only a dry cloth, never liquid or aerosol
cleaners.

5
2. Installation
Warning: To ensure safety, please pay attention to cut off the AC breaker before installation.
The battery breaker also need to be cut off, if its a long backup time model.
Caution:
1. Installation and wiring must be performed by professional personnel in accordance with
local regulations.
2. The UPS needs to connect to the ground.
2.1 Unpacking inspection
Inspect the appearance of the UPS to see if there is any damage during transportation. Do not
turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking
some parts.
Recycling: The packing boxes are recyclable, so please keep them well for using in the
future.
2.2 Wiring schedule
Attention: The diameter of the cable and the cross-sectional area of the three wires
depend on the real power of the UPS.
Model AWG
Input
Output
Battery
Earth
wire
6K
S(L)
10
(6mm
²
)
10
(6mm
²
)
10
(6mm
²
)
10
(6mm
²
)
10KS(L) 8 (10mm²) 8 (10mm²) 8 (10mm²) 8 (10mm²)
2.3 UPS connection
Warning: The rated current for the switch of the AC power must be larger than the UPS
maximum input current. Otherwise the switch of the AC power will be burned and destroyed.
1. Please choose the wire according to the table
of wiring.
2. Remove the terminal cover on the back panel
of the UPS①.
3. Connect the input and output wires to the
corresponding input and output terminals.
4. Tie the wire tightly and pass through the holes②.
5. Tie the input, output and battery wire with the
wire, adjust the wire to the appropriate position
and fix the cable.

6
Warning: When you are connecting the wire, please make sure that the input, output wire
and the input, output terminals are connected tightly.
Terminals block:
6. Reinstall the cover and lock the cover with a screwdriver①.
7. After connecting the wire and AC, then put the UPS input breaker to "ON", the UPS will be
powered.
2.4 External battery connection of long back up type UPS
The nominal DC voltage of external battery pack is 192VDC. Each battery pack consists of 10
pieces of 12V batteries in series. To achieve longer backup time, its possible to connect
multi-battery packs.
The battery connecting procedure is very important, if you do not follow the procedure, you
may encounter the hazardous of electric shock. So please strictly follow the steps below.
1. Set the battery breaker in "OFF" position and connect suitable battery in series.
2. Selecting a suitable battery cable to connect between the battery pack and UPS.(Refer to
table 2.2) One DC breaker must be connected between the battery pack an the UPS, The
capability of breaker must be not less than the data specified in the general.
Model
6K
S
(L)
10K
S
(L)
Battery
voltage
192VDC
192VDC
Battery current 34A. max 56A.max

7
Warning: Please do not connect to the terminals of UPS first, otherwise you may encounter
the hazardous of electric shock.
3. Connect the other end of the battery cable to the UPS, and then connect to the battery
pack. The UPS does not connect any load first, and then turns the battery pack switch to "ON",
then turn on AC, the UPS begins to charge.
Caution: ground mark.
2.5 Connection to the computer
RS232: Using RS232 to connect UPS with the monitoring equipment
1. Use RS232 communication cable to connect to the computers RS232 port first.
2. Then use the other terminal of RS232 to connect to the UPS’s RS232 port.
USB: Using USB to connect UPS with the monitoring equipment
1. Use USB communication cable to connect to the computers USB port first.
2. Then using the other terminal of USB to connect to the UPS’s USB port.
RS232 Interface on UPS:

8
3. Control Panel
3.1 Panel display
Display Function
Error
message
FAULT
Failure
occurred
Warnings
Fault
code
Mute
Mute
function
Input
and
output
voltage,
DC
voltage,
UPS
internal
temperature
VAC: input and output voltage; VDC: DC voltage
℃
:
UPS
internal
temperature;
Hz:
Frequency
Load
information
The load volume(0-25%, 26%-50%, 51%-75%, 76%-100%) is shown here,
and
the
overload
icon
flashes
when
the
battery
is
low
or
not
connected
Battery information
The battery capacity(0-25%, 26%-50%, 51%-75%, 76%-100%) is displayed
separately, and the battery icon flashes when the battery is low or not
connected
Other information
AC
Battery
Bypass
Inverter
Output
working
Fan status: LED will always be on when the fan is normal, and flashes when
the
fan
fails
Setting icon: when entering the setting menu, the icon will light up, and the
icon
is
n
o
t
shown
in
the
other
cases
ECO function: the icon light up when ECO function is used, otherwise the
icon
is
not
displayed
Maintenance icon: when the maintenance switch is turned on, the icon
lights up, in the other cases, the icon is not displayed

