manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Lexing
  6. •
  7. Smoke Alarm
  8. •
  9. Lexing LX928-D User manual

Lexing LX928-D User manual

The product is a new type of photoelectric smoke
detector, When it detects smoke, it will output signal
immediately and trigger connected unit to work, which
tell you in advance that fire will occurs and avoid
unwanted loss, and take you safety and convenience.
Summary
Power source: DC12V~DC33V
Static current:<60uA
Alarm current: ≤30mA
Working temperature:-10°C~40°C
Working humidity: 10%-95%RH non-condensing
Double indicator.
Specifications
Product size
26.8mm
45.5mm
φ100.4mm
63.5mm
79.5mm
Where fit to install smoke detector
1. First, you need to install at least one item in each
bedroom and route.
2. When a fire breaks out, the stairs are important for
you to rush out, so you must install a smoke detector
on top of the stairs.
3. At least one smoke detector is required for each
space on each floor, including the finished attic and
basement.
4. Install a detector next to each electrical facility.
You'd better install a smoke detector in the middle of
the ceiling because the smoke will always spread.
6. If for some reason you are unable to install it in the
middle of the ceiling, you will also need to install them
at least 10 cm from the wall.
7. If you want to mount them on the wall, install them
10-30.5 cm below the ceiling. figure 1.
8. When your hall is more than 9 meters long, you need
to install multiple detectors.
9. In a sloping roof room, install an alarm that is 0.9
meters from the top. figure 2.
10. How to install a smoke detector in a detachable
house. The mobile house lacks insulation, so you'll
better install the detector 10-30.5 cm from the ceiling.
BEST HERE
CEILING
10CM(4'')
30.5CM(12'')
SIDE WALL
MAXIMUM
ACCEPTABLE HERE
NEVER HERE
MINIMUM
MINIMUM
10CM(4'')
figure 1.
IN THIS AREA
0.9M(3ft)0.9M(3ft)
FROM PEAK
HORIZONTAL DISTANCE
ANYWGERE
figure 2.
Where not fit to install smoke detector
1. At or near the place where the burning particles
often exist, such as: kitchen, garage (exhaust gas),
stove, water heater or near the oiler.
3. In a humid or humid place; or near a bathroom with
a shower.
4. In a dusty, dirty or greasy place.
5. In very ventilated areas, the smoke will blow away
completely from the unit.
6. In the air recording area, this will block the sensing
chamber.
7. The distance from the fluorescent lamp is less than
305mm. Electrical “noise” can interfere with the sensor.
8. In the "dead air" space, for example, in Figure 1, less
than 10 cm near the corner.
9. The smoke detector is easy to detect in the smoking
room.
LX928-D
Smoke Detector
R
WARNING: Turn off the loop power before installing
the detector.
1. First turn the product cover off by counterclockwise
rotation;
2. Connect the wires to the corresponding positions
according to the markings on the product and the
connection instructions on the instructions;
3. After all the detectors are installed, supply power to
the control unit;
4. Test the detector according to the test section;
5. Reset the detector on the controller system;
6. Notify the relevant department system to enter the
working state.
The detector must be tested after installation and
maintenance cleaning.
Note: Before the test, the relevant management
department smoke detector system will be notified for
maintenance and therefore will stop working. Cut off
the logic control kinetic energy of the area or system
that will be maintained to avoid unnecessary alarm
linkage. Make sure the detector is wired correctly and
power the system. After the power supply, allow the 80
second detector to work stably and then test it as
follows;
1. Switch the power, the indicator should flash once
every 20 seconds.
2. Press the test pin (less than 1.5mm in diameter) into
the hole for about 2-3 seconds, and the indicator
should always be lit.
3. If the indicator does not light, please check if the test
pin is used correctly.
4. Smoke test: Take a smoldering wooden stick or
cotton core on the side of the detector and blow the
smoke into the detector until the alarm.
Warning: Due to the above test, the detector can only
be reset after the power supply is momentarily
powered off. If the detector fails the above test, check
that the wiring is correct.
- L1
L2+
Test pin(diameter less
than 1.5mm)
Installation
①Terminal + connect" +"
②Terminal -connect "–"
③Terminal L1 and L2
relay output terminal.
1. Test at least once a week.
2. Clean the smoke detector at least once a month.
Use a vacuum soft brush attachment to gently vacuum.
3. Never use water or detergent to clean the smoke
detectors as they may damage the equipment.
Regular maintenance
Test
1. Call the fire station.
2. Don't panic and stay calm. Leave as quickly as
possible through the route of the advanced plan, don't
waste a lot of time to get things.
3. Feel if the door is hot. If it is hot, please do not open
the door; if not, you should also prevent the flame from
entering, you can choose other routes to escape.
Cover your nose and mouth with a damp towel and do
not breathe fumes.
5. After fleeing, gather at the designated location to
ensure that the person is not injured or killed.
What to do when a fire breaks out
Warning!
● Please confirm with prefessional installation.
● Please cut off power supply before installation
and removal operations.
● Make sure that you have cut off the power for
safety purposes.
● Improper operation caused losses, the
manufacturer does not undertake any
responsibility.
This instruction, without our permission, should not
be copied for any other purposes.
Customer Service:
For all Customer Service and Technical Support enquires please call Monday
to Friday during business hours.
No.35 Zhuquan Road,Science & Technology Area.
E-mail:[email protected] www.lexing.com.cn www.lexing.com
Ninghai,Ningbo,Zhingjiang,China Tel:+86-574-65335088 P.C.:315600
Ningbo Lexing Inductor Electronic co.,LTD
Warning:During the installation of the product,
please be careful not to let dust enter the smoke
detection room.
Smoke
detection room

