EM-7802-R Rev.2 P. 2 / 10
COMPONENT IDENTIFICATION
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
MS X10 X1
NODE ADD. B.RATE
CNFG.
12345678
10 11 12 13
2341
15 16 17 18
7896
14
5
NS
23415
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) DeviceNet, Power Supply Terminals
(G) Input Terminals
(A)
(F) (G)
(B) (C) (D) (E)
■STATUS INDICATOR LED
ID S TAT E TO INDICATE
MS Green Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red Critical failure
Blinking Red Minor failure
OFF No power supplied
NS Green Link on-line and connections in the
established state
Blinking Green Link on-line but no connections in
the established state
Red Critical link failure
Blinking Red Minor link failure
OFF No power supplied
■NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking
The R7D communicates in the baud rate setting detected at
the startup with the switch set to the positions 0 (125 kbps),
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network
to determine the baud rate on the network.
■OPERATING MODE
(*) Factory setting
• Extension (SW1-1, 1-2)
SW1-1 SW1-2 EXTENSION
OFF OFF No extension (*)
ON OFF Discrete input, 8 or 16 points
OFF ON Discrete output, 8 or 16 points
• Conversion rate / Accuracy (SW1-3, 1-4)
SW1-3 SW1-4 CONVERSION RATE / ACCURACY
OFF OFF 80 msec. / ±0.5% (*)
ON OFF 40 msec. / ±0.5%
OFF ON 20 msec. / ±1.0%
ON ON 10 msec. / ±2.0%
• Input range (SW1-5, 1-6, 1-7, 1-8)
SW1-5 SW1-6 SW1-7 SW1-8 INPUT RANGE
OFF OFF OFF OFF CLSE-60 (*)
ON OFF OFF OFF CLSE-40
OFF ON OFF OFF CLSE-20
ON ON OFF OFF CLSE-10
OFF OFF ON OFF CLSE-05
ON OFF ON OFF CLSE-R5
ON ON ON ON PC Configurator setting
■DeviceNet TERMINAL ASSIGNMENT
23415
NO. ID FUNCTION, NOTES
1 V+ Network power supply +
2 CAN_H Network data High
3 Drain Shield
4 CAN_L Network data Low
5 V– Network power supply –
■INPUT TERMINAL ASSIGNMENT
10
K0
11
L0
12
K1
1
NC
2
NC
3
NC
13
L1
4
NC
14
NC
5
NC
15
K2
6
NC
16
L2
7
NC
17
K3
8
NC
9
NC
18
L3
NO.
ID FUNCTION
NO.
ID FUNCTION
1 NC No connection 10 K0 AC current K0
2 NC No connection 11 L0 AC current L0
3 NC No connection 12 K1 AC current K1
4 NC No connection 13 L1 AC current L1
5 NC No connection 14 NC No connection
6 NC No connection 15 K2 AC current K2
7 NC No connection 16 L2 AC current L2
8 NC No connection 17 K3 AC current K3
9 NC No connection 18 L3 AC current L3
■EXTENSION MODULE
Combinations with all extension modules are selectable.