LSIS GIPAM 2200 User manual

Front View
CB ON/OFF
CT/PT Ratio Setting
③③Direction
④④Function
⑤⑤CB
ON/OFF
1. Press ESC or ENTER to move to Menu mode.
2. Select 5.PT/CT SETTING.
3. Put and save the value by the direction key.
①①Trip Assign LED
* If there is not any command
inputting for within 15
minutes, the LCD back light
would be turned off.
* After turned off, it is needs
to input password.
※Once the password is put,
only ①⑤⑥steps are needed.
②②Remote / Local
Trip Assign LED
- Fault Indication
- Moving cursor
and change
setting values
Remote /
Local transfer key
Direction key
Function
CB ON/OFF
X 3 times
Move to control
Menu
OPEN
X 3 times
Select
items
Change
values
(Initial monitor)
Completed
These steps apply to GPT, CT, NCT
ratio Setting. After the setting change,
press ESC key to move to the menu
that you want.
Relay element setting
press
Change the value
(High Low)
Move the cursor
Move the cursor
Put values
you want
Saving of
changed data
Move to Time
delay menu
Select the
curve you want
Put each item in the
same way
Saving of
changed data
Move to
initial state
Move the cursor
Put values
you want
Move the cursor
Change the value
(OFF ON)
Setting other element
Same process
Select the element
Saving of changed data
X 3 times
and
After moving the cursor
to a relay element that
you want to set with
2013. 06
For your safety, please read user's manual
thoroughly before operating.
Any maintenance and inspection shall be performed
by the personnel having expertise concerned.
Safety Instructions
●Setting Items
①
Select usage of Instantaneous characteristic.
②
Setting value for Instantaneous characteristic.
(set to multiple of CT ratings)
ex) if CT ratio : 100/5, I >> : 4.0In
�Primary current of CT = 4.0 X 100 = 400A
�Secondary current of CT = 4.0 X 5 = 20A
(In : Rating current of CT)
③
Operating time for Instantaneous characteristic.
※Available to use two stages (Low, High) for Instantaneous
Op. time
- Low : within 40ms - High : 0.05~300s
④
Choose characteristic curve.
[Available to choose DT(Definite Time), SI(Standard Inverse),
VI(Very Inverse), EI(Extremely Inverse), LI(Long Inverse)]
⑤
Setting value for Time delay characteristic. ( Refer to
②
)
⑥Select Time Lever or Time dial for Inverse characteristic.
(range : 0.05~1.2, able to use when choosing Inverse curve in ④)
⑦Constant Time Delay (range : 0.0~10.0 sec)

Other LSIS Relay manuals

LSIS GIPAM 2000 User manual

LSIS

LSIS GIPAM 2000 User manual

LSIS EMPR Series User manual

LSIS

LSIS EMPR Series User manual

LSIS GIPAM 115 FI User manual

LSIS

LSIS GIPAM 115 FI User manual

Popular Relay manuals by other brands

Multilin PROTECT 4A-120 instruction manual

Multilin

Multilin PROTECT 4A-120 instruction manual

Schweitzer Engineering Laboratories SEL-351-1 instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-351-1 instruction manual

Panasonic IC Drivable PC Board instruction manual

Panasonic

Panasonic IC Drivable PC Board instruction manual

Eaton ZE/XTOM Series manual

Eaton

Eaton ZE/XTOM Series manual

Circutor RGU-10C quick start guide

Circutor

Circutor RGU-10C quick start guide

Contrel ELR-3B quick start guide

Contrel

Contrel ELR-3B quick start guide

Areva MiCOM P225 Technical guide

Areva

Areva MiCOM P225 Technical guide

Siemens SIMPRO-100 instruction manual

Siemens

Siemens SIMPRO-100 instruction manual

ABB HCB Instruction leaflet

ABB

ABB HCB Instruction leaflet

Broyce Control P9650 quick start guide

Broyce Control

Broyce Control P9650 quick start guide

KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG-SOLAR manual

KAEL Muhendislik Elektronik

KAEL Muhendislik Elektronik VARkombi-12-PC-TFT-OG-SOLAR manual

Honeywell 7800 SERIES manual

Honeywell

Honeywell 7800 SERIES manual

FANOX SIA F Protocol manual

FANOX

FANOX SIA F Protocol manual

Eaton Motor Insight C441 Product Installation Leaflet

Eaton

Eaton Motor Insight C441 Product Installation Leaflet

urmet domus 1054/102 quick start guide

urmet domus

urmet domus 1054/102 quick start guide

Franklin Electric SUBMONITOR CONNECT Series Installation and operation manual

Franklin Electric

Franklin Electric SUBMONITOR CONNECT Series Installation and operation manual

MICROENER MC20-X/10-4 Operation manual

MICROENER

MICROENER MC20-X/10-4 Operation manual

Functional Devices WR E20-EN2 Series Applications manual

Functional Devices

Functional Devices WR E20-EN2 Series Applications manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.