M-tech MA-1000 User manual

MA-1000
Addressable Fire Alarm Control Panel
Installation & Operations Manual
Conforms to UL864 9th Edition
Issue Number: 180776
Doc#900298 Rev.A
20-05-2012
BY MTECH

1

2

3
Table of Contents
1General
1.1
Product Features
6
1.2
Specifications
7
1.3
Controls and Indicators
9
2Installations
2.1
Agency Requirements
11
2.2
Calculating Current Draw and Standby Battery
12
2.3
Calculating Maximum Current Draw and Battery Backup Requirements
13
2.4
Mounting the Enclosure /Door Label
14
2.4.1
Connecting the AC Power
16
2.4.2
Battery Installation
17
2.4.3
Output (NAC) Installation
18
2.4.4
Relay Installation
19
3 Programming
3.1
Menu System
20
3.1.1
Power-up Screen
21
3.1.2
Idle Screen
21
3.1.3
Alarm Screen
21
3.1.4
Trouble Screen
22
3.1.5
Supervisory Screen
23
3.1.6
Login Screen
23
3.2
Main Menu
24
3.2.1
General Menu Setup
24
3.2.1.1
Default Setup
24
3.2.1.2
Time/Date Setup
25
3.2.2
SLC Setup
26
3.2.2.1
CDR(Customer data record)
26
3.2.2.2
Walk Test
27
3.2.2.3
Maintenance Menu
28
3.2.3
Output Setup
30
3.2.3.1
Nac Setup
30
3.2.3.2
Cadence Setup
31
3.2.3.3
Relay Setup
32
3.2.4
History Display
33
3.2.5
PC Menu
34
3.2.6
Device Enable/Disable
34
3.2.7
Network
36
3.2.8
Remote Annunciator
37
3.2.9
Booster
38
3.3
Gas Release
39

4
4Appendix
4.1
Data Sheet for FSUTLC(Loop Card)
41
4.2
Installation Instructions for 3 Channel I/O Unit FSUTCIOU
42
4.3
Installation Instructions for Mini Input Monitor FSUMIM
45
4.4
Installation Instructions for Output Monitor FSUOM
47
4.5
Installation Instructions for T-tap FSUSIU
49
4.6
Installation Instructions for Remote Annunciator FSURA
51
4.7
Installation Instructions for Mini Output Monitor FSUMOM
54
4.8
Installation Instructions for Mini Zone Monitor FSUMZM
56
4.9
MA-1000 Site Installer User Manual (PC program)
58
4.10
Networking
98
4.11
Operating Instructions
100
4.12
Detectors UL Certifications
101
4.13
Basic Operating Instructions
103
Notes:
1. For maintenance recommendations refer to NFPA 72 National Fire Alarm Code, 2007.
2. Compatibility identifier number: 0409008
3. Software release: Dec 2008 Version 08
4. Install in accordance to NFPA 72 (2007).
5. All circuits inherently power limited except AC wiring and battery cabling.
6. UL 864 9th Edition does not permit the disabling of all zones.
7. UL864 9th Edition does not permit the use of Auto Silence.

5
CAUTIONS
1. BATTERY MAINTENANCE INSTALLATION CAUTIONS
Initial preparation before installation:-
Verify no abnormalities on battery case (like crack or leakage)
Free air space must be provided between each battery. Recommended minimum space is 5~10mm
(0.02~0.04 inches).
Set the batteries firmly in the equipment. Otherwise, batteries may be damaged, or connection
conductivity may be decreased due to shock. When batteries are used in vibration conditions, they
shall be mounted in upright position and with proper cushion for protecting vibration.
Avoid mixed usage of batteries differing in capacity, manufacturer, storage or charge/discharge
conditions. Batteries may be damaged after cycles due to difference in electrical characteristics.
2. REGULAR CHECK AND REPLACE PRECAUTIONS
Measure the total voltage of the batteries during float charge to see whether there is any abnormal
deviation and investigate the situation.
TRANSPORTATION PRECAUTIONS
Handle the batteries carefully to avoid injuries.
Avoid moisture or rain on the batteries and cartons.
Transport the batteries in the upright position and avoid abnormally strong shock / vibration.
Do not lift a battery by its terminal. Otherwise, internal construction may be damaged and leakage
may occur.
3. OTHER PRECAUTIONS
Clean battery with wet soft cloth. Never apply oil, polyvinyl chloride or organic solvents (like gasoline
and paint thinner) to the battery. Otherwise, battery cover may be cracked / deform and acid leakage
will result.
Do not disassemble the battery. Otherwise, sulphuric acid will flow out.
If sulphuric acid deposit on to skin or cloth, wash immediately with water. If splashed into eyes, wash
with a large amount of water and consult medical physician immediately.
Avoid dusting by cloth duster or dry cloth (particularly chemical textile), as they will generate static
electricity which is dangerous.
Wash your hands after handling battery.
Do not short the battery terminals.
Never dispose battery into fire.