9
3.2 Function of button
Button Functional Description
Combo key for turning on the UPS AC Mode: press the two buttons at the same time for 1
second above to start UPS.
Battery Mode: please press confirmation button first,
after turning on the screen, please press the two buttons
at
the
same
time
for
1
second
above
to
start
UPS.
Combo key for turning off the UPS AC Mode: press the two buttons at the same time for 1
second above to turn off the inverter, the system will turn
to Bypass Mode.
Battery Mode: press the two buttons at the same time for
1 second above to turn off the inverter, and after 1
minute, the system will shut down, and the screen will
turn
off.
Combo key for self-checking and
mute function
Testing: in AC Mode, press the two buttons at the same
time for 2 seconds above to test the battery.
Mute: in Battery Mode/Alarm/Testing Mode, press two
buttons at the same time for 2 seconds above to erase
alarms, press two buttons again for 2 seconds above to
recover alarms.
Function setting/confirmation key Function setting: press the key more than 2 seconds to
enter the function setting page, after completing the
setting, press the key more than 2 seconds again to return
to the main page.
Confirmation: in the function setting page, press the
confirmation key 1 to 2 seconds to confirm the setting
options.
Page turning/query key Page turning: press or key 1 to 2 seconds to turn
to left or right page.
Polling Mode: press the key more than 2 seconds to
enter Polling Mode, circularly display each page content
for 2 seconds, press more than 2 seconds again to
return to the main page.
3.3 Audible alarm
Buzzer
alarms
Description
Continuous
beeping
Fault
Sounding every one second
Battery
voltage
low
Overload
Sounding
every
two
minutes
Bypass
mode
Sounding every four seconds Other alarms except the above

10
3.4 UPS working status table of LCD display
AC Mode
LCD display content Instruction
UPS can provide stable AC output when AC input in the
permissible range. In AC Mode, batteries will also be charged by
the UPS.
Battery Mode
LCD display content Instruction
When the AC input is out of limited range or shut off, the UPS will
turn to Battery Mode. The batteries supply the inverter and have
beep every 4 seconds.
Bypass Mode
LCD
display
content
Instruction
When the AC input keeps normal, start the bypass mode and close
the UPS on the panel. The UPS will turn to Bypass Mode, and have
beep every 2 minutes.
Error
Condition
LCD
display
content
Instruction
When the UPS has faults or alarms, LCD display will show the
information.

11
3.5 Parameter query
Normally the LCD display can show 8 pages totally. Pressing the query button or for
0.1-2 sec can enter into the different pages which show all information, such as input, battery,
output, load, software version, temperature, and etc. If alarms occur, the display will add one
more page to show the alarm information. If the UPS has faults, the default display will turn to
the Fault code page automatically, the home page will show the fault or alarm information by
default. When UPS keeps normal working, the home page default display will show the output
voltage and frequency information.
Press (right button) more than 2 sec, LCD will turn to the polling mode. Every 2 sec the
shown display will turn pages. Press long time, LCD will exit the polling mode.
LCD
Display
1:
UPS
input
&
output
voltage
LCD
Display
2:
UPS
input
&
output
frequency
LCD Display 3: Battery voltage and capacity LCD Display 4: Output voltage and output
active
power
LCD Display 5: Output voltage and output
apparent
power
LCD Display 6: Output voltage and load
percentage
LCD Display 7: UPS system software version LCD Display 8: connected battery quantity

12
3.6 Function setting
01: Output voltage
LCD
Display
Setting
1. Press the function setting button over 2 sec, then go to
the setting page. Press the page turning buttons till the setting
page of output voltage, and the word "OPU" flashing.
2. Press confirmation button 0.5-2 sec, then go to the
setting page of output voltage OPU. The "OPU" words light on,
and the numbers by left side of OPU keeps flashing. Press page
turning buttons or 0.5-2sec to choose different output
voltage value, the optional voltage values are 208V, 220V, 230V
and 240V. The default output voltage is 220V. Please save after
setting.
3. Turn to the voltage value which you need, and press
confirmation button 0.5-2sec, then finish the OPU setting.
The number by left side of OPU will keep lighting on, no flashing.
4. Press functional setting button over 2 sec, quit the
setting page and back to the home page.( Or no operation,
waiting more than 30 sec, the page will come back to home page
automatically).
Note: When the output voltage setting with 208V, the output
needs to decrease to 90% of rated power.
02: Other functional setting
02-1: Expert Mode (EP)
LCD
Display
Setting
The expert mode setting with ON, then go to the functional
setting page again. The functional setting will show battery QTY
(PCS), EPO, charging current and other items can be selected.
When the expert mode setting with OFF, functional setting page
will show only the general options.
Note: The expert mode default to OFF. When setting as ON then
re-connected the AC power, the EP can be recovered as OFF.

