Lincoln A Series User manual

Page
Section - F60 - 1
Form 403081
May 2002
LFC 3000 Instruction Manual
Series A
282865
282880
282860
282873
85544
282866
282868
282887
282865
282860
282889
282866

Page Number - 2
LFC 3000 Instruction Manual
Series A
Form 403081
IMPORTANT SAFETY INSTRUCTIONS.
1. Before installing or using this product, please read the
instruction manual thoroughl .
2. Unpacking: Please check that the product is complete
and free from an damage
3. Onl qualified individual should install and/or repair this
product.
4. Unplug the LFC3000 from the electrical outlet before ou
clean it.
Use a damp cloth for cleaning and do not use liquid or
aerosol cleaners.
5. Do not place the LFC3000 on an unstable surface that
ma allow the unit to fall.
6. Never place the LFC3000 near or over a radiator or heat
register.
7. Use the t pe of power source indicated on the label (AC
power). If ou are not sure of the t pe of power available,
consult our supplier or local electric compan .
8. The LFC3000 must be equipped with a plug having a
third (grounding) pin, which fits onl into a grounding-
t pe outlet. This is a safet feature. LFC3000 should not
be used without a properl grounded outlet. Failure to
properl ground the LFC3000 ma cause damage to the
unit or the data stored.
9. Do not put the LFC3000 where the cord will be walked
on.
10. An extension cord is not recommended for use with the
LFC3000.
If ou use an extension cord, make sure that the total of
the ampere ratings on the products plugged into the
extension cord does not exceed the extension cords
ampere rating. Also make sure that the total of all
products plugged into the wall outlet does not exceed
15 amperes.
11. Unplug the LFC3000 from the wall outlet and have it
repaired b a qualified service person under the
following conditions:
A. When the power cord or plug is damaged or fra ed.
B. If liquid has been spilled into it.
C. If it has been exposed to rain or water.
D. If it does not operate normall when the operating
instructions are followed. Adjust onl those controls that
are covered b the operating instructions since improper
adjustment of other controls ma result in damage and
lose of data.
E. If it has been dropped or damaged.
If it exhibits a distinct change in performance, indicating
a need for service.
Table of Contents
Safet Instructions..........................................................................2
Main Components..........................................................................3
Cable Requirements....................................................................3
Network Wiring...............................................................................3
Main Fluid Components................................................................5
Power Suppl Wiring......................................................................6
Ke pad Wiring.................................................................................6
I/O Wiring.........................................................................................7
Printer Settings and Wiring...........................................................8
Displa Wiring.................................................................................8
PC Interface Wiring........................................................................9
Printer Extender Wiring.................................................................9
Power Requirements.................................................................10
Network S stem...........................................................................10
Logic Structure of LFC 3000........................................................10
How the Network Works..............................................................11
Troubleshooting..........................................................................13
Failure to adhere to these safet instructions ma result
in serious bodil injur or death.

