Lightcloud LCOUTLET User manual

Welcome
Outlet
1 (844) LIGHTCLOUD
or 1 (844) 544-4825
WE’ RE HER E TO HELP:

The Lightcloud Outlet is
a tamper-resistant duplex
receptacle that delivers
local and remote plug-load
control and power
monitoring.
Hello
Product Features
Wireless Control & Configuration
Zone Switching
Dual Power Monitoring
Tamper Resistant (TR)
Current Limiting to 20A

Contents
Outlet Faceplate
Faceplate Bracket Instruction Manual
2x 6-32 1/2” Screws 2x 6-32 5/16” Screws
PART NUMBER
LCOUTLET
INPUT
125VAC, 60Hz
CURRENT DRAW
20A
LOAD SWITCHING CAPACITY
2500W Resistive
1500W Tungsten
600W Electrical Ballast
1HP Motor
OPERATING TEMPERATURE
0ºC to 40ºC
DIMENSIONS
Outlet: 1.73”W x 4.1”H x 1.6”D
Faceplate: 2.94”W x 4.69”H x 0.06”D
Faceplace Bracket: 2.8”W x 4.55”H x 0.13”D
TERMINAL
14-12 AWG
Copper Wires Only
WIRELESS RANGE
Line-of-Sight: 1000’
Obstructions: 100’
Specifications

What You Need
Gateway
1 (844) LIGHTCLOUD
or 1 (844) 544-4825
WE’ RE HERE TO HEL P:
A Lightcloud Gateway is required to setup
and control the Outlet.
Wiring
CAUTION
• Use only copper wire.
• Do not operate with the faceplate removed.
• This product should only be installed by a
qualified electrician and in compliance with
local and national electrical codes.
• This product should only be installed in a
UL-approved single gang wall-box enclosure.
• Indoor use only.
Configuration
To configure the Outlet, use the Lightcloud
web application or call RAB:

Finding a Suitable
Location
Lightcloud uses a wireless mesh network to connect
devices such as the Outlet to the Gateway. Unlike a
WiFi router, each Lightcloud device may connect
another device to the network. If there is a clear line
of sight between two Lightcloud devices, they can
be placed up to 1000 feet apart. If the two devices
are separated by ordinary drywall construction, try to
keep them within 100 feet of each other. Brick,
concrete and steel construction may require
additional AC-powered Lightcloud devices to go
around the obstruction. See the Deployment section
of your Gateway for more information.
Setup & Installation
OFF
WARNING
OFF
1Turn off power

Setup & Installation (cont’d)
2Install the Lightcloud Outlet
2a Connect the Line, Neutral, and Ground
to screw terminals.
2b Use the two 6-32 1/2" Phillips round
head screws to secure the Outlet to
the junction box.

Setup & Installation (cont’d)
2Install the Lightcloud Outlet
2c Use the two 6-32 5/16" Phillips flat-head
screws provided to secure the faceplate
bracket to the Outlet.
2d Snap the faceplate onto the
faceplate bracket.

Functionality
Overview
RESET
DEVICE
SIGNAL
STRENGTH
INDICATOR
NETWORK
INDICATOR
RESET
• Single Press: Indicate the Outlet in the Web
Application
• Hold for 10 seconds: Force Outlet to leave current
Lightcloud network
DEVICE
• Single Press: Toggle the top receptacle on/off
Network Indicator
• Solid Green: Connected to a Lightcloud network
• Blinking Red: Not connected to a Lightcloud
network.
SIGNAL STRENGTH INDICATOR
• Indicates strength of the connection to the next
Lightcloud Device
Note: The network and signal strength indicators are
illuminated for 10 minutes following intial power
on. Pressing the Device button will illuminate the
newtork and signal strength indicators for an
additional 10 minutes.

Setup & Installation (cont’d)
3Labeling your device
LC Installer Application
When installing Lightcloud devices, it’s important to
keep track of their Device IDs, installation locations,
panel/circuit #’s, dimming function, and any
additional notes. To organize this information, use
the Lightcloud Installer Application (a) or Device
Table (b).
4Power Up
Turn on power at the breaker, and confirm the
network indicator is blinking red.
5Add Outlet to Network
Call RAB at 1(844)LIGHTCLOUD.
6Confirm Device Connectivity
Confirm network indicator LED is solid green.
Install the LC Installer Application
LC Installer is available for iOS and Android.
Scan & Install Lightcloud Devices
Send to RAB
Once all of the devices have been added and
organized, submit the information for
commissioning.
Device Table
Two Device Tables are provided with each Gateway.
Attach one table to the electrical panel and hand
one off to the building manager.
Attach the Device ID stickers included with each
device to the Device Table and write in the
additional information.

© RAB Lighting, Inc
170 Ludlow Avenue Northvale, NJ 07647
Custom manufactured in China
1 (844) LIGHTCLOUD
1 (844) 544-4825
Lightcloud is a commercial
wireless lighting control system.
It’s powerful and flexible,
yet easy to use and install.
Learn more at lightcloud.com

FCC Information:
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference
that may cause undesired operation.
Note: This device has been tested and found to comply with the limits for
Class B digital devices pursuant to Part 15 Subpart B, of the FCC rules.
These limits are designed to provide reasonable protection against harmful
interference in a residential environment. This equipment generates, uses,
and can radiate radio frequency energy, and if not installed and used in
accordance with the instruction manual, may cause harmful interference
to radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try and
correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
To comply with FCC RF exposure limits for general population/
uncontrolled exposure, this transmitter must be installed to provide a
separation distance of at least 20cm from all persons and must not be
co-located or operating in conjunction with any other antenna or transmitter.
CAUTION: Changes or modifications to this equipment not expressly
approved by RAB Lighting, Inc. may void the user’s authority to operate
this equipment. Custom manufactured in China.
Table of contents
Popular Measuring Instrument manuals by other brands

Armada Technologies
Armada Technologies Pro400 operating instructions

Trotec
Trotec BP17 quick start guide

DOLD
DOLD RN 5897/240 Translation of the original instructions

PCE Instruments
PCE Instruments PCE-LCT 3 user manual

Kiwitron
Kiwitron KiwiEye X001010 Installation, use and maintenance manual

Magnescale
Magnescale DT12N instruction manual