GST GST-FT40N User manual

GST-FT40N Fire Telephone Panel
Installation and Operation Manual

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page II
CONTENTS
1GENERAL......................................................................................................................................1
2TECHNICALSPECIFICATIONS...............................................................................................1
3PANEL INSTRUCTION................................................................................................................2
3.1 APPEARANCE AND STRUCTURE.................................................................................................2
3.2 THE FRONT SURFACE.................................................................................................................2
3.3 THE KEYS.................................................................................................................................3
3.4 INDICATORS ..............................................................................................................................3
3.5 DIGITRON DISPLAY...................................................................................................................4
4FIRE TELEPHONE SYSTEM DESIGN.....................................................................................4
4.1 STAND ALONE FIRE TELEPHONE SYSTEM .................................................................................4
4.2 NETWORKED FIRE TELEPHONE SYSTEM ...................................................................................4
5MOUNTING & COMMISSION...................................................................................................5
5.1 INITIAL CHECK .........................................................................................................................5
5.2 WIRING REQUIREMENT.............................................................................................................5
5.3 INSTALLING DIMENSION............................................................................................................5
5.4 TERMINALS ON THE PANEL........................................................................................................6
5.5 SYSTEM COMMISSIONING.........................................................................................................7
Set panel address..........................................................................................................................7
Register the Network Panels.......................................................................................................7
Test Functions................................................................................................................................7
6USER GUIDE.................................................................................................................................7
6.1 PANEL CALL HANDSET .............................................................................................................7
6.2 HANDSET CALL PANEL .............................................................................................................8
6.3 CALL PANELS IN NETWORK ......................................................................................................8
6.4 PANEL TO PANEL CALL .............................................................................................................8
6.5 INQUIRE ABOUT CONVERSATION RECORD..................................................................................8
7TROUBLESHOOTING ................................................................................................................8
7.1 ZONE FAULT .............................................................................................................................8
7.2 NETWORK FAULT......................................................................................................................9

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 1
1 General
GST-FT40N fire telephone panel is specialized for emergency communication, builds up
convenient and prompt 2-way communication in case of fire and other abnormal conditions.
It is an indispensable device in fire protection system. The panel has features as below:
Standard 4U structure, rack mount installation
24VDC power supply
Receiving and calling out with fire telephone handsets
Networkable fire telephone panels achieve internal communication
Call from handset will be transferred to networked fire telephone panels automatically
after not answered by the dedicated panel
The handset zones are fully monitored for fault of short circuit and open circuit. Panel
will show the fault by sound and indicator.
Failure of one zone will not effect on other zones
The network communication is monitored. When sub-panel fails to communicate with
the main panel, the main panel will get the failure message and broadcast to other
networked sub-panels, both main panel and sub-panels will indicate by sound and light
indication. When the fault happens on main panel, all sub-panels will show the fault
message, and meanwhile the network call will be inhibited.
Record: The conversation between fire telephone panel and Handset or other fire
telephone panel can be recorded up to 15 minutes. The new content will cover the old
one when the storage is full.
2 Technical Specifications
Operation Voltage 24VDC±10%
Standby Current 0.3A
Maximum Current 1.2A
Frequency Range 300~3400Hz
Crosstalk <-60dB
Transmission Loss <5dB
Environment Temperature -5~40°C
Relative Humidity 45%~95%
Dimension 482.5mm×177mm×225mm
Gross Weight 5.3 kg
Network Capacity 8 panels
Panel Capacity 40 zones
Zone Capacity 5 handsets
End of Line Resistor 10kΩ±0.5KΩ

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 2
Notes: words using within this file
Fire Telephone Panel (Panel): Installed in fire control center, the device can
communicate with field terminals, such as GST-FT40N.
Handset: Field device, which can communicate with fire control center, such as
P-9911(F) and P-9911(M).
Main panel: The No.1 panel in the fire telephone panel network
Sub-panel: Panels other than No.1 in the fire telephone panel network
3 Panel Instruction
3.1 Appearance and Structure
GST-FT40N fire telephone panel is rack mount type, the appearance is shown in Fig.3-1
GST-FT40N FIRE TELEPHONE PANEL
Fig.3-1
3.2 The front surface

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 3
Fig. 3-2
3.3 The Keys
Key Description
“Mute” Stop the alarm sound caused by fault
“Network Call” Answer or start network call
Zone 1-40 Answer, call or hang up the corresponding zone.
3.4 Indicators
Indicator Description
“Call” LED, 1-40 Red, indicating the conversation status between panel and
corresponding zone.
¾Flashing: in the process of connection
¾On: under conversation
¾Off: no conversation
“Ring In” LED Red, fast flash when there is call in from network or zone
“Fault” LED, 1-40 Yellow, lit on when corresponding zone in Fault condition
“Network Fault” LED Yellow, lit on when there is network fault
“Power” LED Green, lit based on usual power supply
“Mute” Red, lit when panel sound alarm silenced

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 4
3.5 Digitron Display
State Example Description
Network Free
On the main panel, the first digit
indicates the quantity of panels in
the network, the last digit indicates
its network address
On sub-panel, only the last digit will
show its network address
Network Call
The first digit indicates the address
of the calling panel. The C at the
last digit means Calling.
Network
Conversation
The sample at the left shows the
conversation state between No.1
panel and No.2 panel. The others
will show “BUSY”
Network
Failure
The first digit indicates the address
of failed panel. The E means Error.
4 Fire Telephone System Design
4.1 Stand Alone Fire Telephone System
Fig. 4-1 shows a standalone fire telephone system. The panel can connect maximum 40
zones with each zone maximum 5 handsets.
Fig. 4-1
4.2 Networked Fire Telephone System
The system consists of a group of panels as many as 8. The panel with the address 1 is the
main panel and the rests are sub-panels. Please refer to commission section for setting up
addresses.

