M-system JTY2 User manual

JTY2
EM-1573 Rev.1
P. 1 / 7
The shape of base socket may be different
for some models.
INSTRUCTION MANUAL
MODEL JTY2
PULSE DURATION RECEIVER
(field-programmable; built-in excitation)
Body Base Socket
Connection
Diagram Label
Front Cover
Specification
Label
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket
are slightly different with various
socket types.
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) ..................... (1)
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation and connection, hard-
ware setting, operation of the Programming Unit (model: PU-
2x)* specific to this model and basic maintenance procedures.
This unit is factory adjusted and calibrated according to the
Ordering Information included in the product package. If you
don’t need to change the pre-adjusted setting, you can skip
the sections on hardware setting and calibration and Soft-
ware Setting in this manual.
*When you need to change software settings, please refer to
the Operation Manual for Model PU-2x (EM-9255), Section
B: (B-1) Introduction, (B-2) General Operation Description,
(B-3) Operation Flowchart for general information.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Check the power rating for the unit on the specification label.
85 – 132V AC rating: 85 – 132V, 47 – 66 Hz, approx. 6VA
12, 24, and 48V DC ratings: Rating ±10%, approx. 3.3W
110V DC rating: 85 – 150V DC, approx. 3.3W
■ UNPLUGGING THE UNIT
• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C (23
to 140°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind the unit's cables together with cables where
high noise levels are present. Do not install them in the same
duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
COMPONENT IDENTIFICATION
■ HOW TO OPEN THE FRONT COVER:
Position your finger on the hook at the top of front cover and
pull.
INSTALLATION
Detach the yellow clamps located at the top and bottom of the
unit for separating the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bot-
tom. Position the upper hook
at the rear side of
base socket on the DIN rail
and push in the lower. When
removing the socket, push
down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■ WALL MOUNTING
Refer to the drawings in the
next page.

JTY2
EM-1573 Rev.1
P. 2 / 7
5678
21
1110
80 (3.15)
50 (1.97) 107 (4.21)
136 (5.35) [3.3 (.13)]
80 (3.15)
20
(.79)
35.4 (1.39)
40 (1.57)
50 (1.97)
7.8 (.31)
CLAMP
(top & bottom)
DIN RAIL
35mm wide
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
•When mounting, no extra space is needed between units.
39
4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.
■ DIMENSIONS mm (inch)
■ CONNECTION DIAGRAM
+
–
OUTPUT
1
2
U(+)
V(–) POWER
7
8
PU-2x
MODULAR JACK
–
INPUT
+5
4
6
+
SENSOR EXCITATION
9
10
ALARM OUTPUT
5
4
6
+
5kΩ
■Dry Contact
Input Connection Examples
+
–
–
Vsns
PWR
■2-Wire Current Pulse
•Built-in Excitation
5
4
6
–
+
Vsns
2-WIRE
PICK-UP
•External DC Supply
5
4
6
–
Vsns
2-WIRE
PICK-UP
+
+
DC SUPPLY
–
100Ω
■Voltage Pulse
5
4
6
+
+
–
–
Vsns
PWR
100Ω
CHECKING
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
–8with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the "ANALOG
OUTPUT ADJUSTMENT" procedure.

