UltraLink®Monitor FTMU
lindab | technical information
Option B: Circuit board screw terminals
Connections are made in the terminal board which can be accessed when the lid of the display unit is removed. In the
back of the lid there is a picture with a list of the terminals.
1. 24V, power supply (AC G, DC +) *
2. GND, power supply (AC G0, DC -) *
3. +B, connection for Modbus via RS485
4. -A, connection for Modbus via RS485
5. SH, shield
6. GND, ground (system neutral)
7. AO1, analog output
8. AO2, analog output
9. AIN, (not used in this version)
10. MO1, (not used in this version)
11. MO2, (not used in this version)
12. GND, ground (system neutral)
13. SCL, not used
14. SDA, not used
15. GND, ground (system neutral)
16. 3V3, not used (in case of biasing)
*) When using AC terminal 1 (G) should have system potential and terminal 2 (G0) should be system neutral.
Recommendations for wiring
Function Cable type
24 V Supply 2-wire, thickness depending on length and load, max. 1,5 mm²
RS485 Modbus communication 2-wire shielded twisted pair, min. 0,1 mm² (LIYCY cable)
Using other cables for Modbus signals may result in communication problems.
Analog connection
When connecting the FTMU
using analog signals, it is impor-
tant to connect the analog out
signals on the FTMU (AO1, AO2)
to the analog in terminals on the
RTU and the analog in signal
(AIN) is connected to the analog
out terminal on the RTU. Also
make sure to connect the cables
to the same analog ground.
Option A: Connect to premounted cable
Connect the premounted cable in a junction box near the FTMU. Con-
nect power and signal cables in the junction box according to the color
scheme on the lable on the premounted cable, see picture to the right.
When connecting Modbus signal wires, the length of the premounted
cable needs to be as short as possible, since these have a negative
effect on signal quality.
In this case, place junction box as close to the FTMU as possible, then
cut the premounted where it is as short as possible for installation.
Connection of
UltraLink
Note! All cables that are
not connected must be
insulated.
24V Red
GND White
+B Yellow
-A Brown
GND Grey
AO1 Green
AO2 Blue
AIN Pink