6
MA-1000 FACP
1General
The MA-1000 provides all of the sophisticated features required of a leading edge analog fire
system along with the simple operation and neat installation demanded by both installers and
building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample
facilities for rear or top cable entries.
A comprehensive range of ancillary devices is available to operate with MA-1000, including Optical,
Ionization, photo-thermal and heat detectors.
Each of the MA-1000 system components has been specifically designed to operate as part of a
MA-1000 system, this provides an assurance that the panel, the detectors, the interfaces and the
ancillaries are all fully compatible with one another and that the full range of system functionality is
supported by each device.
1.1 Product Features
The Panel has the following features:
Built-in four-line (16 Characters each line) LCD display provides easy to read readouts.
15 key keypad for programming, reset and silencing.
2 SLC loops (optional 4 loops).
Real time clock.
Event History Buffer (256 events) with Date/Time stamp. Events can be displayed on LCD.
8 selectable/programmable output patterns for notification appliance (outputs) circuits.
4 Notification appliance circuits (NAC's) outputs.
3 programmable general purpose relays.
Built-in walk test.
Switchable 6 amp power supply INPUT 110-120 3.2A, 220-240VAC 1.6A 50/60Hz
OUTPUT +24V 6.5A
Dedicated alarm and trouble relays.
Housed in a 37.0cmW x 39.5 cm H x 11.5 D metal cabinet.
Cabinet supports two 12V, 7Ah backup batteries.

7
1.2 Specifications
AC Power
6.5A POWER SUPPLY AC Input max 3.2A (120VAC) 1.6A (220VAC) model number S-150-24.
Battery (sealed lead acid only)
Maximum charging circuit –0.98A&22VDC
Maximum charger capacity: 18 amp hour battery (two 7 amp hour batteries can be housed in the
enclosure. Larger batteries require a separate Battery Cabinet MBC “Mini Battery Cabinet”
manufactured by space age.
SLC Circuits
The MA-1000 Panel comes with two SLCs loops (optional 4 SLC loop card) which has the following
parameters:
Supply voltage: 24 VDC nominal, 27.6 VDC maximum.
Addressable Loops
Max Number: 2
Max Load per loop: 60 mA
Maximum loop current is 150 mA (short circuit)
Max Number of Addressable Devices per loop: 200
The total number of addresses per loop is 200; this includes detectors, manual pulls and all other
addressable items. When designing systems it’s recommended that allowances are made for future
expansion, Short circuit isolators are incorporated into every MA-1000 loop device, including Smoke
detectors, heat detectors, sounders, manual pulls and interfaces. Therefore, no further fault
protection is required, in the event of a single fault; none of the devices connected to the loop will fail
to operate as the fault will be isolated by the two adjacent devices.
T-tap connected devices downstream of a cable fault will cease to function.
Notification Appliance Circuit(s)
4 NACs Regulated
Supervised for ground faults impedance value 1KΏ
1.2 ampere per NAC
Operation: Style Y (Class B Style Y)
Power-limited Circuitry
Normal Operating Voltage: Nominal 24 VDC, Maximum 27 VDC
Maximum Signaling Current: 4.2 amps total with 6.5AMP power supply P/N 08.009.
Maximum Line Impedance: 1.5 volt drop end-of-line
End-of-Line Resistor: 10KΩ 1/5 5% (part number 06.006)
NAC Specification
Four programmable outputs are Notification Appliance Circuit (NAC).

8
The NAC provide the following programmable modes:
NAC Steady –24 VDC at alarm condition
NAC Temporal Code –24 VDC at alarm condition (on, off, on, off)
NAC March Time –24 VDC at alarm condition (on, on, off, off, on, on, off, off)
Synchronization - Cooper Wheelock DSM-12/24 p/n 06.012 is for per NAC MAX 20 devices can be
connected.
Max arms current 70mA
ANSI S-3-41
Single stroke BI
California code
Form C Relays
Trouble Relay is common working when Trouble condition.
Alarm Relay is common working when Alarm condition.
Relay 1 is programmable relay.
Relay 2 is programmable relay.
Relay 3 is programmable relay.
All relays have same rating: 2A, 30VAC, resistive
The FACP provides 3 programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all
with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note: that the relay connections must be power-limited. Refer to UL Power-limited wiring
requirements.
Loop lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the MA-
1000 Loop Card PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must
be included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between
floors, down to manual call points) must be included. Remember to include these especially when
taking loop lengths from plan drawings.