Page Number - 3
Form 403081
LFC 3000 Instruction Manual
Series A
Cable Requirements
24vdc power cable 2 wire w/ground (see wiring chart for
size)
Solenoid cable - 2 wire w/ground (see wiring chart for size)
Pulse meter cable 1 twisted pair w/shield (see wiring
chart for size)
Network cable One twisted pair w/shield. Can use an of
the following cables: Belden Apple Talk 9999, Belden
8451, Belden 8760, Alpha 24561.
Printer cable 3 wire 24awg w/shield. The maximum dis-
tance that a printer cable can be from an I/O or ke pad is 45ft.
If ou need a longer distance than 45ft for our printer use the
Network Printer Extender P/N 282884.
Main Components
Power Supply - 282865
Input voltage : 90 to 120vac 50/60hz
Fuse: 3 amps time dela
Output voltage: 24vdc with 240va available
It is recommended to use one power suppl per I/O unit.
Power cord is not supplied with unit.
I O 282860
Input voltage: 24vdc
Can support 8 fluid solenoids, 8 pulse meters, 1 printer
and 1 main air solenoid.
Keypad 282868
Used to control, monitor and program s stem. Will
support a printer.
Display 282866
Can read the amount being dispense at the hose reel.
PC Interface 282880
Used to connect a PC to the network. Used to control,
monitor and program s stem. Can have onl one PC per
s stem.
Network Printer Extender 282884
Use this device if our printer needs to be more than 45ft
from a ke pad or an I/O unit. The printer extender is wired
the same as a ke pad. From the printer extender the
printer still must be within 45ft. The network printer
extender is basicall the same as a ke pad but with a
blank cover.
Ticket Printer 282887
Fort column serial printer. Uses thermal paper p/n
282888. Uses printer cable p/n 282879.
Report Printer 282889
Eight column serial printer. Includes printer cable.
Fluid Solenoid 282873
24vdc at .61amps, rated working pressure 3000psi, 6
gpm, normall closed valve. Each hose reel will have one
fluid valve. Comes with ½ NPT (female) adapters.
Pulse Meter 85544
Universal pulse meter, rated 1500psi. 8 gpm maximum.
Each hose reel will have one pulse meter.
Main Air Solenoid 282886
24vdc, 1.8w power consumption, 3 wa normall closed
valve, ¾ NPT port size, flow factor 9cv. Use one air valve
per s stem.
Pressure Relief Valve 282876
Set to relieve at 1000psi. Use one pressure relief valve
per product. Comes with ½ NPT (female) adapters.
Networ Wiring
The network wiring consists of three wires, CAN H, CAN L
and the shield. The following are the network components: I/O
unit, displa , ke pad and PC interface. The network structure
for all components are wired in series. The guidelines below
must be adhered to when installing a s stem.
1. Onl use recommended network cable. See cable
requirements.
2. Total distance of network cabling cannot exceed 2460 ft.
This is the sum of network cable between all network
devices.
3. All network devices all wired in series. A star network
cannot be used. Junction boxes are allowed, however,
the maximum distance from a junction box to a network
device is 9 ft. The ideal s stem would be wired from
network device to network device. See illustration 1
4. The network device at the beginning and the network
device at the end of the network must have its internal
120 ohm resistor set to the ON position. All other devices
in the network must have their internal 120 ohm resistor
set to the OFF position. See illustration 2, 3, 4 and 5 for
location of jumper pin.
Wire
size
Power
Supply
to I/O
unit
I/O unit to Fluid
Solenoid
282873 &
83929 Ready
Light
I/O unit to
Air
Solenoid
282886
I/O unit to
Pulse
Meter
85544
Power
Supply to
Keypad or
Display
18 AWG 10 ft 150 ft 600 ft 600 ft 500 ft
16 AWG 20 ft 250 ft
14 AWG 30 ft 400 ft
12 AWG 50 ft
Wiring Chart

Page Number - 4
LFC 3000 Instruction Manual
Series A
Form 403081
Illustration 1
I/O Unit
Illustration 2
Keypad & Printer Extender
Illustration 3

Page Number - 5
Form 403081
LFC 3000 Instruction Manual
Series A
Display
Illustration 4
PC Interface
Illustration 5
Main Fluid Components
Illustration 6

Page Number - 6
LFC 3000 Instruction Manual
Series A
Form 403081
Wiring the Power Supply 282865
See Illustration 7. The input power for the power suppl is 120vac 50/60hz. The power cord is not supplied with the power
suppl . The power cord must have a third (grounding) pin. The output from the power suppl is 24vdc with 240va of power is
available. It is recommended to use one power suppl per I/O unit.
Wiring the Keypad 282868
See Illustration 8. Input voltage is 24vdc at 3.6va from power suppl . All grounds are connected to the frame nut. The shield
for the network wiring can onl be connected to the terminal marked shield located between CAN H and CAN L terminals.
Illustration 7
Illustration 8

Page Number - 7
Form 403081
LFC 3000 Instruction Manual
Series A
Wiring the I O Unit 282860
See Illustration 9. Input voltage is 24vdc at 2va (no solenoids) from the power suppl .
The I/O controls and supplies power to the eight fluid solenoids located at the hose reel and one main air solenoid. The I/O has
eight inputs for the pulse meter located at the hose reel.
The I/O has one input for high level waste oil (N.O.) switch. When activated the LFC 3000 will print an alert message.
Wiring for single channel pulse meters is shown in illustration 9. The I/O can also support dual channel pulse meters.
Solenoids and pulse meters 1 to 8 are supported b I/O ID 0. Solenoids and pulse meters 9 to 16 are supported b I/O ID 1,
etc
Each I/O supports a printer and the network wiring.
All grounds must be connected to the frame nut.
The shield for the network wiring can onl be connected to the terminal marked shield located between CAN H and CAN L
terminals.
A ke switch is provided to switch all of the fluid solenoids on at one time.
Reversing polarit of 24 VDC input
voltage will result in the opening of
the fuse.
Illustration 9
6.3 AMP TIME DELAY FUSE
SERVICE PART 282894
(PACKAGE OF 5)

