Bardac drives T3-OPPAD User manual

Installation & Operating InstructionsUser Guide
T3-OPPAD
TFT Remote Keypad
IP55

2| T3-OPPAD TFT Remote Keypad IP55 User Guide | Version 1.02
www.bardac.com
General Specification
Compatible Drives:
Signal Interface:
Supply Input:
RS485 Signal:
Environmental:
Relative Humidity:
Protection Rating:
Max Cable Length:
E3, P2,V3
CV Standard 8-way RJ45 connector
24V + / - 10%, DC, 30mA
Industry standard 2-wire +5V differential
Operational: -10 … 50°C
Storage: -40°C … 60°C
< 95% (non condensing)
IP55
25m / 82.5ft shielded twisted pair
Mechanical Installation
Dimensions
11
0mm 100m
m
90mm
80mm
Through Panel Mount
The panel on to which the T3-OPPAD is to be mounted should
be cut out in accordance with the diagram below.
11 0mm102mm
81 mm
Electrical Installation
Cable Requirements
1
1
CAUTION! Incorrect cable connection may damage the drive. Extra care should be taken when using third party cable.

Version 1.02 | T3-OPPAD TFT Remote Keypad IP55 User Guide | 3
www.bardac.com
Allowed System Configurations
Different drive models can be used on the same T3-OPPAD network provided a unique communications address is assigned to
each. NOTE Cannot be used with Master – Slave or Cascade Control
Keypad and Display Layout
The illustration below explains the main features of the T3-OPPAD. Please note that some features and display messages are specific
to certain variants of the drive family.
TFT Display
Product Name
Shows the drive type that the T3-OPPAD is
connected to.
Main Displayed Parameter
Shows which of the selectable parameters
is currently being shown on the main display,
e.g. Motor Speed, Motor Current etc.
Operating Information
Provides a real time display of key operating
information, e.g. output current and power.
Quick Help Button
Provides access to short description
of the displayed messages.
Function Button 1
See specific drive user guide for
actual function.
Start Button
When in keypad mode (or HAND
for Eco), used to start the drive.
Stop / Reset Button
Used to reset a tripped drive.
When in keypad mode (or HAND for Eco),
used to stop the drive.
Name 01 Drive Address
Drive serial communication address.
Navigate Button
Used to display real-time information,
to access and exit parameter edit mode
and to store parameter changes.
Function Button 2
See specific drive user guide for actual
function.
Up Button
Used to increase speed in keypad
mode or increase parameter values in
parameter edit mode.
Down Button
Used to decrease speed in keypad
mode or decrease parameter values in
parameter edit mode.
STOP
15 kW 400V 3Ph

Easy Startup
To setup the drive communication address
By default, the T3-OPPAD will try to communicate with the drive that has Address 1 in the network after powering up for the first time.
The T3-OPPAD will display “Scanning for Drive 01.” after power up, which indicates that the T3-OPPAD is searching for the drive with
the correct drive address in the network. Once the drive has been found, the message “Load...” will be displayed on the T3-OPPAD,
which indicates that the T3-OPPAD is reading the configuration information from the drive. Usually it will take 1~2 seconds for the T3-
OPPAD to read this information. After the data has been loaded, the T3-OPPAD will display the drive real time status.
NOTE In the case where the keypad is connected to a drive where the network address is not 1, the following steps can be used to
set the address of the drive
Select Drive Address
01
Select Drive Address
01
Use the Up and Down
arrows to select the
address.
Press the Stop button once
address has changed to
match the connected drive.
Working with Multiple Drive Networks
When the T3-OPPAD is used on networks with multiple drives, the user can change the drive address to set up communication
with another drive in the same drive network at anytime.
Select Drive Address
xx
Select Drive Address
xx
Select Drive Address
xx
Briefly press the Stop and
Down keys to display the
above message.
Use the Up and Down
arrows to select the
desired address.
After selecting the new
address, press the Stop
and Down keys to
establish communications
with the drive.
NOTE For detailed parameter listing and functional setup, please refer to the corresponding drive user guide
Networks with 2
T3-OPPADs
connected
A maximum of 2 T3-OPPADs can be connected within the same drive network to communicate with the same drive or different
drives.
When using two T3-OPPADs simultaneously on a network, the user must change the T3-OPPAD Device Number on the second
T3-OPPAD to ensure correct operation. All T3-OPPAD units are set to Device Number 1 by default.
Select OPPAD ID xx Select OPPAD ID xx Select OPPAD ID xx
To change the Device
Number, press the
Navigate, Stop and
Down keys together.
Use the Up and Down
arrows to select the
desired T3-OPPAD
Numer (1 or 2).
Press the Stop key
to return ro normal
operation.
4| T3-OPPAD TFT Remote Keypad IP55 User Guide | Version 1.02 www.bardac.com

