INSTRUCTION MANUAL
(M021B02-03-18A)
REACTIVE ENERGY REGULATOR
Controller MASTER control VAR FAST
(Static operation)

2
Controller MASTER control VAR FAST
Instruction Manual

SAFETY PRECAUTIONS
DISCLAIMER
LIFASA, reserves the right to make modi cations to the device or the unit speci cations set
out in this instruction manual without prior notice.
LIFASA, on its web site, supplies its customers with the latest versions of the device speci -
cations and the most updated manuals.
www.lifasa.es
LIFASA, recommends using the original cables and accessories that are sup-
plied with the device.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead to the risk of re.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation stan-
dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
LIFASA, reserves the right to modify features or the product manual without prior noti cation.
3
Instruction Manual
Controller MASTER control VAR FAST

CONTENTS
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3
DISCLAIMER ����������������������������������������������������������������������������������������������������������������������������������������������������������3
CONTENTS�������������������������������������������������������������������������������������������������������������������������������������������������������������4
REVISION LOG�������������������������������������������������������������������������������������������������������������������������������������������������������6
1�- VERIFICATION UPON RECEPTION�����������������������������������������������������������������������������������������������������������������7
2�- PRODUCT DESCRIPTION��������������������������������������������������������������������������������������������������������������������������������8
3�- UNIT INSTALLATION ����������������������������������������������������������������������������������������������������������������������������������������9
3�1�- PRELIMINARY RECOMMENDATIONS ����������������������������������������������������������������������������������������������������� 9
3�2�- INSTALLATION ����������������������������������������������������������������������������������������������������������������������������������������10
3�4�- UNIT TERMINALS������������������������������������������������������������������������������������������������������������������������������������12
3�5�- CONNECTION DIAGRAM������������������������������������������������������������������������������������������������������������������������14
3�5�1�- 3 VOLTAGES + NEUTRAL AND 3 CURRENTS, CONTROLLER MASTER CONTROL VAR
FAST 6 MODEL� �������������������������������������������������������������������������������������������������������������������������������������������14
3�5�2�- 3 VOLTAGES + NEUTRAL AND 3 CURRENTS, CONTROLLER MASTER CONTROL VAR
FAST 12 MODEL� �����������������������������������������������������������������������������������������������������������������������������������������15
3�5�3�- 3 VOLTAGES + NEUTRAL AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR
FAST 6 MODEL� �������������������������������������������������������������������������������������������������������������������������������������������16
3�5�4�- 3 VOLTAGES + NEUTRAL AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR
FAST 12 MODEL� �����������������������������������������������������������������������������������������������������������������������������������������17
3�5�5�- 2 VOLTAGES AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR FAST 6 MODEL������ 18
3�5�6�- 2 VOLTAGES AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR FAST 12 MODEL���� 19
3�5�7�- LEAKAGE CURRENT CONNECTION, I����������������������������������������������������������������������������������������20
3�6�- STARTING UP THE UNIT������������������������������������������������������������������������������������������������������������������������21
4�- OPERATION ����������������������������������������������������������������������������������������������������������������������������������������������������22
4�1�- DEFINITIONS ������������������������������������������������������������������������������������������������������������������������������������������23
4�1�1 FOUR-QUADRANT REGULATOR������������������������������������������������������������������������������������������������������ 23
4�1�2 STAGES AND STEPS ������������������������������������������������������������������������������������������������������������������������� 23
4�1�3 FCP SYSTEM (FAST Computerized Program)� ��������������������������������������������������������������������������������23
4�1�4 REGULATION PROGRAM� ����������������������������������������������������������������������������������������������������������������� 23
4�1�5� PLUG AND PLAY�������������������������������������������������������������������������������������������������������������������������������� 24
4�1�6 CONNECTION TIME (Ton) AND RECONNECTION TIME (Trec)������������������������������������������������������� 24
4�1�7 THD AND HARMONICS ���������������������������������������������������������������������������������������������������������������������� 24
4�2�- MEASUREMENT PARAMETERS ������������������������������������������������������������������������������������������������������������ 25
4�2�1� CONNECTION TYPE: 3U.3C ��������������������������������������������������������������������������������������������������������������� 25
4�2�2� CONNECTION TYPE: 3U.1C ��������������������������������������������������������������������������������������������������������������� 26
4�2�3� CONNECTION TYPE: 2U.1C ��������������������������������������������������������������������������������������������������������������� 27
4�3�- KEY FUNCTIONS ������������������������������������������������������������������������������������������������������������������������������������� 28
4�4�- DISPLAY ���������������������������������������������������������������������������������������������������������������������������������������������������30
4�4�1� STATUS OF THE CAPACITORS�������������������������������������������������������������������������������������������������������� 31
4�4�2� STATUS OF THE UNIT ����������������������������������������������������������������������������������������������������������������������� 31
4�4�3� ANALOGUE BAR ������������������������������������������������������������������������������������������������������������������������������� 32
4�4�4� OTHER SYMBOLS ON THE DISPLAY ���������������������������������������������������������������������������������������������� 32
4�5�- LED INDICATORS������������������������������������������������������������������������������������������������������������������������������������33
4�6�- OPERATING STATES ������������������������������������������������������������������������������������������������������������������������������34
4�6�1� MEASUREMENT STATUS ����������������������������������������������������������������������������������������������������������������� 34
4�6�2� TEST STATUS ������������������������������������������������������������������������������������������������������������������������������������54
4�7�- INPUTS �����������������������������������������������������������������������������������������������������������������������������������������������������57
4�8�- OUTPUTS ������������������������������������������������������������������������������������������������������������������������������������������������� 57
4�9�- RS-485 COMMUNICATIONS��������������������������������������������������������������������������������������������������������������������58
4�9�1� CONNECTIONS���������������������������������������������������������������������������������������������������������������������������������58
4�9�2� PROTOCOL ���������������������������������������������������������������������������������������������������������������������������������������59
4�9�3� MODBUS MEMORY MAP ����������������������������������������������������������������������������������������������������������������� 60
4�9�4� EXAMPLE OF A MODBUS QUERY�������������������������������������������������������������������������������������������������� 68
4�10�- CPC-NET COMMUNICATIONS�������������������������������������������������������������������������������������������������������������� 69
4�10�1� MODBUS CONTROL FRAME���������������������������������������������������������������������������������������������������������� 70
5�- CONFIGURATION �������������������������������������������������������������������������������������������������������������������������������������������71
5�1�- PLUG&PLAY ��������������������������������������������������������������������������������������������������������������������������������������������72
5�2�- CURRENT TRANSFORMATION RATIO��������������������������������������������������������������������������������������������������75
4
Controller MASTER control VAR FAST
Instruction Manual