Page Number - 8
LFC 3000 Instruction Manual
Series A
Form 403081
Printer Settings and Wiring 282887 or 282889
Printers are normall connected to a ke pad but can also be connected to an I/O unit. The printers are used in the serial mode,
9600 baud and no parit . See the printer table below for wiring connections.
Settings for 282887 Ticket Printer
Three dip switches must be set in software before using the printer with LFC 3000. See the printer manual to access these
switches. Set switches as follows:
SW 1 = 01101011
SW 2 = 10111110
SW 3 = 11110111
Settings for 282889 Report Printer
The three internal dip switches should alread be set when ou receive our report printer. If the switches need to be set refer
to the printer manual for location of switches. The switch settings are as follows:
SW 1 = 00001010
Serial SW 1 = 11111110
Serial SW 2 = 01101110
Wiring the Display 282866
See Illustration 10. Input voltage is 24vdc at 3.6va from the power suppl . The four dip switches on the printed circuit board are
used to set the address of displa . All grounds are connected to the frame nut. The shield for the network wiring can onl be
connected to the terminal marked shield located between CAN H and CAN L terminals.
Address SW4 SW3 SW2 Sw
1
0 ONONONON
1 OFF ON ON ON
2ONOFFONON
3OFFOFFONON
4ONONOFFON
5 OFF ON OFF ON
6ONOFFOFFON
7 OFF OFF OFF ON
8 ONONONOF
F
9 OFF ON ON OF
F
10 ON OFF ON OF
F
11 OFF OFF ON OF
F
12 ON ON OFF OF
F
13 OFF ON OFF OF
F
14 ON OFF OFF OF
F
15 OFF OFF OFF OF
F
I/OUnit Keypad 282887 TicketPrinter 282889 ReportPrinter
9 pin printer connector 25 pin printer connector
TXDO TXD #3 #3
GND GND #5 #7
RXDO/CTSO CTS #8 #20
Printer connections to I O unit & Keypad

Page Number - 9
Form 403081
LFC 3000 Instruction Manual
Series A
Wiring the PC Interface 282880
See Illustration 11.
The shield for the network wiring can onl be connected to the terminal marked shield located between CAN H and CAN L
terminals.
Wiring the Network Printer Extender 282884
See Illustration 12. Input voltage is 24vdc at 3.6va from the power suppl . The shield for the network wiring can onl be
connected to the terminal marked shield located between CAN H and CAN L terminals.

