Mandik OID User manual


2
……………………………………………………..........................................
………………………………………………………………...........................
…………………………………………................................
……………..........................
……………………………………………........................
Uživatelská korekce teploty…………………………......................................
5
Nastavení časového programu………………………….................................
5
Nastavení základních požadovaných teplot a reálného času........................
5
Výchozí nastavené hodnoty regulátoru………………………........................
6
…………………………………………………….........................
Svorky………………………………………………………...............................
7
Přepínače…………………………………………………….............................
7
………………………………………………………………….........................
……………………………………………………………….........................
……………………………………………………………….…......................
…………………………………………..……....................
………………………………………………………............................
……………………………………………………………….................
………………………………………………………..........................

3
OID je systém pro řízení dvoustupňových infrazářičů Helios. Skládá se z ovládací skříňky OI a
regulátoru UC301. Ovládací skříňka se vyrábí ve verzi pro jeden až šest zářičů, počet ovládaných
zářičů je dán číslem v typu OID, OID 1 až OID 6.
10/I hlavní vypínač regulace.
Poloha „I“ centrálně zapíná ovládání OID
Poloha „0“ centrálně vypíná ovládání OID
2
třípolohový přepínač pro každý zářič
Polohy přepínače:
●v tomto případě je zářič ručně zapnut, bez
ohledu na regulátor MANDÍK UC301
● (střední poloha) v tomto případě je konkrén
zářič ručně vypnut
●v tomto případě je infrazářič řízen automaticky
regulátorem MANDÍK UC301 viz níže
3.
kontrolka sítě jednotlivých zářičů
4.
kontrolka chodu jednotlivých zářičů
1. Zapneme hlavní elektrický vypínač „ “ do polohy „ I“.
2. Přepínače ovládání jednotlivých zářičů „ - STOP - “ přepněte do polohy ručně „ “ nebo
automat „ “ rozsvítí se zelená kontrolka el. síť „ “ na ovládací skříni a zelená kontrolka na spodku
hořákové skříně (počet přepínačů se bude lišit s ohledem na provedeníovládání - OID 1 až OID 6.
OID 1 ovládá 1ks zářiče Helios, OID 6 ovládá 6ks zářičů Helios)
3. Po proběhnutí odvětrávacího času (cca 50 s) se infrazářič uvede do chodu a rozsvítí se zelená
kontrolka chodu na ovládací skříni „ “ a oranžová kontrolka na spodku hořákové skříně.
4. Pokud nedojde k zapálení hořáku (nerozsvítí se zelená kontrolka chodu) opakuje se cyklus ještě
dvakrát. Pokud nezapálí ani napotřetí, rozsvítí se červená kontrolka na hořákové skříni signalizující
poruchu. Pro odblokování je třeba provést odpojení a nové připojení elektrického napájení infrazářiče
(přepínač ovladače „ -STOP- “ přepněte do polohy „STOP“ a zpět do polohy „ “ nebo „ “.
Pokud i po několikanásobném zapalovacím cyklu se infrazářič nepodaří uvést do provozu, volejte
servisní organizaci.
5. Výkon dvoustupňových infrazářičů se v případě ovládání OID řídí automaticky na základě povelu
regulátoru MANDÍK UC301.
6. Teplotní čidlo – standardně je teplotní čidlo součástí regulátoru UC301. Dle potřeby lze k regulátoru
připojit teplotní čidlo ASTF Pt 1000 pro snímání sálavé teploty. Podrobný postup pro změnu čidla
naleznete níže v návodu regulátoru.