13
02-2 Battery low voltage shutdown point/End of discharge voltage (EOD)
LCD Display Setting
The options of EOD setting are dEF, 9.8V, 9.9V, 10V, 10.2V, 10.5V.
By default, the EOD is dEF
(The EOD will be changed according to loading condition.
10.5V@load <25%,10.2V@25%<load<50%,10V@load>
50%).
02-3: Economic Operation Mode
LCD
Display
Setting
ECO is OFF by default, can be set as ON to improve the efficiency
of system operation.
Note: For the models with PF <1, OFF by default, and unable to
set.
02-4: Emergency shutdown (EPO)
LCD
Display
Setting
When EP is set to ON, the EPO option appears on the function
setting page. Emergency shutdown can be set as closed or open
to trigger, the default is open to trigger.
Note: After EPO action, emergency shutdown, close all outputs
immediately.

14
02-5: Battery quantity (PCS)
LCD Display Setting
When EP is set to ON, the PCS option appears on the function
setting page, will enter the password page, enter the password
(the general password is 135), you can set the number of
batteries. The default battery number is 16pcs, which can be set
to 16/18/20pcs.
02-6: Charger Current (CHG)
LCD Display Setting
When EP is set to ON, the CHG option appears on the functional
setting page, the charging current can be set, 1-12A optional,
default 1A. Noted: if UPS built-in batteries, the charger current
default 1A, and cant be changed.
02-7: Input Neutral and Live cable reverse alarm function
LCD Display Setting
The input neutral and live cable reverse alarm mode is closed by
default, can choose to open to improve the safety of the system.
Note: Factory settings default closed, please open if you need.

15
4. Warning code/fault code and solution
4.1 Warning code and solution
When the " "symbol on the UPS LCD flashes, the UPS is in alarm state. Press the page turning
key to the error state page (refer to 3.5), observe the alarm code and make appropriate
processing according to the table below.
Alarm
code
Indication Possible reasons Treatment measures
1No battery
connection
1. No battery connected
2.
Battery
damage
d
1. Check the connection of batteries.
2.
Change
the
batter
ies
.
2Battery low
voltage
The battery voltage is less than
the low voltage warning point.
The batteries discharge to below
the
alarm
point.
After the battery has been sat for a
period of time, it can be turned on
again. The built-in charger can be
turned
on
to
charge
the
battery.
4Input neutral
and live cables
are reversed
1. Input neutral and live cables
are reversed.
2. Input ground cable is not
connected.
3. Output ground cable is not
connected.
1. Reverse the neutral and the live
cables.
2. Check the ground cable
connection.
8Battery over
voltage UPS detects high battery voltage Check that the battery quantity
setting is consistent with the actual
battery
quantity.
9
Charger
failure
Abnormal
charger
hardware
Contact
the
supplier.
10 Over
temperature
alarm
1. Fan fault
2. Air duct of UPS rear panel is
blocked.
3. Overload
4. NTC sensor abnormal or
connection abnormal
5. Power component IGBT is
damaged.
1. Check the rectifier fan.
2. Remove blockages on the rear
panel of the UPS.
3. Check the load.
4. If the above treatments do not
work, contact the supplier.
12 Fan fault 1. Fan wiring is loose.
2.
Fan
hardware
abnormal
Check the fan and connection
13
AC
fuse
open
Fuse
blown
Contact
the
supplier.
14
EEPROM
fault
EEPROM
chip
damages.
Contact
the
supplier.
21 Overload The loads exceed the rated
power
.
Check the load.
22 3 times
consecutive
overload
locks
3 times consecutive overload
locks Shut down and restart UPS.
23 EPO action Press EPO button. 1. Release EPO button.
2. Check the wiring harness on EPO
button.
24 Maintenance
switch action The maintenance switch is
pressed. Release maintenance switch.