Page Number - 10
LFC 3000 Instruction Manual
Series A
Form 403081
Power Requirements
Power Supply - Supplies power to I/O,
ke pad, displa s and solenoids.
Input voltage: 90 to 120vac 50/60hz
Output: 240va at 24vdc
I O Use one power suppl per I/O
24vdc
2va (no solenoids)
Keypad
24vdc
3.6va
Display
24vdc 3.6va
Fluid Solenoid 282873
24vdc
15va
Main Air Solenoid 282886
24vdc
1.8va
Network Printer Extender
24 VDC
3.6 VA
ID I/O unit ID Keypad ID Solenoid ID Pulser
0 0-1-2-3-4-5-6-7 1-2-3-4-5-6-7-8 1-2-3-4-5-6-7-8
1 8-9-10-11-12-13-14-15 9-10-11-12-13-14-15-16 9-10-11-12-13-14-15-16
2 16-17-18-19-20-21-22-23 17-18-19-20-21-22-23-24 17-18-19-20-21-22-23-2
4
3 24-25-26-27-28-29-30-31 25-26-27-28-29-30-31-32 25-26-27-28-29-30-31-3
2
4 32-33-34-35-36-37-38-39 33-34-35-36-37-38-39-40 33-34-35-36-37-38-39-4
0
5 40-41-42-43-44-45-46-47 41-42-43-44-45-46-47-48 41-42-43-44-45-46-47-4
8
6 48-49-50-51-52-53-54-55 49-50-51-52-53-54-55-56 49-50-51-52-53-54-55-5
6
7 56-57-58-59-60-61-62-63 57-58-59-60-61-62-63-64 57-58-59-60-61-62-63-6
4
The I/O unit with ID 0 will communicate with ke pads #0 to 7 and control hoses #1 to 8 based on pulses from counters #1
to 8.
The I/O unit with ID 1 will communicate with ke pads #8 to 15 and control hoses #9 to 16 based on pulses from counters
#9 to 16.
If our installation uses a network printer extender for long distance printing use ID 0 for this device.
Network System
The LFC 3000 can be grouped into 3 levels.
Level 1: Maximum 8 hoses without a PC
One I/O unit
1 to 8 fluid valves
1 to 8 pulse meters
Maximum of 8 ke pads
Maximum of 16 displa s
Level 2: Maximum 64 hoses without a PC
I/O units maximum of eight
Maximum of 64 fluid valves
Maximum of 64 pulse meters
Maximum of 8 ke pads
Maximum of 16 displa s
Level 3: Maximum 64 hoses with a PC.
I/O units maximum of eight
Maximum of 64 fluid valves
Maximum of 64 pulse meters
Maximum of 64 ke pads
Maximum of 16 displa s
ogic Structure of FC 3000
The table below shows the address (ID) of the I/O unit and the corresponding ke pads, solenoids and pulse meters.

Page Number - 11
Form 403081
LFC 3000 Instruction Manual
Series A
How the Networ Wor s
The main part of the software is stored in the I/O unit. The ke pad is the interface between the I/O unit and the operator.
In a multi I/O installation, there is alwa s an I/O which is the Master. The software recognizes onl the I/O 0 as the
Master. This Master I/O unit will store all the transactions and is the rela between the ke pads and the other I/O units.
These last ones will onl control the solenoids and pulse transmitters but will not store an transactions. The alwa s
receive their instructions from the Master I/O.
The following operations must be executed depending on the different installation configurations.
We recommend to structure the communication of the network before connecting the pulse transmitters and the
solenoids to the I Os.
1) Installation with 1 I/O unit, maximum 8 eypads and without PC
- All the I/O units are delivered with the ID 0, dont modif it.
- All the ke pads are delivered with the ID 0. A different ID number must be given to each ke pad.
- All the displa s are delivered with the ID 0, a different ID number must be given to each different displa .
Procedure to change the address of the keypad (ID):
This procedure must be done from each ke pad. At power up, all the ke pads will show:
VERSION n° #.##
I.D.: X Version Date (X is the address of the Ke pad)
1. Remove all the ke pads connectors or shut the power down.
2. Press the Space ke on the ke pad ou need to change and hold down.
3. Put back the connector or power on.
4. Release the Space ke ; the screen will show ou: ID?
5. T pe the ke pad ID number (0 to 7).
6. Press enter.
Execute the same procedure with different ID numbers for all the ke pads. On ever ke pad, ou have to give an address
for the ticket A & B printer setup.
When all the ke pads will be correctl identified b the network the will all show PIN.
Procedure to change the address of the display (ID):
1. Remove the displa s connector or shut the power down.
2. Change the address b using DIP switches on the PC board.
3. Put back the connector or power on.
4. The displa s identification can be checked via the software in test C.
2) Installation with multi (2-8) I/O, maximum 8 eypads without PC
- The 8 ke pads must be set to communicate with I/O 0.
- All the I/O units are delivered with the ID 0.
A different address (ID) must be given to each I/O unit.
- Regarding the address of the ke pad (ID), see procedure to change the address of the ke pad (ID).
On each ke pad, ou have to give an address for the ticket A & B printer setup.
- Regarding the address of the displa (ID), see procedure to change the address of the displa (ID).