4
1. Přepínač „ - STOP - “ přepnete do polohy „STOP“.
2. Při dlouhodobém odstavení z provozu je vhodné zavřít plynový ventil před zářičem.
UC301 je komunikativní dvoustupňový regulátor plynových zářičů s výstupy SSR. Může buď pracovat
autonomně, nebo být připojen na primární regulátor (MiniPLC nebo SoftPLC), vizualizaci (RcWare
Vision nebo jiný systém SCADA) nebo na webové rozhraní UCWEB.
●Systémy se sálavým vytápěním – výrobní haly, sklady
●Systémy s libovolným zdrojem tepla, řízené dvoustupňově
Regulátor snímá teplotu v místnosti pomocí vestavěného čidla nebo pomocí externího čidla Pt1000,
korekci teploty otočným knoflíkem a požadovaný provozní stav, který se nastavuje stiskem tlačítka nebo
v menu. Rozsah měřených teplot externího čidla je -20 až +50 °C. Nasnímané a zadané hodnoty jsou
zpracovány v regulačním algoritmu PI, na jehož výstupu je dvoustupňová sekvence pro řízení dvou
dvoustavových výstupů, které ovládají jednotlivé stupně plynových zářičů. Ze systému mohou být čteny
další hodnoty (korekce, provozní stav zadaný z centrály apod.), které se zobrazují na přehledném LCD
displeji.

5
Externí čidlo se používá v případech, kdy regulátor je instalován na místě, kde není možné korektně
měřit teplotu. Použijte analogové čidlo Pt1000 v provedení do místnosti, do průmyslu (s vyšší odolnos-
tí) nebo venkovním (vyšší krytí). Pokud není čidlo připojeno (svorky rozpojeny), automaticky se bere
teplota z interního čidla. Parametry regulace, hystereze, časové programy atd. se nastavují pomocí
konfiguračního softwaru ModComTool, který je zdarma ke stažení na webu www.domat.cz. Pokud je
rozdíl mezi nastavenou a žádanou teplotou velký (např. více než 2 K), jsou oba dva výstupy sepnuté
a vytápění pracuje s výkonem 100%. Pokud se teplota přiblíží na 1 K k požadované, DO2 rozepíná.
Vytápění pak dotápí 50% výkonem a po natopení prostoru na požadovanou teplotu rozepne i DO1
kontakt a regulace čeká na pokles teploty. Regulátor obsahuje hodiny reálného času s týdenním
programem (6 událostí denně). Přepíná se mezi stavy Komfort, Útlum a Vypnuto. Každý stav má svou
požadovanou hodnotu pro topení, hodnoty jsou nastavitelné v menu regulátoru nebo po sběrnici. Na
displeji se střídá zobrazení aktuálního času a měřené teploty.
Otočte kolečkem po směru hodinových ručiček – nastavená teplota se zvyšuje, otočte kolečkem proti
směru hodinových ručiček – nastavená teplota se snižuje. Pozor, nastavená teplotní korekce se ruší
při přechodu časového programu do jiného stavu! Teplotní korekce nelze nastavit v módu Vypnuto.
Týdenní časový program přepíná mezi módy Den, Noc, Neaktivní a Vypnuto podle tabulky událostí.
V jednom dni lze definovat až 6 přechodů mezi módy. Do nastavení časového programu přepněte
dlouhým stiskem knoflíku (> 1 s). Regulátor se přepne do režimu nastavení hodin (zobrazí se symbol
hodin). Otáčením knoflíku vyberte den v týdnu (1 až 7). Výběr potvrďte krátkým stiskem knoflíku.
Otáčením knoflíku vyberte událost (velká číslice 1 až 6). U každé události je symbol módu, do nějž
událost přepíná – Den (slunce), Noc (měsíc), Vypnuto (prázdný dům), Neaktivní (symbol Vyp-Zap).
Pozn. V módu Vypnuto jsou kontakty DO1 a DO2 trvale rozepnuty a nelze nastavovat teplotní korekci.
Krátkým stiskem potvrďte výběr události. Otáčením knoflíku nastavte požadovaný provozní mód pro
tuto událost (Den, Noc, Vypnuto, Neaktivní). Je-li událost neaktivní, předešlý provozní mód se v čase
události nemění – událost tedy nemá na řízení regulátoru vliv. Krátkým stiskem potvrďte nastavení
provozního módu. Na to se zobrazí čas události. Otáčením nastavte požadovaný čas události (tedy
v kolik hodin má dojít k přepnutí do daného stavu) a potvrďte krátkým stiskem. Pak otočením knoflíku
vyberte další událost v daném dni nebo dlouhým stiskem a otáčením knoflíku vyberte další den v
týdnu. Po nastavení všech požadovaných událostí dlouhým stiskem knoflíku opusťte nastavení
časového programu. Regulátor se automaticky vrací zpět do zobrazení teploty, stejně jako po 30
vteřinách neaktivity.
Přepněte do nastavovacího módu super dlouhým stiskem knoflíku (> 5 s). Regulátor se přepne do
stavu, kde se nastavují požadované teploty pro jednotlivé provozní módy (indikováno ikonkou
teploměru).
O
●Reálný čas a den v týdnu (hodiny, jeden ze dnů v týdnu 1..7)
●Požadovaná teplota topení, den (bliká teploměr, topení, slunce)
●Požadovaná teplota topení, noc (bliká teploměr, topení, měsíc)
Potvrďte výběr hodnoty krátkým stiskem. Otáčením knoflíku teplotu změňte. Novou hodnotu potvrďte
krátkým stiskem.
Regulátor se automaticky vrací zpět do zobrazení teploty po 30 vteřinách neaktivity.