Version 1.02 | T3-OPPAD TFT Remote Keypad IP55 User Guide | 5
www.bardac.com
Changing the Display Language
STOP
Select Language Select Language
Español
Deutsch
English
Español
Deutsch
English
Hold down the Start and
Up keys for >1s
Use the Up and Down
arrows to select a
language.
Press the Navigate button
to select.
Operating Displays
Inhibit /
STO Active
Drive Stopped Drive Running
Output Frequency
Display
Drive Running
Output Current
Display
Drive Running
Motor Power
Display
Drive Running
Motor Speed
Display
Name 01 Name 01
Output Frequency 01
Motor Current 01 Motor Power 01 Motor Speed 01
INHIBIT STOP 23.7Hz 15.3A 6.9kW 718rpm
15 k W 400V 3Ph 15 k W 400V 3Ph 15.3A 6.9kW 6.9kW 23.7Hz 23.7Hz 15.3A 23.7Hz 15.3A
Drive Inhibited. The
STO connections
are not made.
Drive Stopped /
Disabled.
Drive is enabled
/ running, display
shows the output
frequency (Hz).
Press the Navigate
key to select
alternative displays.
Press the Navigate
key for < 1 second.
The display will
show the motor
current (Amps).
Press the Navigate
key for < 1 second.
The display will
show the motor
power (kW).
If P1-10 > 0,
pressing the
Navigate key for
< 1 second will
display the motor
speed (Rpm).
Additional Display Messages
Auto Tuning in Progress External 24VDC Supply Overload Fire Mode
Name 01 Name 01 Fire Mode
Auto-tuning Ext 24V OL 23.7Hz
External 24V mode
15.3A 6.9kW
Auto tune in progress.
The drive control board
is powered only from an
external 24 Volt source,
with no mains power
applied.
Indicates an Overload
condition. Output current
exceeds the motor rated
current.
Display shows 'Fire Mode'.

6| T3-OPPAD TFT Remote Keypad IP55 User Guide | Version 1.02
www.bardac.com
Switching Frequency
Reduction
Mains Loss Maintenance
Time Elapsed
Name 01 Name 01 Name 01 Name 01
SF23.7Hz ML 23.7Hz OL 23.7Hz 23.7Hz
15.3A 15.3A 6.9kW 15.3A 6.9kW 15.3A 6.9kW
Switching frequency is
reduced, due to high
heatsink temperature.
The incoming mains
power supply has been
disconnected or is missing.
The motor is in overload
drawing a current higher
than its rated current.
The user programmable
maintenance reminder time
has elapsed.
Changing Parameters
Name 01 Name 01 Name 01 Name 01 Name 01
Stop P1-01 P1-08
30.0A
P1-08 Stop
15 k W 400V 3Ph 50.0Hz 30.0A P1-08 30.0 3.0 30.0A 15 k W 400V 3Ph
Press and hold the
Navigate key > 2
seconds.
Use the Up and
Down keys to
select the required
parameter.
Display will
show the present
parameter value on
the lower line of the
display.
Press the Navigate
key for < 1 second.
Adjust the value
using the Up
and Down keys.
Display will show
the maximum and
minimum possible
settings on the
lower line of the
display.
Press for < 1 second
to return to the
parameter menu.
Press for > 2
seconds to return
to the operating
display.
Parameter Factory Reset / User Reset
Factory Parameter Reset : User Parameter Reset :
Name 01 Name 01 Name 01 Name 01 Name 01 Name 01
Stop P-Def Stop
Stop
U-Def Stop
15 k W 400V 3Ph 50.0Hz 15 k W 400V 3Ph P1-08 30.0 3.0 30.0A 15 k W 400V 3Ph
Press and hold the
Up, Down, Start
and Stop keys for
>2s.
The display shows
P-def. Briefly press
the Stop key.
The display
returns to Stop. All
parameters are
reset to Factory
defaults.
Press and hold the
Up, Down and Stop
keys for >2s.
The display shows
U-def. Briefly press
the Stop key.
The display
returns to Stop.
All parameters
are reset to User
Defaults.

Version 1.02 | T3-OPPAD TFT Remote Keypad IP55 User Guide | 7
www.bardac.com
Drive Fault Messages and Trip Codes
See drive User Guide for further information.
Further Status Messages and Troubleshooting
T3-OPPAD uses various display messages to indicate different working status. See the following table for more information.
Status Messages
Message Explanation
Scanning for Drive
xx
The T3-OPPAD is searching for the drive with address ‘xx’ in the network.
Load… The T3-OPPAD has found the drive in the network and is loading the initialisation information from
the drive.
SC-OBS The communication link between the drive and T3-OPPAD has failed.
Select Language Displayed in the language selection screen, with a list of available languages. Press the Navigate
key to select a language
Select drive address
xx
Displayed when selecting the address of the drive that the T3-OPPAD should try to communicate
with. Press the Stop key to select the drive address.
Select T3-OPPAD ID Displayed when selecting the T3-OPPAD ID (1 or 2) so that two T3-OPPADs can be
connected to a single drive, or network of multiple drives.
Troubleshooting
Symptom Explanation
Select drive address
xx
displayed after
‘SCAN..’ message
The T3-OPPAD failed to successfully communicate with the specified drive address in the network.
Check that the RJ45 data cable connection is correct. Check that the drive with address XX is
available in the network.
If XX > 1 and only one T3-OPPAD is connected, then check the T3-OPPAD device number, make
sure the number is 1.
Display ‘Err-id’
on
power up
This normally occurs when there are two T3-OPPAD units in the same drive network and both of
them have the same device number. Check and change the device number of one T3-OPPAD.
Display ‘Err-id’
during
normal operation
This normally occurs when the user plugs a second T3-OPPAD into the drive network. Change
the device number of one of the T3-OPPAD units.
Display
‘SC-OBS’
Communication link between the T3-OPPAD and drive has failed during operation.
Check the electrical connection, and make sure the cable is connected correctly between the T3-
OPPAD and the drive. Press ‘STOP’ button to enable the T3-OPPAD to search for the drive again.

Ñ82-OPTFT-IN_V2.00[Ó
82-OPTFT-IN_V2.00
Bardac Drives
40 Log Canoe Circle. Stevensville, MD 21666
(410) 604-3400 | (888) 667-7333
bardac.com | driveweb.com | automationthings.com