Page Number - 12
LFC 3000 Instruction Manual
Series A
Form 403081
Procedure to change the address of the I/O unit (ID)
1. Remove all the power connectors of all the I/O units.
2. Put back the power connectors of the highest I/O units. For example, if ou have 3 I/O units in the garage, put back
the power connector from the I/O corresponding to hoses #17 to 24.
3. Go to the closest ke pad, enter into the s stem configurations and install menu to set the minimum parameter.
See User Manual.
4. Go to the prompt change I/O ID.
5. Set I/O address to 2 (Hoses #17 to 24).
6. Exit the configuration procedure (go back to PIN).
7. Remove the I/O power connector.
8. Do the same procedure for I/O Number 1 (hoses #9 to 16).
9. Do the same procedure for I/O Number 0 (hoses 1 to 8).
The following are the minimum parameters which must be set correctly for each I O unit to set up the dispensing part of
the program. Refer to the Supervisor, Customer and S stem menus in the User Manual.
Minimum Parameters Factor Settings
- Initial Time-out 6 sec.
- Inactive Time-out 60 sec.
- Encoder t pe Single Channel
All of the above data must be the same on each I/O
Note: On an installation with PC, just b activation of the send option, the configuration (minimum parameters is automati-
call sent to all different I/O units. Except Date/Time, ou still have to program on each I/O.
The I/O address ID number is stored in a permanent memor which is read onl when the s stem is powered on. This is
the reason wh it is requested to power off and back on (or unplug and replug the power connector) the s stem after a
modification of the address.
Modification of the minimum parameters after configurations:
If one or more of the minimum parameters have to be modified on a multi I/O s stem, it will be necessar to change one of
the ke pads ID number to talk with the respective I/O. Following is an example if a minimum parameter has to be changed
on I/O Number 2.
1. Change the address of the closest ke pad (see procedure to change the address of the ke pad (ID)) into the
address ID number compatible with I/O ID number 2.
2. Enter in the s stem configuration and installation menu to modif one or more parameters.
3. Exit the configuration procedure (go back to PIN).
4. Reenter the original ke pad ID ou modified.
3) Installation with a PC, multi I/O and maximum 64 eypads
With the use of a PC, ou still need to :
- Give to each I/O a different address (ID); see procedure to change the address of the I/O unit (ID).
- Program Date and Time on each I/O.
- Give at each ke pad a displa a different address (ID); see Procedure to change the address of the ke pad (ID).
- Give at each displa a different address (ID); see procedure to change the address of the displa (ID).
- Configure the entire s stem, send the configuration through the network.
See software manual.

Page Number - 13
Form 403081
LFC 3000 Instruction Manual
Series A
TROUBLESHOOTING
Do not forget that you need to clear all the transactions (Supervisor Menu) before any configuration!
In case of a problem, try to isolate the problem by changing the device that seems damaged.
Never try to repair a damaged item by yourself (not under warranty).
Therefore, you need to have spare parts with you.
1. Communication Problems:
The displa on the ke pad shows:
and does not switch to the prompt:
Check the following:
1. The network cable is wrong.
2. You have a Star network and not an IN Line network.
3. The jumper sockets are not in the In position at the beginning and the end of the CAN bus (120 Ohm between
CAN H and CAN L): See Illustrations 2, 3, 4 and 5.
IN: Resistor is fitted between CAN H and CAN L.
OUT: Resistor is not fitted between CAN H and CAN L.
4. The CAN L or CAN H wires are open.
5. CAN L and CAN H are inverted.
6. No 24 VDC power at the I/O unit.
7. Low Voltage (<9 VDC) at the I/O unit or at the ke pad.
8. Check the fuses on the I/O card.
Check the fuse and circuit breaker on the P.S.U.
9. The displa on the ke pad reads Inactive.
a. Power c cle s stem.
b. When the displa reads Inactive press enter one time. That should clear it.
ost Supervisor PIN
We have a method to release the s stem where the Supervisor PIN has been lost or illegall changed. This is based on
time and date and gives a different PIN ever hour.
If the customer calls needing the PIN, he should be asked for the time and date which is shown on the displa ever
minute. You have then to make the following calculation:
Month x 7891
Da x 3456
Hour X 4567
The PIN code to use will be the 4 last numbers of the addition.
Example: We are the 21st of Januar 1998 - 11:35 AM.
01 x 7891 = 7891
21 x 3456 = 72576
11 x 4567 = 50237
130704
The correct code is 0704.
Enter PIN No.
VERSION n°#.##
I.D.: X Date of Version