6
●Po – Pá 6:00 ... 15:00 komfort, jinak útlum
So – Ne trvale útlum
●Regulace podle interního čidla (přepnutí teplotního čidla se provádí přepínačem na zadní straně
regulátoru-viz níže)
●Teplota pro útlum 15 C, pro komfort 19 C
●Rozsah zadávaných teplot 5 °C - 30 °C, absolutně
●Hystereze pro regulaci 1 K
●Přítomnost: dálkově řízeno, bez možnosti editace
●Zobrazování hodnot: aktuální čas, měřená teplota
●Reset teplotní korekce při přechodu časového programu do jiného stavu
●DO2 offset (výchozí 0) - teplotní posun druhého stupně topení od prvního stupně (hystereze je
pro oba stupně stejná).
hystereze 1K, DO2 offset 0K, požadovaná teplota 19 °C, DO1 (první stupeň topení) zapne při
poklesu teploty pod 18 °C a vypne při dosažení 19 °C, DO2 (druhý stupeň topení) sepne při
poklesu pod 17 °C a vypne při dosažení 18 °C.
S nadřazeným systémem komunikují pomocí sběrnice RS485 po protokolu Modbus RTU a proto
se dají využít v řadě řídicích a monitorovacích systémů.
Popis protokolu viz samostatný dokument Ovladače, moduly a regulátory IRC, Popis komu-
nikace.
2
Napájení 24 V ss +/- 10%
Spotřeba 600 mVA + periferie (cca. 5VA)
Rozsah měření interní čidlo 0...50 °C
externí čidlo -20 až 50 °C
Krytí IP20
Přesnost čidla +/- 1,5 K (možnost softwarové korekce)
Výstupy
2x SSR se spínáním v nule pro stejnosměrnou
nebo střídavou zátěž, 24 V ss/st, maximální
spínaný proud 0,4 A, pro spínání relé
Korekce požadované hodnoty podle konfigurace, +5 až +30 °C
Komunikace RS485 - Modbus RTU, slave, opticky odděleno,
1200 ... 115 200 bps
Displej LCD 60 x 60 mm
Svorky šroubové svorky pro vodiče 0,14 – 1,5 mm
Kryt ABS, RAL9010
Hmotnost 0,13 kg
Rozměry viz níže

