6 7
L N LN L N L N L N L N L N L N L N L N L N L N L N L N
Power Pump R1 R2 R3 R4 R5 R6 R7 R8 G1 G2 W1 W2 W3 W4 W5 W6 W7 W8 Cooling
COM NOCOM NO °
C°
C°
C°
C°
C°
C°
C°
CCOM NO
AC
Cooling changeover port
W1-W8:connect to thermostat
lowvoltage, regardless of null
lineandfire line.W1 must
connect with master thermostat
Water pump(Current<5A)
Power supply(100-240VAC 10A)
L:Fire Line N:Null line : Earth line
R1-R8:Connected electric heating actuator
(the total current<5A)
G1、G2:Passive linkage
(can be linked to boiler, heat pump host, mixed water device)
(Current<5A)
Wiring diagram
Wiring control centre H64-CC
Precautions
①W1-W8: Connected to the thermostat, low voltage, regardless of null line and fire line,
W1 must be connected to the master thermostat, W1 corresponds to an area.
② R1-R8: Connected electric heating actuator, R1 corresponds to W1, R2 corresponds to W2, and so on,
R1-R4 can be connected to two electric heating actuators respectively, the total current does not exceed 5A.
15
R1-R8: Aansluiting actuatoren (230VA)
(Totale stroom <5A)
Circulatiepomp stroom<5A
Stroomvoorziening (100-240VAC 10A)
L = Line N = Neutraal = Aarde
W1-W8: aansluiten op de laagspan-
ningsthermostaat, zonder polariteit.
W1 moet worden aangesloten op de
masterthermostaat.
Poort overschakelen naar koelmodus
G1, G2: passieve verbinding (potenciaalvrij contact)
Aansluiting voor ketel, warmtepomp of mengsysteem (Max. 5Amp.)
5. Aansluitschema
Aansluiting thermostaten W1-W8: Aansluiting thermostaten (Masterthermostaat altijd op W1).
Aansluiting Actatoren (230VA) R1-R8: R1 = W1, R2 = W2 etc....
Groep R1-R4: Zijn dubbel uitgevoerd en daar kunnen 8 actuatoren (4 per ingang) aangesloten worden.
Groep R5- R8: Maximaal 4 actuatoren per ingang.
Totaal: R1-R4 (4x8) en R5-R8 (4x4) = 48 actuatoren.
LET OP: De totale stroomsterkte mag nooit meer dan 5 Ampère bedragen.
Montage & installatie H64-CC Regelunit