Page Number - 14
LFC 3000 Instruction Manual
Series A
Form 403081
Now have the customer to enter an invalid PIN to reset the 9999 counter. He should now enter 9999 twice followed b the
PIN calculated above. On each entr the Invalid Pin message will be shown.
At this point, the default PINs will be reset (i.e. 9999-1111 and 2222).
2. Problems with the display:
If ou are in Test C (S stem Menu) and the addresses displa ed are not the same as these selected on the dip switches
(back of the card): shut the s stem off (or the wrong displa ), wait at least five seconds and switch the power back on.
- Check the displa allocation (S stem Menu) of the different hoses.
- Check the minimum power (9 vdc) at the displa .
- Check the network (CAN H and CAN L) at the displa .
- Replace the displa .
3. Problems with the solenoid valves:
- All the solenoids are open all the time: check the position of the override ke switch on the I/O box.
- You are in Test A (S stem Menu) and one or more solenoids are not working:
- Check the connections (Solenoids, I/O card)
- Check the voltage at the solenoid, there is ma be too much power-lost on the line?
- Check the continuit of the cables.
- Exchange the solenoid.
- You have an Pulser Error message, check in set encoder t pe if ou are in quadrature or in single pulse mode.
4. Problems with the pulsers:
You dont have an delivered quantit on our tickers and the displa is not working, but ou can deliver oil.
- Check to see if the hose has been programmed to the correct displa .
- Check the connections (pulsers, I/O Card)
- Check the continuit of the cables.
- Check the opening and closing of the pulse meter switch.
- If ou have a pulse counter, check that the pulses are arriving at the I/O Card.
- Exchange the pulser.
5. Problems with the printers:
- Check the printer switch settings - See Printer Settings and Wiring
- Check all the connections
- Check the continuit of the cables
- Check the different printer setup (S stem Menu)
6. Problem with the PC Interface:
On the right side of the bottom of the PC screen, there are 8 little squares. If ou have five I/Os connected to our s stem,
ou must have five little green squares with xs in them. Otherwise, ou have a network problem.
7. Explanations for the transaction end codes printed on each transaction ticket:
0 Means the transaction has been stopped after the inactive time-out:
- Its normal in free dispense mode.
- The preset quantit has not been totall dispensed.
1 In preselect mode, the preset quantit has been totall dispensed: Completed.
2 Input Error in the pulses sequence: for quadrature pulsers onl .
3 Count Error: Missing pulse in quadrature pulsers onl .
4 It means that the power has been shut down during the transaction: Power Down.
5 The transaction has been stopped b the emergenc procedure (....): S stem inactive.
6 IOP Error: Microprocessor Error
7 Unauthorized transaction: for approved s stems onl , quantit dispensed between 0,5 Lt and 100 lt.

Page Number - 15
Form 403081
LFC 3000 Instruction Manual
Series A
8. Procedure to change the battery:
- Test of the microprocessor supervisor circuit MAX690 next to the batter :
- With 24 VDC power: Pin 3 (-) Pin 7 (+) = 5 VDC
- Without 24 VDC power: Pin 4 (-) Pin 8 (+) = 3 VDC
(2 VDC MIN)
- Print a diagnostic report for our records.
- Under power, remove the batter and replace it with a new one. Must replace with same t pe of batter .
- Batter References: Lithium Manganese Batter
3 VDC - 180 mAH - T pe CR 2032

Page Number - 16
LFC 3000 Instruction Manual
Series A
Form 403081
Americas:
One Lincoln Wa
St. Louis, MO 63120-1578
USA
Phone +1.314.679.4200
Fax +1.800.424.5359
Europe/Africa:
Heinrich-Hertz-Str 2-8
D-69183 Walldorf
German
Phone +49.6227.33.0
Fax +49.6227.33.259
Asia/Pacific:
25 Intl Business Park
#01-65 German Centre
Singapore 609916
Phone +65.562.7960
Fax +65.562.9967
© Cop right 2002
Printed in USA
Web site:
www.lincolnindustrial.com
Other manuals for A Series
20
This manual suits for next models
1
Other Lincoln Keypad manuals