7
Zadní část plošného spoje:
BUS END: v poloze ON ukončuje sběrnici
(pokud je regulátor poslední na sběrnici)
USR(1): přepínání teploty, podle které se reguluje:
● OFF - interní čidlo
● ON - externí čidlo (Pt1000)
INIT(2): nastavuje regulátor na výchozí komunikační
parametry:
adresa 1, přenosová rychlost 9600 bps.
●připojte přístroj po sběrnici RS485 k PC s konfiguračním programem domat.exe
●nastavte INIT na ON
●připojte napájení (použijte jen černý konektor vyjmutý ze dna regulátoru)
●vyhledejte regulátor v programu (funkce Scan)
●nastavte INIT na OFF
●v programu domat.exe rozklikněte regulátor
●klikněte na tlačítko Init v programu
●vypněte a zapněte napájení
1
2
3
4
5
6
78
9
1: K- komunikace RS485 -
2: K+ komunikace RS485 +
3: DO1 výstup pro topení, 1. stupeň proti G0
4: N/C nevyužito
5: DO2 výstup pro topení, 2. stupeň proti G0
6: - napájení minus, výstupy – vztažný bod
7: + napájení plus
8: AIN externí čidlo teploty Pt1000
9: AGND
externí čidlo teploty Pt1000

8
Regulátory jsou určeny pro provoz v běžném, chemicky neagresivním prostředí. Nevyžadují údržbu.
Montují se ve svislé poloze do míst, kde jsou snadno přístupné pro ovládání a kde správně měří teplotu
v místnosti, tedy asi ve výšce 150 cm, na stinné straně, mimo průvan a vliv zdrojů tepla a chladu
(vyústky klimatizace, chladnička, el. spotřebiče).
dna se svorkami a krytu s plošným spojem a ovládacím panelem. Upevňují se pomocí 2 nebo 4 šroubů
na krabici pod omítku o průměru 50 mm nebo na stěnu. Ve dně spodní části pouzdra je otvor pro
vyvedení kabelu. Při montáži se doporučuje instalovat nejprve dno a kryt s elektronikou vsadit až po
skončení stavebních prací, kdy již nehrozí jeho poškození.
●jemně stiskněte bočnice dna a zároveň opatrně o několik milimetrů povytáhněte pravou část
krytu s dvoupólovým konektorem
●opatrně povytáhněte levou část krytu se sedmipólovým konektorem
●kolmým pohybem uvolněte kryt od dna.
Nevylamujte kryt příliš do strany, mohlo by dojít k poškození pinů v konektoru krytu!
Zámečky jsou pouze na bocích krytu, nikoli v jeho horní či spodní části!

9
Přístroj obsahuje nedobíjitelnou baterii, která napájí systémové hodiny a zálohuje část paměti.
Po skončení životnosti zařízení je vraťte výrobci nebo zlikvidujte v souladu s místními předpisy.
kabelové čidlo teploty, Pt1000, délka kabelu 1.5 m
venkovní čidlo teploty Pt1000, IP65
visuté čidlo teploty Pt1000
visuté čidlo teploty Pt1000 (kulový teploměr)
nástěnné čidlo teploty (polokulový teploměr)
pokojové čidlo teploty (polokulový teploměr)
převodník USB/RS485 pro adresování regulátorů
převodník RS232/RS485 pro adresování regulátorů
komunikativní regulátor topení
komunikativní regulátor topení a chlazení
vizualizační program
webové rozhraní pro pokojové regulátory
Výchozí hodnoty a další parametry regulátoru (PI konstanty, adresa, přenosová rychlost...) je možné
nastavit konfiguračním programem ModComTool přes převodník RS232/RS485 nebo USB/RS485.
Vhodné typy kabelů jsou LAM DATAPAR 2x0.8 (průřez mm ), JYTY 2x1 (průměr mm) apod. Pokud ve
stejném kabelu povede i komunikace, použijte čtyřžilové kabely LAM DATAPAR 2x2x0.8, JYTY 4x1. Při
vzdálenostech desítek metrů souběh napájení 24V a sběrnice nevadí. Z hlediska elektromagnetické
odolnosti je vhodnější, když jsou žíly v páru kroucené (jako je tomu u kabelu LAM DATAPAR).
Do svorky regulátorů se vejdou max. 3 vodiče o průřezu 0.8 mm . Při použití výše uvedených typů
kabelů, uvažovaném maximálním (startovacím) příkonu sady „regulátor + ventil“ cca. 7 VA a přípustném
úbytku napětí do 15 % vychází při 10 regulátorech osazených vždy jedním ventilem max. délka kabelu
asi 50 m.
2
2

10

11

12
……………………………………….......……………………………
……………………………………………………………............................
……………………………………….......…………………………….
………………………
…………………………………….....................................................
User temperature correction………………………….....................................
15
Setting the time program…………………………..........................................
15
Setting basic desired temperatures and real time..........................................
15
Default regulator settings……………………….............................................
16
……………………………………….......………….....
Terminals………………………………………………………..........................
17
Switches.……………………………….…………………................................
17
……………………………………….......…………………………….....
……………………………………………………………........................
………………………………………………………….….........................
………………………………………..……....................