5�3�- TARGET COS φ��������������������������������������������������������������������������������������������������������������������������76
5�4�- CONNECTION AND RECONNECTION TIME����������������������������������������������������������������������������������������� 77
5�5�- CONNECTION TYPE�������������������������������������������������������������������������������������������������������������������������������78
5�6�- PHASE CONNECTION����������������������������������������������������������������������������������������������������������������������������78
5�7�- NO� OF STAGES �������������������������������������������������������������������������������������������������������������������������������������80
5�8�- PROGRAM ����������������������������������������������������������������������������������������������������������������������������������������������81
5�9�- C/K FACTOR �������������������������������������������������������������������������������������������������������������������������������������������82
5�10�- ADVANCED SETUP ������������������������������������������������������������������������������������������������������������������������������84
5�11�- VOLTAGE TRANSFORMATION RATIO������������������������������������������������������������������������������������������������ 85
5�12�- STATUS OF THE STAGES�������������������������������������������������������������������������������������������������������������������� 86
5�13�- DISPLAY ������������������������������������������������������������������������������������������������������������������������������������������������87
5�14�- ANALOGUE BAR ���������������������������������������������������������������������������������������������������������������������������������� 88
5�15�- FAN ��������������������������������������������������������������������������������������������������������������������������������������������������������89
5�16�- RS-485 COMMUNICATIONS�����������������������������������������������������������������������������������������������������������������90
5�17�- CPC-NET COMMUNICATIONS������������������������������������������������������������������������������������������������������������� 91
5�18�- CLEAR���������������������������������������������������������������������������������������������������������������������������������������������������92
5�19�- ENABLING ALARMS ����������������������������������������������������������������������������������������������������������������������������93
5�20�- VOLTAGE ALARMS ������������������������������������������������������������������������������������������������������������������������������ 94
5�21�- COS φALARM��������������������������������������������������������������������������������������������������������������������������������������95
5�22�- VOLTAGE THD ALARM ������������������������������������������������������������������������������������������������������������������������ 96
5�23�- CURRENT x I THD ALARM ������������������������������������������������������������������������������������������������������������������ 97
5�24�- TEMPERATURE ALARM ����������������������������������������������������������������������������������������������������������������������98
5�25�- LEAKAGE CURRENT ALARM ����������������������������������������������������������������������������������������������������������� 100
5�26�- NO� OF OPERATIONS ALARM ���������������������������������������������������������������������������������������������������������� 101
5�27�- SIMULATION SCREEN ����������������������������������������������������������������������������������������������������������������������� 102
6�- TECHNICAL FEATURES ������������������������������������������������������������������������������������������������������������������������������103
7�- MAINTENANCE AND TECHNICAL SERVICE����������������������������������������������������������������������������������������������106
8�- WARRANTY���������������������������������������������������������������������������������������������������������������������������������������������������106
5
Instruction Manual
Controller MASTER control VAR FAST