16
4.2 Fault code and solution
When the "FAULT" is long bright, and " "symbol on the UPS LCD flashes, the UPS is in fault
state. UPS automatically switches to the error status page (refer to 3.5) to observe the fault
code and make appropriate processing according to the following table.
Fault
code
Indication Possible reasons Treatment measures
1 Bus boosting soft-
starting fail
1. AC abnormal
2. Abnormal soft-starting
circuit of bus
Check the mains, if all normal,
please contact the supplier.
2 Bus over voltage 1. AC abnormal
2. Software processing error
3.
Bus
capacitor
failure
Check the mains, if all normal,
please contact the supplier.
3 Bus under voltage 1. City electricity is too low.
2. Software processing errors
3. Bus capacitor failure
1. Please check the rectifier fan.
2. Clean the obstacles on the air
duct of the rear panel of the UPS.
3. Check the loads.
4. If all of above do not work, please
contact
the
supplier.
7 Over temperature 1. Fan failure
2. The air duct on the rear
panel of the UPS is blocked;
3. Overload
4. NTC sensor abnormality or
abnormal wiring
5. Power component IGBT is
damaged.
1. Please check the rectifier fan;
2. Clean the obstacles on the air
duct of the rear panel of the UPS;
3. Check the loads;
4. If all of above do not work, please
contact the supplier.
8 Battery relay
short circuit
Relay RL1/RL3 hardware
damaged
Please contact the supplier
9 Bus relay soft-
starting fail
1. City electricity abnormal
2. Bus soft-staring circuit
abnormal
Please check the city electricity
power, if no abnormal, please
contact
the
supplier.
17 Inv soft-starting
fail
1. Some hardware of the
inverter is damaged;
2. The control panel fails.
Please contact the supplier.
18 Inv output over
voltage
1. Some hardware of the
inverter is damaged;
2. The control panel fail.
Please contact the supplier.
19 Inv output under
voltage
1. Some hardware of the
inverter is damaged;
2. The control panel fails.
Please contact the supplier.
20 Inv short circuit 1. Some hardware of the
inverter is damaged.
2. Output short circuit
1. Check if the short circuit exists on
the output of UPS.
2. Check if the load is short circuit.
3. If no abnormal, please contact
the supplier.

17
26 Negative power
protection(output
with AC input fail)
1. Bypass reverses to the
inverter.
2. load abnormal
Check the loads and if no abnormal,
please contact the supplier.
33 Inv relay or SCR
open circuit
Relay RL8 is damaged. Please contact the supplier.
34 Inv relay or SCR
short
circuit
35 Bypass relay or
SCR
open
circuit
Relay RL4/RL6 is damaged. Please contact the supplier.
36 Bypass relay or
SCR short circuit
37 I/O connection
reversed
Reverse wiring on input and
output.
Please check the wiring harness of
input and output.
39 Charger short
circuit
1. Output of charger short
circuit
2.
Charger
hardware
abnormal
Please contact the supplier.
66 Over load fault 1. Overload too much
2. The voltage reduction
causes the system rated power
to
decrease.
1. Check if the load is within the
specified range;
2. Check if the voltage has been
reduced.
67 Charging over
voltage or battery
connection
reversed
1. Hardware error
2. Number of battery wrong;
3. Wiring wrong.
1. Check whether the battery wiring
or battery number meets the
requirements.
2. If no any abnormal, please
contact
the
supplier.
68 Unknown
machine model
Software version error 1. Restart the machine;
2. If no any abnormal, please
contact the supplier.
72 Charger over
current
1. Hardware error;
2. Battery abnormal.
1. Check whether the battery wiring
or battery number meets the
requirements;
2. If no any abnormal, please
contact
the
supplier.
73 No bootstrap Software version error 1. Restart the machine;
2. If no any abnormal, please
contact
the
supplier.
81 Unknown battery
QTY
setting
Number of battery wrong 1. Check whether the battery
number meets the requirement;
2. Check if the configuration of the
battery jumper cap is the same as
the software setting.
82 Battery QTY
setting matching
error
Number of battery setting
wrong and cannot be matched
with software setting.
Other manuals for Dragon Power 2
1
Table of contents