13
OID is control system for two-stage control of radiant heaters. It consist of switchboard OI and controller
UC301. The switchboard OI is available for one to six heaters, the number of heaters connected is
indicated by the number in the OID type, OID 1 to OID 6.
1main control switch.
The „I“ position centrally turns on the OID control
The „0“ position centrally shuts off the OID control
2
three-position switch for each heater
Positions:
● in this case the heater is manually ON,
regardless of the MANDÍK UC301 regulator
● - central position In this case the
specific heater is manually OFF
● in this case the heater is controlled
automatically by MANDÍK UC301 regulator
3 power indicator light for each heater
4 operating indicator light for each heater
1. Switch the main electrical switch „0 “ to the „ I“ position.
2. Turn the control switch of individual heaters „ - STOP - “ manually „ “ or automatically
„ “ the electric network green indicator light will light up „ “ on the control box. (the number of
switches will vary depending on the type of control box - OID 1 to OID 6. OID 1 controls 1 Helios
heater, OID 6 controls 6 Helios heaters)
3. After the venting time (about 50 seconds) the infrared heater starts up and the green indicator light
lights up on the control box „ “ and orange indicator light at the bottom of the burner box of the
heater.
4. In case the burner is not fired (the orange lamp of operation on the control box is not alight), the cycle
is repeated twice. If it does not ignite even the third time, the red indicator light on the burner box lights
up to indicate an error. For unblocking the error state, the power supply of the heater must be
disconnected and reconnected (turn the control switch „ - STOP - “ to the „STOP“ position and
back to „ “ or „ “. If the infrared heater fails to work after multiple ignition cycles, call your service
organization.
5. The performance of two-stage infrared heaters in the case of OID is controlled automatically by the
MANDÍK UC301 regulator.
6. Temperature sensor - the temperature sensor is a standard part of the UC301 regulator. If necessary,
the temperature sensor ASTF Pt 1000 can be connected to the regulator for measuring radiant
temperature. A detailed procedure for changing the sensor can be found below in the regulator manual.

14
1. Turn the „ - STOP - “ switch to the „STOP“ position.
2. When the radiator is shut off for a long time, it is advisable to close the gas valve.
The UC301 is a communication two-stage regulator for gas heaters with SSR outputs. It can work
autonomously or be connected to a primary regulator (MiniPLC or SoftPLC), visualization (RcWare
Vision or other SCADA system) or UCWEB web interface.
●Radiant heating systems - factories, warehouses
●Systems with any source of heat, controlled in two stages
The regulator measures the room temperature via a built-in sensor or external sensor Pt1000, The
measured and required values are processed in a PI control algorithm, at the output of which is a
two-stage sequence for controlling two-stage outputs that control the individual stages of the gas heaters.
The system shows other values (correction, central operating status, etc.), which are displayed on an
LCD display.The required temperature is based on a weekly program (6 events per day).
The control knob can be used for temperature correction.