JTY2
EM-1573 Rev.1
P. 3 / 7
HARDWARE SETTING & CALIBRATION
■ FRONT PANEL CONFIGURATION
5
4
3
2
1
0
9
8
7
6
1
2
3
4
5
6
ON
Span Adj.
Detecting Level Adj.
Detecting Level Adj. Pin
Pulse Amplitude Selector
Input Type Selector
Zero Adj.
Sensor Excitation Adj.
Modular Jack
Input Monitor LED PL1
■ PULSE AMPLITUDE (rotary switch) (*) Factory setting
For voltage pulse input, select the pulse amplitude (V p-p)
among the switch positions 0 through 6. For open collector
or two-wire current pulse input, set the switch to 7. DO
NOT SET to 8 or 9. The power supply to the unit must be
turned off when changing the setting.
■ DIP SWITCH SETTING (*) Factory setting
SW6 is not used. The power supply to the unit must be turned
off when changing the setting.
•Input Type
INPUT TYPE SW1 SW2 SW3 SW4 thr. 6
Open collector (*) ON OFF ON OFF
Voltage pulse OFF OFF ON OFF
Two-wire current pulse
OFF ON ON OFF
SW PULSE AMPLITUDE MAX. INPUT VOLTAGE
050 – 100V p-p 50V
125 – 50V p-p 50V
210 – 25V p-p 25V
3 5 – 10V p-p 10V
4 1 – 5V p-p 5V
50.5 – 1V p-p 1V
6 0.1 – 0.5V p-p 0.5V
7(*) Open collector or two-wire current pulse
■ DETECTING LEVEL
A specific sensitivity scale is applied according to the pulse
amplitude setting. The scaled input voltage is then com-
pared to the preset detecting level.
The scaled H level voltage must be higher than the detect-
ing level so that the pulse state is accurately detected.
SW PULSE AMPLITUDE SENSITIVITY SCALE
050 – 100V p-p 1/20
125 – 50V p-p 1/10
210 – 25V p-p 1/5
3 5 – 10V p-p 1/2
4 1– 5V p-p 1
50.5 – 1V p-p 5
6 0.1 – 0.5V p-p 10
7Open collector or 1
two-wire current pulse
■EXAMPLE 1:
VOLTAGE PULSE with Amplitude 5V p-p, DC Offset 2.5V
Input type: Voltage
Input amplitude: 1 – 5V p-p
The rotary switch and DIP switch are configured as shown
below.
■EXAMPLE 2:
VOLTAGE PULSE with Amplitude 35V p-p, DC Offset 15V
Input type: Voltage
Input amplitude: 25 – 50V p-p
The rotary switch and DIP switch are configured as shown
below.
ON
123456
Rotary SW DIP SW
5
6
7
8
9
0
1
2
3
4
ON
123456
Rotary SW DIP SW
5
6
7
8
9
0
1
2
3
4
•How to Change the Detecting Level
A pulse generator which can simulate the selected input type
and waveforms with appropriate amplitude is required.
1) Set the rotary switch and the DIP switch to an appropriate
input type and pulse amplitude.
2) Connect the positive probe of the pulse generator to the
terminal 5, the negative probe to the terminal 6 of the base
socket.
3) Set the pulse generator output to 1 kHz with the duty ratio
50%, and apply the signal to the transmitter.
4) Connect the Programming Unit to the modular jack and
execute [GROUP 01] [ITEM 06] to show the input duty
ratio.
5) Press [ENTER] key multiple times to adjust the detecting
level until the display shows 50.00 ±0.1%. This adjust-
ment affects the transmitter’s accuracy. Be sure to set the
duty ratio within 0.1% allowances.
6) Confirm that the input monitor LED (PL1) is ON (it should
actually be flashing in 1 kHz). If the LED does not turn on,
the detecting level may be out of the pulse amplitude
range. Change the detecting level again.

JTY2
EM-1573 Rev.1
P. 4 / 7
25
5
12
24
60 120
CURRENT (mA)
VOLTAGE (V)
Voltage (V) ×Current (A) ≤600mW
+
–OUTPUT
1
2
U(+)
V(–) POWER
7
8
PU-2x
MODULAR JACK
–
INPUT +5
4
6
+
SENSOR EXC.
9
10
ALARM OUTPUT
V
A
Ammeter
Voltmeter
■ SENSOR EXCITATION ADJUSTMENT
You can change the sensor excitation voltage with the sensor
excitation adj. located behind the front cover. If you need to
change it, check that the required current is within the
specification.
•How to Change the Excitation
A voltmeter and ammeter of class 0.5 or better accuracy are
required.
1) Connect the voltmeter across the terminals 4 – 6.
2) Connect the ammeter to terminal 4.
3) Turn the potentiometer until the meter shows the desired
value.
Check that the current value indicated on the ammeter is
within the allowable limit. If the value is greater than the
limit, lower the voltage value or connect a separate power
source. Otherwise, the transmitter may fail.
■ ANALOG OUTPUT ADJUSTMENT
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibra-
tion.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
• How to Calibrate The Output Signal
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure
1) – 3).

