MacroAir Technologies Controller 30 User manual

Operation Manual
Controller 30


Table of Contents
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
1
Introduction
Network Installation
Configuration and Operation
Information
Caution & Safety, Electrical Guidelines..........................2
Hazard of Electrical Shock, Installation and Service,
Key Safety Systems, Electrical Guidelines ......................3
Mounting Guidelines......................................................4
Clearance Guidelines, Fan Placement and Spacing,
Fan Network Ordering....................................................5
Controller Dimensions....................................................6
Controller Components..................................................7
Network Wiring Requirements ......................................8
Network Wiring Configurations .....................................9
Network Excess Cable...................................................10
Controller Wiring Instructions......................................11
AVD 370 RJ45 Wiring Instructions................................12
T-Splice Connection Method for ADV 370 Fans...........14
Fan Wiring Instructions ................................................16
Mixed Network Wiring Instructions.............................17
AirEffect Sensor ...........................................................18
Controller Setup ...........................................................19
Controller Home Screen...............................................20
Fan Control Screen .......................................................21
Fan Configure Screen ...................................................22
Settings Screen .............................................................23
Advanced Settings Screen ............................................24
Groups Screen ..............................................................25
Schedules Screen..........................................................26
Fine Tune Screen ..........................................................27
Remote Operation....................................................28
Technical Support.....................................................29

2 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Caution and Safety
This appliance can be used by children aged from eight (8) years and above and persons with
reduced physical, sensory, or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in a safe way and
understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
⚠ATTENTION: Safety. READ AND SAVE THE ENTIRE MANUAL BEFORE OPERATING THE FAN.
Ensure that all safety procedures and instructions are followed during the installation, operation
and servicing of the fan. Failure to apply these safety practices could result in death or serious
injury. If you do not understand the instructions, please call our Technical department for
guidance.
⚠CAUTION:Non-Compliance. The fan installation should follow the recommendations
outlined in this manual. MacroAir is not responsible for any injury or damage to persons or
property because of ‘not complying’with the recommendations outlined in the manual.
Electrical Guidelines
⚠WARNING: Electrical Damage. Improper electrical installation can cause damage to the fan
and interfere with other electronic equipment. In addition to standard electrical safety
considerations, please observe the following:
•MacroAir Cables. The wiring from the control panel to the fan MUST be MacroAir
supplied shielded cable. CAT5e to be MacroAir supplied twisted, stranded, and shielded
or greater.
•Electrical Interference. Separate incoming power and motor control cables by a
minimum of six (6) inches.
•Individual Fan Wiring. Run wiring for each fan separately.
•Multiple Fans. Do not attempt to control multiple fans from one (1) fan control panel.
•ALWAYS GROUND PROPERLY. Connect the supplied cable glands to each end of the
motor cable and tighten them securely at both the fan motor and control panel ends.
Connect the ground bar in the control panel to ground at the main breaker and test.
•Read. Please refer to the installation instructions for more information.
⚠ATTENTION: Qualified Technicians. All fan controls should only be installed by qualified
technicians familiar with the requirements of the National Electrical Code (NEC) and local codes.
Refer to appropriate portions of this manual for other important requirements. Failure to follow
these guidelines will void the manufacturer’s warranty.