Other Lexing Smoke Alarm manuals

Lexing LX-SI-918 User manual

Lexing

Lexing LX-SI-918 User manual

Lexing LX-SO-215 User manual

Lexing

Lexing LX-SO-215 User manual

Lexing LX108A User manual

Lexing

Lexing LX108A User manual

Lexing LX-SO-215HT User manual

Lexing

Lexing LX-SO-215HT User manual

Lexing LX928 Datasheet

Lexing

Lexing LX928 Datasheet

Lexing LX-SO-918 User manual

Lexing

Lexing LX-SO-918 User manual

Lexing LX-SO-98D User manual

Lexing

Lexing LX-SO-98D User manual

Lexing LX-SO-738-1 User manual

Lexing

Lexing LX-SO-738-1 User manual

Lexing LX-SO-98A-D User manual

Lexing

Lexing LX-SO-98A-D User manual

Lexing LX728-V1 User manual

Lexing

Lexing LX728-V1 User manual

Lexing LX98A-D User manual

Lexing

Lexing LX98A-D User manual

Lexing LX928-N User manual

Lexing

Lexing LX928-N User manual

Lexing LX-SO-215 User manual

Lexing

Lexing LX-SO-215 User manual

Lexing LX608 User manual

Lexing

Lexing LX608 User manual

Lexing LX708 User manual

Lexing

Lexing LX708 User manual

Lexing LX-SO-729 User manual

Lexing

Lexing LX-SO-729 User manual

Popular Smoke Alarm manuals by other brands

LST AI-58000-500 Specification sheet

LST

LST AI-58000-500 Specification sheet

iess ANTINCENDIO IE 326S-2L Technical manual

iess

iess ANTINCENDIO IE 326S-2L Technical manual

Edwards Signaling SuperDuct TSD-SJ Installation sheet

Edwards Signaling

Edwards Signaling SuperDuct TSD-SJ Installation sheet

Zeta NPAD 2 User manual, maintenance guide & log book

Zeta

Zeta NPAD 2 User manual, maintenance guide & log book

Polon-Alfa DOP-6001R Installation and maintenance manual

Polon-Alfa

Polon-Alfa DOP-6001R Installation and maintenance manual

MGC SD-100 Series Installation and maintenance instructions

MGC

MGC SD-100 Series Installation and maintenance instructions

First Alert 7020b user manual

First Alert

First Alert 7020b user manual

System Sensor D4P120 installation instructions

System Sensor

System Sensor D4P120 installation instructions

Dicon 650MBX owner's manual

Dicon

Dicon 650MBX owner's manual

Clas Ohlson Deltronic PM-7221 instruction manual

Clas Ohlson

Clas Ohlson Deltronic PM-7221 instruction manual

Masterbuilt 20050106 Assembly, care & use manual

Masterbuilt

Masterbuilt 20050106 Assembly, care & use manual

Nittan EVCA-P instruction manual

Nittan

Nittan EVCA-P instruction manual

Emos GS536G manual

Emos

Emos GS536G manual

RESitech F user manual

RESitech

RESitech F user manual

Kidde KIR-OSHD Installation sheet

Kidde

Kidde KIR-OSHD Installation sheet

Honeywell D355PL Installation and maintenance instructions

Honeywell

Honeywell D355PL Installation and maintenance instructions

Gentex Smarter Vision CO1209 Series installation instructions

Gentex

Gentex Smarter Vision CO1209 Series installation instructions

Smartwares RM520 manual

Smartwares

Smartwares RM520 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.