JTY2
EM-1573 Rev.1
P. 5 / 7
SOFTWARE SETTING
Please refer to the Operation Manual for Model PU-2x (EM-9255), Section B: (B-1) Introduction, (B-2) General Operation
Description, (B-3) Operation Flowchart for general information.
MDF.
CODE
[GROUP 01]
ITEM INPUT DATA EXAMPLE (EXAMPLE) DEFAULT CONTENTS
01 S N/A MAINTENANCE SWITCH
0MTSW : MON.MODE 0 : Data indication only.
1 MTSW : PRG.MODE 1 : All ‘P’ marked parameters are modifiable.
02 P Alphanumeric TG : XXXXXXXXXX N/A Tag name entry (10 characters max.)
03 P Percentage OUTPER XXX.XX N/A Output monitor (%) & simulation output
05 D No input INPPER XXX.XX N/A Input monitor (%)
06 D No input INDUTY XXXXXX N/A Input duty ratio (%)
07 D No input N/A Input specification selected with the front rotary switch
SW : IN_V 1/20 SW = 0, Voltage input, Sensitivity scale = 1/20
SW : IN_V 1/10 SW = 1, Voltage input, Sensitivity scale = 1/10
SW : IN_V 1/5 SW = 2, Voltage input, Sensitivity scale = 1/5
SW : IN_V 1/2 SW = 3, Voltage input, Sensitivity scale = 1/2
SW : IN_V 1/1 SW = 4, Voltage input, Sensitivity scale = 1/1
SW : IN_V 5/1 SW = 5, Voltage input, Sensitivity scale = 5/1
SW : IN_V 10/1 SW = 6, Voltage input, Sensitivity scale = 10/1
SW : IN_OC, mA SW = 7, Open collector or two-wire current input
SW : no use SW = 8, (not used)
SW : no use SW = 9, (not used)
08 P Numetic AVERAGE XX 4 Cycles for the moving average calculation, 0 to 30
08 P Numetic HI CUT XX 1 High samples to be discarded, 0 to 10
10 P Numeric LO CUT XX 1 Low samples to be discarded, 0 to 10
11 P0Linearization
0STRAIGHT Without
1CURVED With (ITEM 60 to 91 for segment data input)
12 P 0.00 Input zero duty ratio (two methods are available)
Percentage ZERO XXX.XX 1. Enter a specific duty ratio in % (0.00 – 100.00%)
XXX.XX 2. Apply a simulated input and press [DATA] [ENTER]
13 P 100.00 Input span duty ratio (two methods are available)
Percentage SPAN XXX.XX 1. Enter a specific duty ratio in % (0.00 – 100.00%)
XXX.XX 2. Apply a simulated input and press [DATA] [ENTER]
19 P Percentage FINZER XXX.XX 0.00 Fine zero adjustment
OUTPER XXX.XX When data is entered, output (%) is shown.
20 P Percentage FINSPN XXX.XX 100.00 Fine span adjustment
OUTPER XXX.XX When data is entered, output (%) is shown.
21 P 1 Alarm mode
0NO ALARM No alarm trip
1UPPER ALARM High alarm trip
2LOWER ALARM Low alarm trip
22 P Percentage ALARM XXX.XX 100.0 Alarm setpoint (-15 to +115%)
23 P Percentage ALMHYS 1.00 Alarm deadband (hysteresis) (0 to 20%)
24 P Seconds ALTIME 3.0 Alarm delay at the startup (2.0 to 1000.0 seconds)
25 P 0 No input alarm
0TMOUT ALM : OFF Without (Hi/Lo setpoint alarm only, ITEM 22 – 24)
1 TMOUT ALM : ON With (Hi/Lo setpoint alarm + no input alarm, ITEM 26)
26 P Seconds TMOUT XXXX.X 1.0 No input detecting time (0.1 to 100.0 seconds)
When no input is detected for the specified time period,
the duty ratio is forced to 100%/0%.
27 P 1 Input pulse logic
0ACTIVE LO Non-inverted: Lo level with the voltage/current pulse or
ON with the open collector is valid.
1ACTIVE HI Inverted: Hi level with the voltage/currrent pulse or
OFF with the open collector is valid.