9
1.3 Controls and Indicators
Front Panel Membrane User Buttons
Acknowledge
This function, also abbreviated to "ACK", is used to acknowledge an abnormal situation such as an
alarm or trouble condition. The acknowledge function tells the panel that building personnel or
emergency responders are aware of the alarm, trouble, or supervisory condition. Acknowledging the
alarm or trouble condition also normally silences the panel's own sounder.
Alarm Silence
Also known as "audible silence". Depending on the configuration of the alarm system, this function
will either silence the system's notification appliances completely, or will silence only the audible
alarm, with strobe lights continuing to flash. Audible silence allows for easier communication
amongst emergency responders while responding to an alarm. This can also be used during
construction as a means of a preliminary test, before the final full test.
Reset
This resets the panel after an alarm condition. All initiating devices are reset, and the panel is
cleared of any alarm conditions. If an initiating device is still in alarm after the system is reset, such
as a smoke detector continuing to sense smoke, or a manual pull station still in an activated
position, another alarm will be initiated.
LED Indicators
AC Green LED
AC power (green light) when this indicator is lit, power is being provided to the system from the
building's electrical system, and not from the backup battery. When an AC power condition changes,
the Trouble indicator comes on and the AC power indicator goes off and the screen alerts building
personnel of a power failure. If the AC power indicator is lit without any other indicators also lit, then
the system is in a normal condition. If no LEDs are lit, there is no power source feeding the panel.
ALARM Red LED
Alarm (red light) This indicator is lit when an alarm condition exists in the system, initiated by smoke
detectors, heat detectors, sprinkler flow switches, manual pull stations, manual call points, or
otherwise. Along with the indicator on the panel, notification appliances, such as horns and strobes,
are also activated, signaling a need to evacuate to building occupants. In an alarm condition, the fire
alarm panel indicates where the alarm originated. The alarm panel can be reset once the device
which initiated the alarm is reset, such as returning the handle of a manual pull station to its normal
position.
TROUBLE Yellow LED
Trouble/Fault (yellow light) When held steady or flashing, it means that a trouble condition exists on
the panel. Trouble conditions are often activated by a contaminated smoke detector or an electrical
problem within the system. Trouble conditions are also activated by a zone being disabled
(disconnected from the system), a circuit being disabled, low power on the backup battery, the
disabling of a notification appliance, the ground faults, or short or open circuits. The alarm panel's
sounder will activate if a trouble condition exists. In a trouble condition, the panel displays the zone
or devices causing the condition. The "Trouble" indicator goes out automatically when the situation
causing the trouble condition is rectified.

10
SILENCE Yellow LED
Also known as "audible silence". Depending on the configuration of the alarm system, this function
will either silence the system's notification appliances completely, or will silence only the audible
alarm, with strobe lights continuing to flash. Audible silence allows for easier communication
amongst emergency responders while responding to an alarm. This can also be used during
construction as a means of a preliminary test, before the final full test.
SUPERVISORY Yellow LED
Supervisory (yellow light) This signal indicates that a portion of the building's fire protection system
has been disabled (such as a fire sprinkler control valve being closed and, consequentially, a
sprinkler tamper switch being activated), or, less frequently, that a lower priority initiating device has
been triggered (such as a duct smoke detector). The "Supervisory" indicator requires a "Reset" to
clear.
Local Piezo Sounder
A Piezo sounder provides separate and distinct sounds for alarm, trouble, and supervisory
conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off

11
2Installations
Essential please read before proceeding!
The equipment described in this manual is listed by ETL TESTING LABORATORIES, for use in fire
alarm signaling systems, only when installed in accordance with this manual and the latest National
Fire Protection Association Standards NFPA 72; the National Electrical Code (NFPA 70); the Life
Safety Code (NFPA 101); and/or the local authority having jurisdiction (AHJ).
It is possible to apply system components incorrectly or arrange system components and installation
wiring so that required life safety functions are NOT performed. As a result, lives may be lost.
To minimize this possibility:
DO NOT deviate from any installation instructions contained in this manual.
DO NOT assume any installation details not shown in this manual.
DO NOT alter any mechanical or electrical features of the equipment supplied
BE FAMILIAR with the building code, fire prevention code, and/or requirements of the Authority
Having Jurisdiction (AHJ) in the locale of the installation.
!Caution!
Under normal and fault conditions, AC line voltages may be present on any terminal. Touching any
component could be hazardous and result in loss of life. A short circuit can result in arcing that could
cause molten metal injuries to testing personal.
To minimize this possibility, only qualified electrical technicians familiar with electrical hazards
should perform these checkout procedures. Safety glasses should be worn by such personnel, and
instruments used for voltage measurement should be designed for the purpose and should be in
good mechanical and working order.
If there is application or installation information that is not clear or not covered in this manual, please
contact us at: MTECH Technical Support at +972-4-6000610 or by email:
2.1 Agency Requirements
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
The PANEL is listed by ETL TESTING LABORATORIES to UL 864 9th edition as a FACP control
unit for use in NFPA 72 systems.
Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer to the
specific section of the manual for additional requirements.
All field wiring must be installed in accordance with NFPA 70 National Electric Code.
Use UL listed smoke detectors and notification appliances compatible with the PANEL

