The following table shows the configuration possibilities. The display's top line shows the
option, the bottom line is the value that can be changed.
option
Basic load ON 0 – 200 (500) cm This value establishes the switch-on point for the first pump
Basic load OFF 0 – 200 (500) cm This value establishes the switch-off point for the first pump
Peak load ON 0 – 200 (500) cm This value establishes the switch-on point for the second
pump
Peak load OFF 0 – 200 (500) cm This value establishes the switch-off point for the second
pump
High water 0 – 200 (500) cm When the configured value is transgressed, the common fault
report relay and the high water relay will switch
Running time max 0 – 60 sec. The value 0 deactivates this function. If the value is set between 1-60
min. the pump shuts off if the set operating time has been exceeded
without interruption
Run time altern. Is deactivated
1 – 60 min
When the configured time is transgressed in basic load mode,
there will be a pump change.
Start delay 0 – 900 sec. After loss of power, the pumps won't start until after the
configured time has passed. The display shows the remaining
time.
Stop delay 0 – 180 sec. The basic load pump will continue to run after transgressing
the shut off point until the configured time has ended.
Interpump Delay 0 – 60 sec. When both pumps are triggered, then the 2nd pump won't turn
on until after the configured time has passed.
Force activation Is deactivated,
1 – 10s
Is activated = When the pumps are not triggered for 24 hours,
then they will automatically run for the configured
Acoustic alarm Is deactivated,
is activated
Is activated = when there is an error, the internal piezo buzzer
will sound
Intermitt. alarm Is deactivated,
is activated
Is activated = The error report relay is clocked.
Instead of a blinking light, a more economical solid light can
be used.
Pump alternation Is deactivated,
is activated
Is activated = After each use of the basic load pump, there will
be a change to the other pump.
P1: therm fault 1 Is deactivated,
is activated
Is shut off = On block 31, 32 (pump 1), no bimetal contact
(warning contact) is connected.
P2: therm fault 1 Is deactivated,
is activated
Is shut off = On block 38, 39 (pump 2), no bimetal contact
(warning contact) is connected.
ATEX mode Is deactivated,
is activated
Is activated = If no liquid is configured via level detection, then
the pumps cannot be started. This applies for the manual
function, as well as for 24-h switch on and remote control
systems.
Service mode is activated,
Is deactivated
Is activated = All settings can be modified
Is shut off = Settings can be displayed, but cannot be modified
Level control Internal converter
(optional)
Float switch
4 – 20 mA Interface
Level detection via dynamic pressure or bubbler system
Level detection via float switch
Level detection via external sensor (4 - 20 mA)
20mA => Level 0 – 1000 cm Display modification to the connected probe
Language German - English - French
- Italian - Spanish - Dutch -
Polish - Czech
The country language can be changed on the display.