3 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Electrical Guidelines cont.
⚠ATTENTION: Factory Configured. All electrical controls are configured at the factory and are
ready to use. No user adjustments are available. Follow the included wiring schematics and
installation instructions when installing this device to ensure proper operation. Do not make any
changes to any part of the motor control panel without first consulting MacroAir.
⚠ATTENTION: Code Compliance. Installation is to be in accordance with the NEC, ANDSI/NFPA
70-1999 and local codes.
Hazard of Electrical Shock, Explosion, or Arc Flash:
⚠ATTENTION: Read. Read and understand this manual before installing or operating a fan unit.
Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
⚠ATTENTION: Code Compliance. The user is responsible for compliance with all international
and National Electrical Code requirements with respect to grounding of all equipment.
⚠WARNING: Do Not Touch. Many of the parts of this unit operate at line voltage. DO NOT
TOUCH.
⚠WARNING: Covers. Install all covers before applying power or starting and stopping the unit.
Installation and Service
⚠WARNING: Damage. Do not operate or install any fans or fan accessories that appear to be
damaged.
⚠WARNING: Death and Injury. Failure to follow this instruction can result in death, serious
injury, or equipment damage.
⚠WARNING: Disconnect Power. If the fan does not operate properly using the procedures in
this manual, BE CERTAIN TO REMOVE ALL POWER TO THE UNIT and contact our Technical
Department for further assistance.
⚠CAUTION: Moving Parts. Keep all body parts clear of moving parts at all times.
⚠ATTENTION: Qualified Technicians. All electrical troubleshooting and repair must be done by
a qualified technician and meet all applicable codes.
Key Safety Systems
⚠ATTENTION: Safety. MacroAir fans are engineered with key safety features to prevent pieces
of the fan from falling in the unlikely event of a catastrophic failure. Used together, these
systems and devices provide comprehensive protection to people, equipment, and property.

4 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Key Safety Systems, cont.
⚠WARNING: Safety Cable and Guy Wires. Install safety cable on EVERY fan. Install guy wires
on every fan, unless otherwise specified. Properly installing the guy wires will keep the fan stable
in case of earthquake or in “outdoor” installations where high wind conditions may occur. The
safety cable, if installed per MacroAir specifications, will prevent the fan from falling in the
unlikely event that the mounting system should fail.
⚠WARNING: Safety Cable. A MacroAir fan should never be run without a properly installed
safety cable, which is supplied with every fan along with all required hardware. You must install
a safety cable for the warranty to be in effect.
⚠WARNING: Blade Safety Links. Install the complete set of extended blade safety links, which
connect each blade to the adjacent blades and reinforce the area between the mounting holes.
This is an important precautionary measure that will help prevent a blade from falling should
one break off at the hub for any reason.
⚠ATTENTION: Mark the Floor to Alert Personnel. When mounting a fan in an area where
materials may be elevated into its path, MacroAir recommends marking or painting the floor
with a large crosshatched circle to alert personnel of the overhead location of the fans.
Mounting Guidelines
⚠WARNING: Weight Considerations. We recommend that a building structure be capable of
holding approximately twice the stated hanging weight of the fan. If there is some doubt of this,
a professional contractor or architect should perform a thorough evaluation of the building prior
to purchasing the fans. MacroAir provides guidelines for mounting fans, however it is the sole
responsibility of the building owner and installer to ensure the safety of the mounting system,
that the building structure is sound, and that the installation complies with all federal, state, and
local codes.
⚠WARNING: Torque. The maximum torque (twisting force) that must be handled by the
mounting system, including the building structure, occurs at fan startup. For a 24-foot fan, the
maximum potential starting torque is 137 Ft-Lbs. When standard electrical controls are installed,
the fan will never begin to approach this maximum because the standard variable-speed control
system uses the soft-start fail, or when a fan is installed as a single-speed model without the
variable speed control system (rare), full torque might be applied to the mounting system, so it
is important that it be adequate to withstand 137 Ft-Lbs. torque.
⚠ATTENTION: Check Federal, State, and Local Codes. Check all relevant codes to make sure
that all product certifications, product listings, and building regulations are met. Code
compliance is the responsibility of the installer.
⚠WARNING: Welding. DO NOT attach the fan or fan mounting components to the building
structure by welding that component to the structure. DO NOT cement the fan to the structure.

