
Logix® TC-2000 Process Controller, Page 3 of 7
output relay will energize when Sensor 2 measures above 57 F (55 F + ½ of 4 F). The Stage 2 output relay would de-energize
when Sensor 2 measures below 53 F (55 F - ½ of 4 F). A negative Setpoint would energize when Sensor 1 exceeds Sensor 2.
Controller Configuration
All “programming”, including changing setpoints, is performed in the Configuration Mode. To enter the Configuration Mode press
the Set button, the SP1 prompt appears. Both output relays remain de-energized during configuration. Use the up or down
arrow buttons to change the displayed parameter value. Press and hold the up or down arrow buttons to rapidly advance the
parameter. Press the Set button again move to the next parameter (you may scroll through each configuration parameter by
repeatedly pressing the Set button). Pressing the On/Off button will exit the configuration mode.
All configured values are stored in non-volatile (permanent) memory and will be retained for a minimum of 10 years without
power. No batteries are required.
Configuration Steps
When changing a setpoint value, then new value is saved when the Set button is pressed. If no buttons are pressed within 30
seconds the controller will save all new values and exit the Configuration mode automatically.
Step# Prompt Parameter Adj Range Default
1 Stage 1 Control Setpoint -20 F to +200 F (-29°C to +121°C) 70.0 F
2 Stage 1 Deadband 0 to 30 F (0 C to 17 C) 5 F
3 Stage 1 Mode HEAT or COOL COOL
4 Stage 2 Control Setpoint -20 F to +200 F (-29°C to +121°C) 80.0 F
5 Stage 2 Deadband 0 to 30 F (0 C to 17 C) 5 F
6 Stage 2 Mode HEAT, COOL, ALA = Alarm, dIF =
Differential (Dual Sensor Configuration
Only), OFF=disabled
OFF
7 High Temp Alarm Setpoint -20 F to +200 F (-28°C to +121°C) &
OFF
OFF
8 Low Temp Alarm Setpoint -20 F to +200 F (-28°C to +121°C) &
OFF
OFF
9 High Temp Alarm Setpoint 2 (Dual
Sensor Configuration Only)
-20 F to +200 F (-29°C to +121°C) &
OFF
OFF
10 Low Temp Alarm Setpoint 2 (Dual
Sensor Configuration Only)
-20 F to +200 F (-29°C to +121°C) &
OFF
OFF
11 Alarm on differential (Dual Sensor
Configuration Only)
-200 F to +200 F (-110 C to +110 C) &
OFF
OFF
12 AdEL Alarm Time Delay In 10ths of minutes, 0 to 1000 minutes. 0
13 User field scratchpad -1000 to +1000 0
14 Display Units, F or C, Whole or
Tenths
F = F Whole Units, F.0 = F in Tenths, C
= C Whole Units, C.0 = C in Tenths,
F Whole
Units
15 Configuration Lock On or OFF OFF
16 Datacomm Address 0 (disabled) to 255 255
17 Datacomm Speed 9600, 19.2K 38.4K or 115.2K BPS 9600 BPS
18 Sensor 1 Calibration Offset -30 F to +30 F (-17 C to +17 C) 0.0 F
19 Sensor 2 Calibration (Dual Sensor
Configuration Only)
Offset -30 F to +30 F (-17 C to +17 C) 0.0 F
Locking the Set Button
The Set button can be disabled to prevent tampering by unauthorized persons by setting the “Loc” function to On. To access the
Configuration mode when the Set button has been locked, the controller must first be Deactivated using the On/Off button, then
re-activated while holding the Set button. When the controller is activated, the “SP1" prompt will be displayed indicating that it is
in the Configuration mode. After leaving the Configuration mode the Set button will remain locked unless the “Loc” parameter
was changed to “OFF”.