JTY2
EM-1573 Rev.1
P. 6 / 7
MDF.
CODE
■LINEARIZATION TABLE
The I/O curve is approximated at 16-point segments. Set only
the required pairs of I/O points. Refer to the figure below.
X (nn) : Input %
Y (nn) : Output %
Range : -15.00 to +115.00%
[GROUP 01]
ITEM MDF. CODE DATA EXAMPLE
60 P X (01) : XXX.XX
61 P Y (01) : XXX.XX
62 P X (02) : XXX.XX
63 P Y (02) : XXX.XX
64 P X (03) : XXX.XX
65 P Y (03) : XXX.XX
66 P X (04) : XXX.XX
67 P Y (04) : XXX.XX
68 P X (05) : XXX.XX
69 P Y (05) : XXX.XX
70 P X (06) : XXX.XX
71 P Y (06) : XXX.XX
72 P X (07) : XXX.XX
73 P Y (07) : XXX.XX
74 P X (08) : XXX.XX
75 P Y (08) : XXX.XX
76 P X (09) : XXX.XX
77 P Y (09) : XXX.XX
78 P X (10) : XXX.XX
79 P Y (10) : XXX.XX
80 P X (11) : XXX.XX
81 P Y (11) : XXX.XX
82 P X (12) : XXX.XX
83 P Y (12) : XXX.XX
84 P X (13) : XXX.XX
85 P Y (13) : XXX.XX
86 P X (14) : XXX.XX
87 P Y (14) : XXX.XX
88 P X (15) : XXX.XX
89 P Y (15) : XXX.XX
90 P X (16) : XXX.XX
91 P Y (16) : XXX.XX
Modification Code
S:Modifiable at any time.
P:Modifiable only when the MAINTENANCE SWITCH is in
the “PRG” mode.
-15%
0
Y01 X02 X03 X04 X05 +115%
Y02
X01
Y03
Y04
+100% Y05
INPUT
OUTPUT
-5%
[GROUP 01]
ITEM INPUT DATA EXAMPLE (EXAMPLE) DEFAULT CONTENTS
60 P Percentage X (01) : XXX.XX 0.00 Linearization table (16 points)
P Percentage Y (01) : XXX.XX 0.00 Set at the maximum of 16 pairs of input (X) and output
:: : : (Y) calibration points in %. Fill data from the lowest
:: : : ITEM No. from the lowest calibration point and add as
:: : : many as required. The output in the undefined range is
90 P Percentage X (16) : XXX.XX 0.00 maintained at the value of the first and the last
91 P Percentage Y (16) : XXX.XX 0.00 calibration points.
Modification Code
D:No modification (writing) possible. Used only for monitoring (reading).
S:Modifiable at any time.
P:Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.
ROM Version Indication
[GROUP 00] [ITEM 99]

JTY2
EM-1573 Rev.1
P. 7 / 7
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
productwasoriginallypurchasedifsuchproducthasbeenusedundernormaloperatingconditionsandproperlymaintained,M-System'ssoleliability,andpurchaser'sexclusiveremedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
■NO INPUT DETECTING TIME
When no input is detected for a preset time period, the transmitter provides an output equivalent to 0% or 100% duty ratio
according to the input status.
Select the time to be longer than the ON/OFF or Hi/Lo levels of the input pulse.
INPUT LOGIC
NON-INVERTED INVERTED
Open collector OFF state longer than the preset Output equivalent to 100% duty ratio Output equivalent to 0% duty ratio
input time period
ON state longer than the preset Output equivalent to 0% duty ratio Output equivalent to 100% duty ratio
time period
Voltage pulse, H state longer than the preset Output equivalent to 100% duty ratio Output equivalent to 0% duty ratio
Two-wire time period
current pulse L state longer than the preset Output equivalent to 0% duty ratio Output equivalent to 100% duty ratio
input time period
Table of contents
Other M-system Receiver manuals
Popular Receiver manuals by other brands

Lynx
Lynx yellobrik ORX 1802 LC quick reference

Denon
Denon Ceol Quick setup guide

JVC
JVC KD-DV7406 Installation and connection manual

International Datacasting
International Datacasting STAR Generation 2 user guide

GAMA Electronics
GAMA Electronics RF240V-2WP instruction manual

Marantz
Marantz SR6009 quick start guide