5 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Clearance Guidelines
⚠ATTENTION: Sprinkler Systems and Fan Placement. In any installation where fire sprinklers
are in place, do not interfere with their correct operation. Fans should be located no less than
three (3) feet below a sprinkler and placed central to each sprinkler quadrant.
⚠ATTENTION: Sprinkler Systems and Code Compliance. Prior to installing fans, review all
codes applicable to sprinkler systems and fans to ensure code compliance. Refer to the wiring
diagrams packaged inside the control panel for proper installation. If further advice is needed,
you may contact our support staff, however it is your sole responsibility to see that the
installation is completed to code and correct.
General Information on Fan Placement and Spacing
⚠ATTENTION: Strobe and Performance. If possible, avoid mounting fans directly below lights
or skylights to avoid any strobe effect caused by moving blades. A large fan, 20-24 feet in
diameter, performs best at 20 to 30 feet above the floor, but acceptable performance has been
demonstrated as low as 10 feet and as high as 50 feet.
⚠WARNING: Mezzanine Placement. If the building has a mezzanine, fans should be mounted
so a person cannot reach a fan in any way from the upper level/deck. Make certain that fans are
positioned so that blade tips are at least three (3) feet away from any area where a person may
be able to extend outward to reach them.
⚠WARNING: Oscillating Movement. If unusual oscillating movement is observed, immediately
stop using the ceiling fan and contact the manufacturer, its service agent or suitably qualified
persons.
REFER TO FAN INSTALLATION MANUAL(S) FOR FURTHER MAINTENANCE INFORMATION.
Fan Network Ordering
Type of controller: Controller 30, which can network up to 30 fans.
MacroAir customizes fans to operate in a network by:
•Addressing the fans.
•Providing bean crimps for T-splices (AVD 370).
•Supplying an additional 15ft [4.57m] piece of CAT5e (AVD 370).
•Modifying the panel enclosure (AVD3, 550, 780, Y and X Series Fans).
•Modifying the wiring on the VFD (AVD3, 550, 780, Y and X Series Fans).
Note: If you did not order your fans for a network, please contact Technical Support for
assistance with networking your fans. Also, when installing new fans in an existing mixed
network, contact Technical Support.

6 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Controller Dimensions

7 Introduction
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Controller Components
Note: The glands for the fire alarm and CAT5e to local network are plugged from the factory in
order to maintain the screen’s IP 66 rating when not used. If you are utilizing the fire alarm
option and/or remote operation, remove the plugs from any gland you will be using.

8 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Network Wiring Requirements:
•Use stranded CAT5e or higher shielded cable.
•Minimum 24AWH (0.5mm) cross section.
•Ground the shielding and drain wire at only one point of the cable run.
•DO NOT TERMINATE THE BROWN/WHITE WIRE IN AVD NETWORKS. Running the
brown/ white wire throughout a network can cause communication issues and may void
the warranty of the fans.
•Route wires as far away as possible from high voltage AC cables, fluorescent lights, arc
welders, and other equipment that transmits EMI (electromagnetic interference).
•Do not run CAT5e in conduit with high voltage AC cables.
•Do not exceed 4000ft [1219m] of CAT5e between the screen and the last fan in the
network.
•A repeater is required for every five (5) AVD 370 fans.
•Repeaters need to be evenly placed throughout the network, which will not necessarily
be at every 5th fan. Refer to the below wiring diagrams for further information.
Daisy Chain
Network MacroAir fans must be connected in one single line, referred to in this document as a
“daisy chain”. The characteristics of a proper daisy chain are: one beginning (Controller 30) and
one end (last fan or control panel).
If the fans are not connected in
one line/chain, there will be a
degradation of the
communication signal and the
network may not function as
intended (fans in the network
may not operate).
Each fan has a unique address,
which is noted on a sticker on
the fan itself (AVD 370) or
control panel (AVD3, 550, 780,
Y and X Series Fans). It is
important to mount the fans in
the correct order.

9 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Network Wiring Configurations
Improper Wiring Configuration
End of Line x3 End of Line x8
Proper Wiring Configuration
ONE End of Line

10 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Network Wiring Configurations cont.
Excess Cable at Connection Point
With noise being emitted throughout a typical industrial/commercial environment, extra cable
should not be coiled up as the coil itself will create noise/interference in the communication
signal. There should be no more than 2ft [0.6m] of excess cable at each connection point.
If more than 2ft [0.6m] of cable is needed for future relocation of the fan, run the cable up
toward the ceiling and back down in a horseshoe shape.
ALWAYS AVOID SHARP BENDS OF THE CABLE.