15
The external sensor is used in cases when the regulator is installed in a place where it is not possible to
measure the temperature correctly. Use the analog sensor Pt1000 designed for rooms, industrial spaces
(high resistance) or the outdoors (higher coverage). The temperature range of the external sensor is -20
to +50 °C. If the sensor is not connected (terminals disconnected), the temperature is automatically taken
from the internal sensor.Regulation parameters, hysteresis, time programs, etc., can be set using the
configuration software ModComTool, which is free to download at www.domat.cz.If the difference
between the measured temperature and the desired temperature is large(eg. more than 2 K), both
outputs are on and the heating system operates at 100%. If the temperature gets closer to 1 K of the
desired temperature, the DO2 switches off. The heating then heats at 50% and when the room is heated
to the desired temperature, the DO1 contact also switches off and the regulator waits for the temperature
to drop.The regulator contains a real-time clock with a weekly program (6 events per day). It switches
between Comfort, Economy, and Off modes. Each mode has a target value for heating. The values are
selectable in the control menu or by remote control. The display alternates between the current time and
temperature measurement.
Turn the control knob clockwise - the set temperature increases, turn the knob counterclockwise - the
set temperature decreases. Note that the temperature correction setting is canceled when the time
program transitions into a different mode! The temperature correction can not be set in Off mode.
The weekly time program switches between Day, Night, Inactive and Off modes according to the table
of events. Up to 6 transitions between modes can be defined in one day.Switch to the time program with
a long press of the knob (> 1 second). The control with switch to the clock setting (clock symbol is
displayed). Turn the knob to select a day of the week (1 to 7). Confirm your selection with a short press
of the knob. Turn the knob to select an event (large number 1 to 6). Each event has a mode symbol to
which it switches the event - Day (sun), Night (moon), Off (empty house), Inactive (Off-On symbol). Note
In Off mode the DO1 and DO2 contacts are switched off and the temperature can not be corrected.
Confirm your selection with of event by short press of the knob. Turn the knob to select an operating
mode for this event (Day, Night, Off, Inactive). If the event is inactive, the previous operating mode at the
time of the event does not change - the event therefore has no influence on the operation of the control.
Confirm the operating mode setting with a short press. The time of the event will show on the display.
Turn the knob to adjust the desired time of the event (what time it should switch to the desired mode)
and confirm with a short press. Then turn the knob to select another event on the given day, or select
another day of the week with a long press and turn of the knob. After setting all the desired events, exit
the time program setting with a long press of the knob. The regulator will automatically return to the
temperature display, just like after 30 seconds of inactivity.
Switch to settings mode with a very long press of the knob (> 5 seconds). The regulator will switch to the
mode where the desired temperature is set for individual operating modes (indicated by thermometer
symbol).
●Real time and day of the week (hours, one day of the week 1..7)
●Desired heating temperature, day (flashing thermometer, heating, sun)
●Desired heating temperature, night (flashing thermometer, heating, moon)
Confirm your selection with a short press. Turn the knob to change the temperature. Confirm the new
value with a short press.
The regulator will automatically return to the temperature display after 30 seconds of inactivity.

16
●Mon – Fri 6:00 ... 3:00pm Comfort, otherwise Economy
Sat – Sun permanently Economy
●Regulation according to internal sensor (switching the temperature sensor is performed with
a switch on the back of the regulator, see below)
●Economy temperature 15 C, Comfort temperature 19 C
●Range of entered temperature 5 °C - 30 °C, absolute
●Hysteresis for control 1 K
●Presence: remote controlled, with no option of editing
●Display of values: current time, measured temperature
●The temperature correction resets when the time program transitions into a different mode
●DO2 offset (default 0) - temperature shift of the second stage from the first stage
(hysteresis is the same for both stages)
hysteresis 1K, DO2 offset 0K, required temperature 19 °C, DO1 (first heating stage) switches on
when temperature drops below 18 °C and switches off when the temperature reaches 19 °C, DO2
(second heating stage) switches on when temperature drops below 17 °C and switches off when
temperature reaches 18 °C. UC301 regulator communicates with the superior system with bus
RS485 in protocol Modbus RTU and can therefore be used in various control and monitoring
systems. For description of protocol see separate document, Controls, Modules and Regulators,
IRC, Communication Description.
Power supply 24 V ss +/- 10%
Consumption 600 mVA + peripherals (approx. 5VA)
Measurement range internal sensor 0...50 °C
external sensor -20 až 50 °C
Protection IP20
Sensor accuracy +/- 1,5 K (option of software correction)
Outputs
2x SSR with zero voltage switching for DC or AC
load, 24 V ss/st, maximum current 0,4 A, for
relay switch
Correction of desired value according to configuration, +5 to +30 °C
Communication RS485 - Modbus RTU, slave, optically isolated,
1200 ... 115 200 bps
Display LCD 60 x 60 mm
Terminals screw terminals for conductors 0,14 – 1,5 mm
Cover ABS, RAL9010
Weight 0,13 kg
Dimensions see below
2