REVISION LOG
Table 1: Revision log�
Date Revision Description
07/18 M021B02-03-18A Initial Version
6
Controller MASTER control VAR FAST
Instruction Manual

1�- VERIFICATION UPON RECEPTION
Check the following points when you receive the unit:
a) The unit meets the specications described in your order.
b) The unit has not suffered any damage during transport.
c) Check the features shown on the label of the unit to make sure that they are suitable
for the type of grid to which the unit will be connected. (Voltage and power supply fre-
quency, measurement range, etc.)
d) Perform an external visual inspection of the unit prior to switching it on.
e) Check that it has been delivered with the following:
- An installation guide,
- Four retainers for rear attachment of the unit,
If any problems are detected upon reception, immediately contact the trans-
port company and/or the LIFASA after-sales service.
7
Instruction Manual
Controller MASTER control VAR FAST

2�- PRODUCT DESCRIPTION
The Controller MASTER control VAR FAST reactive energy regulator is a unit that measures
the grid cosine and regulates capacitor connection and disconnection in order to correct it. It
also calculates and displays the main electrical parameters of balanced or unbalanced sin-
gle-phase and three-phase networks. The measurement is taken in RMS, via four AC voltage
inputs and three current inputs.
There are 2 versions of the unit, according to the number of output relays:
Controller MASTER control VAR FAST 6, with six optoMOS relay outputs.
Controller MASTER control VAR FAST 12, with twelve optoMOS relay outputs.
The unit features:
- 5 keys that can be used to browse the various screens and program the unit.
- 4 indicator LEDs: CPU, ALARM, FAN and KEY PRESSED.
- LCD display, amber backlit, 70x60.7 mm display for viewing all the parameters.
- 2 digital inputs, for selecting the target cosine (4 target cosines).
- 2 digital outputs and 1 relay output, fully programmable as alarms.
- 1 relay output, specic for the fan.
- 6 optoMOS relay outputs (Controller MASTER control VAR FAST 6 model) or 12
optoMOS relay outputs (Controller MASTER control VAR FAST 12 model) for regu-
lating the cos φ by means of capacitors.
- RS-485 communications, MODBUS RTU©.
- CPC-NET communications port.
8
Controller MASTER control VAR FAST
Instruction Manual

3�- UNIT INSTALLATION
3.1.- PRELIMINARY RECOMMENDATIONS
In order to use the unit safely, it is critical that individuals who handle it follow the
safety measures set out in the standards of the country where it is being used,
use the personal protective equipment necessary, and pay attention to the vari-
ous warnings indicated in this instruction manual.
The Controller MASTER control VAR FAST unit must be installed by authorised and quali-
ed staff.
The power supply plug must be disconnected and measuring systems switched off before han-
dling, altering the connections or replacing the unit. It is dangerous to handle the unit while it is
powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal
injury and damage to installations.
The manufacturer of the unit is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations that appear in this manual, nor
for damage resulting from the use of products or accessories that did not come with the unit or
that were made by other manufacturers.
If an anomaly or malfunction is detected in the unit, do not use the unit to take any measure-
ments.
Inspect the work area before taking any measurements. Do not take measurements in danger-
ous areas or where there is a risk of explosion.
Disconnect the unit from the power supply (unit and measuring system power
supply) before maintaining, repairing or handling the unit's connections.
Please contact the after-sales service if you suspect that there is an operational
fault in the unit.
9
Instruction Manual
Controller MASTER control VAR FAST