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 5
Fig. 4-2
5 Mounting & Commission
5.1 Initial Check
Check the appearance of the panel after open the box. Then power on and check working
state.
5.2 Wiring Requirement
¾Cross-section area of the power cable not less than 1.5mm2
¾Twisted-pair cable connecting panel and handset with SA not less than 1.0 mm2
¾Twisted-pair cable for the network with SA not less than 1.0 mm2
¾The cable selection must comply with local code
Note: the impedance of single line not more than 20Ω
5.3 Installing dimension
Installing dimension:482.5mm*177mm*225mm

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 6
5.4 Terminals on the panel
Fig. 5-1
Power (+24, GND): 24VDC power in, polarized
E: GND
Network (+, -): Network, polarized
Audio Output:Audio signal output
Zn+, Zn-: Zone Terminals, connecting with handsets (a 10KΩ±0.5KΩresistor is
required to the last point of each zone).

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 7
5.5 System Commissioning
Please Make Sure the Correct Wiring before Commissioning.
Set panel address
¾For standalone fire telephone system, the address can be assigned 1 or keep the
default setting.
¾There must be one panel assigned 1 in the network fire telephone system and register
other panels.
¾Addressing step:Press a key between 1-8 key of front surface, then power on, press
the key over 2s, the number will become the network address of the panel. The
address will not be lost when the panel is switched off. The address will not be changed
unless 1-8 key is pressed when the panel is powered on.
Note: The panel addresses can not be repeated in same network.
Register the Network Panels
After assigning the addresses, power on the sub-panels first. Then power on the main panel.
The main panel will register all networked sub-panels automatically. Subsequently, the first
digit of the digitron will show the number of networked panels (including the main panel).
Check whether all panels have been registered according to the shown number. If no
consistency, check the wiring and repeat the above-mentioned process.
The registration information is saved in non-volatile memory, will not loss on power off. The
registration should be carried out again in case adding or removing network panels.
Not necessary for registration on sub-panel.
Test Functions
Test the other functions according to Operation Manual after commissioning.
6 User Guide
6.1 Panel Call Handset
Press a key of zone 1 to 40, the corresponded zone will be called with “Call” LED
slow-flashing. The conversation will be set when handset picked-up, with “Call” LED lit
showing status. During the conversation, press the key again will stop the call. The “call”
LED won’t go out until hanging up the handset. If the handset is hung up first, the
conversation will stop immediately with “Call” goes out.

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 8
The panel can make call to handsets in other zones when a conversation is underway.
6.2 Handset Call Panel
Once the handset is picked up without being called, the call will go to the panel. The panel
will ring with “Call” and “Ring In” LED fast-flashing. Press the relative key and enter into
conversation with “Call” being on, “Ring In” goes out. Meanwhile, if there are other zones
calling panel, “Ring In” will keep fast-flashing. Hang-up the handset or press the relative key
on the panel will stop the conversation.
6.3 Call Panels in Network
If the handset call is not answered by the panel within 12s, and the network is available, the
call will be transferred to other networked panels. Press “Network Call” and start the
conversation. Stop the conversation by handset hanging up or “Network Call” repressed.
6.4 Panel to Panel Call
When network is available, press “Network Call” will send the call to entire network with the
LED indicator fast-flashing. Meanwhile, the digitron on other networked panels will show by
flashing “X — —C” (X- The calling panel), the “Ring In” and “Network Call” LED will fast
flash with ringing sound.
Press “Network Call” button and then start the conversation. The digitron of the panels not attending
conversation will show “BUSY” and the ring tone stops. Panel in conversation will show the
address of the other one. Either part can stop the conversation by pressing “Network Call”.
6.5 Inquire about conversation record
Press “PLAY” key of the electric recorder, then the record will be played. Press
“FORWARD” and “REWIND” to switch the content rapidly and press “■” to stop.
Electric recorder will start or stop recording automatically along with the conversation, The
new content will cover the old one when the storage is full.
7 Troubleshooting
7.1 Zone Fault
The zone fault shows an open or short circuit between panel and handsets, or the End of
Line Resistor not connected. Check the cable by multi-meter, whether the resistance is
roughly 10kΩ.

GST-FT40N
Fire Telephone Panel The Intelligent Solution
Page 9
7.2 Network Fault
The panel shows network fault when there is any of the panels powered off or network cable
fault. Check the malfunction panel and wiring.

GST China
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
Fax: +86 (0) 335 8508942
www.gst.com.cn
GST UK
Global System Technology PLC
Lion Court, Staunton Harold Hall,
Melbourne Road, Ashby de la Zouch,
Leicestershire,
England LE65 1RT
Tel: +44 1283 225 478
Fax: +44 1283 220 690
www.gst.uk.com
GST Dubai
Global System Technology PLC
PO Box 17998 Unit ZA04 JEBEL ALI Free Zone,
Dubai, UAE
Tel: +971 (0) 4 8833050
Fax: +971 (0) 4 8833053
www.gst.uk.com