12
from those specified in the Appendix to this manual.
A full system checkout must be performed every time the panel is programmed.
The MA-1000 range of analog fire alarm control panels are designed in accordance UL864 9th Fire
Detection and Fire Alarm systems Control and Indicating Equipment.
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864,
9th Edition has not been evaluated. Such operation requires the approval of the local Authority
Having Jurisdiction (AHJ).
2.2 Calculating Current Draw and Standby Battery
This section is to determine the current draw and standby battery needs for your installation.
Maximum Battery Standby Load
It is recommended to use the battery of Diamec Company (www.diamec.com). The required nominal
batteries capacity as versus standby current system is shown in the table bellow (1-1). For chosen
battery order the compatible wire set model
Make sure that for the system configuration the standby is not more than 0,270 A for 8Ah battery
and 0.4287 A for 12 Ah battery.
Table 1-1
L W H 24 h 60 h
DMU12-7 7 151 65 101
0.2393 -- 06.014
DMU12-12 12 151 99 101
0.4287 -- 06.015
Battery wires
model
Battery
Model
Capacity,
Ah
Size , mm
Max.permissible System
Standby current during

13
2.3 Calculating Maximum Current Draw and Battery Backup Requirements
This section will assist you in determining the maximum system current draw and standby battery
needs for your installation. Follow the steps below to determine the current draw and standby
battery requirements. Appendix B—MA-1000 Current Draw/Battery Backup lists the standby and
alarm current draw for the panel. Total standby and alarm Current is determined by multiplying the
quantity of items by its current draw. To quickly determine maximum system current draw, perform
the following computations:
Download the “Backup Calculation.xls” file from www..biz
Fill in the quantities of conventional detectors, addressable detectors and devices.
Fill in the quantities and current draw of the Notification Appliances or auxiliary-powered devices for
each output from the manual for each specific device.
Fill in the total quantities of detectors and modules. The detectors and modules total alarm current
is determinate by estimation method, under the hypothesis that 5% LED will be ON.
The required battery capacity is determined according to equation
Cb >= (Isb* Tsb + Ia*Ta)*1.1
Where:
Cb- required battery capacity, Ah
Isb –standby current, A
Tsb –supervisory time, 24 or 60 hours
Ia –alarm current, A
Ta –alrm time, 5 min (0.0833 hours)
1.1 –safety factor.
Make sure the total alarm current you calculated (including current for the panel itself) does not
exceed 4.5 Amps. This is the maximum alarm current allowable.
Calculation example is shown in the following table (1-2).

14
MA-1000

15
2.4 Mounting the Enclosure
Install the Enclosure as follows:
1. Carefully unpack the system components and inspect for any damage due to shipping.
2. Mount the enclosure in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The location should be readily accessible with sufficient room for easy installation and
maintenance.
3. Mount by using the two mounting holes located in the upper back of the cabinet. After the panel
has been properly located using the mounting holes, the panel can be secured.
4. Complete all conduit connections to the cabinet. Use the knockouts provided in the top and the
sides.
Wire must NOT enter the bottom of the cabinet, since this area is intended for batteries only.

16
Peripheral Devices

17
2.4.1 Connecting the AC Power
WARNING!
To reduce the risk of electrical shock, make sure that all power has been turned off or disconnected
prior to attempting to connect power to the Power Supply.
Apply the AC Power BEFORE connecting the batteries to the Panel!
Provide the Fire Alarm Control Panel with a dedicated AC Circuit rated 15 Amps.
Refer to Figure 2.1 for wiring diagram.
1. Enter Power Cable into Cabinet via left side knock out hole.
2. Attach the brown (live) wire from the source to terminal “Line” (USA use color black wire).
3. Attach the blue (neutral) wire from the source to the “Neutral” terminal (USA use color white wire).
4. Attach the ground wire from the source to the “GD” terminal block (USA use color green wire).
Figure 2.1
P1
Battery
Fault
GND wire
NEUTRAL
LIVE
Normal
+ -
GND
Factory fitted
NO NOT REMOVE
The GND cable must
be connected to this
point + -

18
2.4.2 Battery Installation
The batteries are placed at the bottom of the enclosure by removing the four nuts holding the battery
plate. The MA-1000 is fully protected if the batteries are connected in the opposite direction the
battery fault yellow led will show steady in such a condition. When green battery LED is in a steady
condition to shows that the battery connection is normal.

19
2.4.3 Output (NAC) Installation
Each NAC can be programmed to operate for a limited amount of time or continuously, stay on
during operation or operate using one of several on/off patterns as well as start operation due to
various conditions happening.
Table of contents