3.2.- INSTALLATION
The Controller MASTER control VAR FAST regulator is connected to units that
contain capacitors, which remain charged after the voltage source is disconnect-
ed. Wait at least 5 minutes after the unit is disconnected before handling its
internal components in order to avoid the risk of electric shock.
Any manipulation or use of the unit other than that specied by the manu-
facturer may compromise user safety�
Make sure that the units are correctly earthed before they are connected. A faulty earth connec-
tion could lead to faulty operation and lead to a risk of electrical shock for the user or person
handling the unit.
Resonance can occur when the unit is connected with no load. In this case, the voltage har-
monics can be amplied, causing damage to the compensation unit and other units connected
to the mains.
The safe use of the Controller MASTER control VAR FAST requires the persons installing
or handling it to follow the general safety measures of LV electrical installations, as well as the
warnings indicated in this instruction manual.
The unit will be installed on a panel (138+1 x 138+1 mm panel drill hole, in compliance with DIN
43700). All connections are inside the electric panel.
Terminals, opening roofs or removing elements can expose parts that are haz-
ardous to the touch while the unit is powered. Do not use the unit until it is fully
installed.
The unit must be connected to a power circuit that is protected with gl (IEC 269) or M type fuses
with a rating of 0.5 to 2 A. It must be tted with a circuit breaker or equivalent device for discon-
necting the unit from the power supply mains.
The power and voltage measurement circuits as well as the relay contact circuits must be con-
nected with cables that have a minimum cross-section of 1.5 mm2.
One or three external current transformers (CT) need to be installed in order to measure cur-
rent. Usually, the transformation ratio of these CTs is In/5 A, where In is at least 1.5 times the
total maximum load current.
The secondary cables of the current transformers (CT) must have a minimum cross-section
of 2.5 mm2. For distances between the CTs and the unit of more than 25 m, this cross-section
should be increased by 1 mm2 for every 10 m.
The current transformers (CT) must be installed at a point in the distribution panel which carries
all the current of the loads to be compensated as well as the current of the capacitors them-
selves ( Figure 1).
10
Controller MASTER control VAR FAST
Instruction Manual

CORRECT INCORRECT
~
P1
P2
S1
S2
TC
LOAD CAPACITORS
The current transformers (CT) must
measure the combined current of
the capacitors plus the loads
If it does not work, make sure
that the CTs are not short-
circuited�
~
LOAD CAPACITORS
P1
P2
S1
S2
TC
If the CTs are connected
in this position, NONE OF
THE CAPACITORS WILL BE
CONNECTED, even if there are
inductive loads.
The unit does not compensate�
~
LOAD CAPACITORS
P1
P2
S1
S2
TC
If the CTs are connected in this
position ALL THE CAPACITORS
WILL BE CONNECTED, but they
will not be disconnected if the load
drops.
Risk of over-compensation in
the grid with no load�
Figure 1: Location of the current transformers
11
Instruction Manual
Controller MASTER control VAR FAST

3.4.- UNIT TERMINALS
Table 2:List of Controller MASTER control VAR FAST terminals�
Terminals of the top side of the unit
1: A1, Auxiliary power supply. 23: 8, Output 8 (1)
2: A2, Auxiliary power supply. 24: 9, Output 9 (1)
3: VL1, L1 voltage input 25: 10, Output 10 (1)
4: VL2, L2 voltage input 26: 11, Output 11 (1)
5: VL3,L3 voltage input 27: 12, Output 12 (1)
6: VLN, Neutral voltage input 28: A(+), RS-485
7: S1, L1 current input 29: B(-), RS-485
8: S2, L1 current input 30: S, GND for RS-485
9: S1, L2 current input 31: 1, Digital input 1
10: S2, L2 current input 32: 2, Digital input 2
11: S1, L3 current input 33: C, Digital inputs common
12: S2, L3 current input 34: 1, Digital output 1
13: S1, Leakage current input 35: 2, Digital output 2
14: S2, Leakage current input 36: C, Digital outputs common
15: COM, Outputs common 37: Fan relay output
16: 1, Output 1 38: Fan relay output
17: 2, Output 2 39: NC, Alarm relay output
18: 3, Output 3 40: C, Alarm relay output
19: 4, Output 4 41: NO, Alarm relay output
20: 5, Output 5 42: A(+), CPC-NET
21: 6, Output 6 43: B(-), CPC-NET
22: 7, Output 7 (1) 44: S, GND for CPC-NET
(1) Model Controller MASTER control VAR FAST 12
12
Controller MASTER control VAR FAST
Instruction Manual

3
2
145 6 7 8 9 10 11 12 13
15
14
16
17
18
19
20
21
22
23
24
25
26
27
28 29 30 31 32 33 34 35 36 37 38 39 40 41
42
43
44
Figure 2: Controller MASTER control VAR FAST terminals�
13
Instruction Manual
Controller MASTER control VAR FAST

3.5.- CONNECTION DIAGRAM
3�5�1�- 3 VOLTAGES + NEUTRAL AND 3 CURRENTS, CONTROLLER MASTER CONTROL
VAR FAST 6 MODEL�
Connection type: 3U.3C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2 S1 S2
P1 P2 S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
Power Supply
COM 1 2 3 4 5 6
COM ACT C1...C6
Power Supply
Figure 3: 3 voltages + Neutral and 3 currents, Controller MASTER control VAR FAST 6 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
Note: In this type of connection, the connection from Neutral to VLN is not mandatory.
14
Controller MASTER control VAR FAST
Instruction Manual

