Start Temperature: specifies the minimum temperature value of the fire place from which
the control starts. The unit of measurement is degrees Celsius.
Differential Temperature: specifies how many degrees the water in the fire place must be
higher compared to the tank in order for the circulating pump to start. The unit of
measurement is degrees Celsius.
Motor Overrun Sec: we can set the pump running time after the temperatures have
equalized so that the hot water does not get stuck in the pipes. The unit is seconds.
Display Time Internal Temp Sec: the value measured by the two sensors alternates on the
display and with this parameter we can set how many seconds the temperature from the
puffer is displayed. At this value, a dot appears on the display. The unit is defined in
seconds.
Display Time External Temp Sec: the value measured by the two sensors alternates on
the display and with this parameter we can set how many seconds the temperature from the
fire place is displayed. The unit is defined in seconds.
Low Temperature: if the temperature in the system falls below this value, the controller
starts the pump to circulate the liquid to prevent freezing. This value must be determined in
such a way that there is no danger of freezing.
Low Temperature Hysteresis: this value determines by how many degrees the system
must warm back from the value specified in the Low temperature parameter, in order for the
danger of freezing error signal to disappear and the pump to stop.
Dangerously High Temperature: this is the value that, when the water tank temperature is
reached, the controller sounds an alarm and the Error LED lights up. Together with these,
the pump also comes into operation. Furthermore, if the email notification is set, the
controller will send the error signal to the specified address. Its unit is degrees Celsius.
Dangerously High Temperature Hysteresis: the Dangerously High Temperature and the
difference of this value gives the value where the sound signal stops, but the Error LED and
the pump work.
Overheating Temperature: if the temperature of the system has reached this value, the
Error LED will light up and the pump will start. The controller also sends a notification if the
notification sending function is activated.
Overheating Temperature Hysteresis: the value given by the Overheating Temperature
and its difference is the point below which, when the temperature of the fire place drops, the
controller stops the alarm and the pump.