17
1
2
3
4
5
6
78
9
Rear side of regulator board:
BUS END: switch on if the regulator is the last on the
RS485 bus
USR(1): Chooses the valid temperature sensor:
●OFF - internal temperature sensor
●ON - external temperature sensor (Pt1000)
INIT(2): sets the default communication settings:
address 1, transfer rate 9600bps
●Connect the regulator using RS485 bus to PC with installed configuration software domat.exe
●Switch INIT to ON
●Connect the power supply (use exclusively the black connector on the bottom of the regulator
●Search for the regulator by the software (Scan function)
●Switch INIT to OFF
●Click to the regulator in the domat.exe software
●Click to the INIT button in the domat.exe software
●Turn the power supply off and back on
1: K- RS 485 communication -
2: K+ RS 485 communication+
3: DO1 output heating, 1st stage
4: N/C not used
5: DO2 output heating, 2nd stage
6: - Power supply – pole, reference
7: + Power supply + pole
8: AIN external temperature sensor Pt1000
9: AGND
external temperature sensor Pt1000

18
The regulators are designed to operate in a normal non-corrosive indoor environment. They don't
require maintenance. They are installed vertically in places where they are easily accessible for control
and where they properly measure the room temperature, which is at about a height of 150 cm in the
shade, away from drafts and sources of heat and cold (air conditioner outlets, refrigerator, electric
appliances).
the bottom with terminals and the cover with a PCB and control panel. They are attached with 2 or 4
screws on a flush-mounted box with a diameter of 50 mm or on the wall. At the bottom of the box is an
opening for cable. It is recommended to first install the bottom and only insert the cover with the
electronics after the construction works are finished to prevent damage.
When removing the cover with electronics, proceed as follows:
●Gently press the sides of the bottom and carefully pull the right side of the cover with a 2 pole
connector up by a few millimeters
●Carefully pull up the left side of the cover with a 7 pole connector
●Unfasten the cover from the bottom with a vertical movement
Don't pull the cover too much to the side, it could damage the pins in the cover connector!
Clasps are only on the sides of the cover, not at the top and bottom!

19
The device contains a non-rechargeable battery that supplies power to the system clock and backs up
part of the memory. After the end of the device life, return it to the manufacturer or dispose of it in
accordance with local regulations.
cable temperature sensor, Pt1000, cable length 1.5 m
outdoor temperature sensor Pt1000, IP65
aerial temperature sensor Pt1000
aerial temperature sensor Pt1000 (spherical thermometer)
wall temperature sensor (hemispherical thermometer)
room temperature sensor (hemispherical thermometer)
converter USB/RS485 for addressing controls
converter RS232/RS485 for addressing controls
communication heating regulator
communication heating and cooling regulator
visualization program
web interface for room regulators
Default values and other regulator parameters (PID constants, address, baud rate...) can be set in the
configuration program ModComTool via converter RS232/RS485 or USB/RS485.
Suitable cable types are LAM DATAPAR 2x0.8 (diameter mm ), JYTY 2x1 (diameter mm) etc. If the
communication will lead through the same cable, use four conductor cables LAM DATAPAR 2x2x0.8,
JYTY 4x1. At distances of dozens of meters, the concurrence of the power supply 24V and the bus is
not a problem. In terms of electromagnetic endurance it is better if the conductors are twisted in pairs (as
in the cable LAM DATAPAR).
The regulator terminals can fit a maximum of 3 conductors with cross-section of 0.8 mm . When using
the types of cables listed above, the maximum (start-up) power of the "regulator + valve" approx. 7 VA,
and permissible voltage drop up to 15%, the maximum cable length with 10 regulators containing one
valve each is 50 m.