3�5�2�- 3 VOLTAGES + NEUTRAL AND 3 CURRENTS, CONTROLLER MASTER CONTROL
VAR FAST 12 MODEL�
Connection type: 3U.3C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2 S1 S2
P1 P2 S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
COM 1 2 3 4 5 6 7 8 9 10 11 12
COM ACT C1...C12
Power Supply
Power Supply
Figure 4: 3 voltages + Neutral and 3 currents, Controller MASTER control VAR FAST 12 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
Note: In this type of connection, the connection from Neutral to VLN is not mandatory.
15
Instruction Manual
Controller MASTER control VAR FAST

3�5�3�- 3 VOLTAGES + NEUTRAL AND 1 CURRENT, CONTROLLER MASTER CONTROL
VAR FAST 6 MODEL�
Connection type: 3U.1C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
COM 1 2 3 4 5 6
COM ACT C1...C6
Power Supply
Power Supply
Figure 5: 3 voltages + Neutral and 1 current, Controller MASTER control VAR FAST 6 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
Note: In this type of connection, the connection from Neutral to VLN is not mandatory.
Note: In this type of connection, the current transformer must be connected to the IL1 termi-
nals.
16
Controller MASTER control VAR FAST
Instruction Manual

3�5�4�- 3 VOLTAGES + NEUTRAL AND 1 CURRENT, CONTROLLER MASTER CONTROL
VAR FAST 12 MODEL�
Connection type: 3U.1C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
Power Supply
COM 1 2 3 4 5 6 7 8 9 10 11 12
COM ACT C1...C12
Power Supply
Figure 6: 3 voltages + Neutral and 1 current, Controller MASTER control VAR FAST 12 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
Note: In this type of connection, the connection from Neutral to VLN is not mandatory.
Note: In this type of connection, the current transformer must be connected to the IL1 termi-
nals.
17
Instruction Manual
Controller MASTER control VAR FAST

3�5�5�- 2 VOLTAGES AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR FAST 6
MODEL�
Connection type: 2U.1C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
Power Supply
COM 1 2 3 4 5 6
COM ACT C1...C6
Power Supply
Figure 7: 2 voltages and 1 current, Controller MASTER control VAR FAST 6 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”
Note: In this type of connection, the Neutral connection is not necessary.
Note: In this type of connection, the current transformer must be connected to the IL1 termi-
nals, and the two voltages must be connected to VL1 and VL2.
18
Controller MASTER control VAR FAST
Instruction Manual

3�5�6�- 2 VOLTAGES AND 1 CURRENT, CONTROLLER MASTER CONTROL VAR FAST 12
MODEL�
Connection type: 2U.1C
VLN IL2
S1
L1
L2
L3
N
VL1 VL2 VL3
S1 S2
P1 P2
S1 S1S2 S2 S2
IL3
IL1
A1 A2
COM 1 2 3 4 5 6 7 8 9 10 11 12
COM ACT C1...C12
Power Supply
Power Supply
Figure 8: 2 voltages and 1 current, Controller MASTER control VAR FAST 12 model�
Note: If the connection layout mentioned above is not respected, you must adjust the phase
following the procedure described in section "5�6�- PHASE CONNECTION”.
Note: In this type of connection, the Neutral connection is not necessary.
Note: In this type of connection, the current transformer must be connected to the IL1 termi-
nals, and the two voltages must be connected to VL1 and VL2.
19
Instruction Manual
Controller MASTER control VAR FAST

3�5�7�- LEAKAGE CURRENT CONNECTION, IΔ
To measure the leakage current, an earth leakage transformer must be used, such as WGS.
The leakage current transformer must be connected such as to measure the current of the
capacitor bank. This will detect any leakage in the capacitors of the capacitor bank.
~
TC
LOAD CAPACITORS
S1 S2
P1 P2
I∆
S1
S1
S2
S2
IL1, IL2, IL3
Figure 9: Connection of the leakage current transformer (IΔ)�
Note: The earth leakage transformer must have a ratio of 500 turns. The maximum leakage
current that the unit can measure correctly is 1.5A AC, even though the maximum input is 5A
AC via the earth leakage transformer.
Do not operate the leakage current transformer with the Controller MASTER
control VAR FAST powered on.
20
Controller MASTER control VAR FAST
Instruction Manual