11 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Controller Wiring Instructions
⚠WARNING: Power to be off. Prior to following the steps below, ensure all power to the
touchscreen is off.
1. Run the included power supply cable through the gland on the bottom of the network
controller and plug the terminal block in per the below diagram.
2.
3. Run one end of CAT5e through the gland on the bottom of the network controller and wire
the blue and blue/white wires to the touchscreen per the diagram below. Do not remove
any factory wiring.
4.
5. If a fire alarm is being used, a normally closed relay can be tied into the orange and orange/
white wire coming from the fans. If a fire alarm is not being used, the orange pair needs to
be twisted together.
6. If you are utilizing the optional remote operation feature (pg 28), run a separate CAT5e from
your router to the LAN A port on the back of the screen. The CAT5e will need an RJ45 male
end terminated per the pinout below.
Touchscreen Wiring Diagram
•For AVD 370 fans with RJ45 ports refer to page (pg 12).
•
•For all other fans (AVD3, 550, 780, Y and X Series Fans) refer to page (pg 16).
•

12 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
AVD 370 RJ45 Wiring Instructions
AVD 370 fans with RJ45 ports on the board are wired in T-splices. Each T-splice will consist of 3
CAT5e cables. A properly wired T-splice network is shown below:
Typical T-Splice of CAT5e Network Cable

13 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
AVD 370 RJ45 Wiring Instructions cont.
A repeater is required for every 5 fans, which will be spliced evenly in the CAT5e network
between fans. Repeaters are not required on networks with 4 fans or less.
Repeater Wiring Diagram

14 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
T-Splice Connection Method for AVD 370 Fans
1. Take the incoming CAT5e from the
network, the 15ft [4.57m] CAT5e whip
from the fan, and the CAT5e going to
the rest of the network. Give some slack
(no more than 2ft / 0.6m) on each
CAT5e to strip the wires and splice them
together. Run the slack up towards the
ceiling and back down in a horseshoe
shape.
DO NOT roll the excess slack into a circle or coil because this creates a place for the
network to pick up noise on the lines.
2. Strip jacketing off the three CAT5e
cables and separate each color wire
leaving approximately 2in [5cm] of each
wire exposed including the drain/shield
wire.
3. Strip approximately 1/2in [1.3 cm] off
each color wire leaving the bare copper
exposed.
4. Twist the 3 wires of same color from
each CAT5e together.

15 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
T-Splice Connection Method for AVD 370 Fans cont.
5. Place a gel filled bean crimp onto the end
of the 3 wires and use a small crimper or
pliers to crimp the bean tight on the
wires.
6. Double check that the 3 drain wire/bare
wires are also crimped together as this is
what continues the shielding throughout
the network. The shielding and drain wire
MUST be connected to Earth Ground at
only one point of the cable run.
7. Repeat steps 3-5 for all the wires EXCEPT
the Brown/White wire. The Brown/White
wire is only needed for wiring in a
repeater.
8. Once all the wires are crimped, carefully
twist the wires up. Then fold them back
and tape them up with electrical tape to
clean up your wiring.

16 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Fan Wiring Instructions
AVD3, 550, 780, Y and X Series fans are wired in a daisy chain with one CAT5e from the
touchscreen/previous fan into an RJ45 port on the control panel, and one CAT5e going to the
next fan from the second RJ45 port on the panel. The internal panel wiring does not need to be
modified for communications.
A properly wired daisy chain network will have the CAT5e network ran per the below illustration.
Control Panel Schematic: Refer to documentation included in the Fan Installation Manual.

17 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Mixed Network Wiring Instructions
Networks utilizing different types of connections, will wire each fan according to the preceding
wiring instructions in the manual. Below is an example of wiring for a mixed network:
When networking AVD 370 fans, you will need a repeater for every 5 fans. For example, if you
have twelve fans, but 7 are Y or X Series fans and 5 are AVD 370 fans, you will only need one
repeater.
Note: When installing new fans in an existing mixed network, contact Technical Support for
assistance with networking your fans.

18 Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
AirEffect Sensor
⚠ATTENTION: AirEffect Option. If you ordered the optional AirEffect feature, refer to the
Operation Manual (MacroAir #90-30017-00) accompanying the AirEffect Sensor.
Table of contents