Marathon TS 830 Manual

9087A –198th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110
TS 830
AUTOMATIC TRANSFER SWITCHES
INSTALLATION, OPERATING &
SERVICE MANUAL
PM059 REV 9 14/01/16


TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 Thomson Power Systems
TABLE OF CONTENTS
1. PRODUCT REVISION HISTORY 1
1.1. ENVIRONMENTAL CONDITIONS 1
2. NOTES TO INSTALLER 2
2.1. ELECTRICAL CONNECTIONS 2
2.2. TRANSFER SWITCHES WITH ADJUSTABLE OVER CURRENT PROTECTION 2
2.3. TRANSFER SWITCHES WITH MULTI-TAP VOLTAGE CAPABILITY 3
2.4. SYSTEM PHASING-HIGH LEG DELTA SYSTEMS 4
2.5. REMOTE START CONTACT FIELD WIRING 5
2.6. DIELECTRIC TESTING 5
2.7. INSTALLATION OF OPEN TYPE TRANSFER SWITCHES 5
3. GENERAL DESCRIPTION 6
3.1. PRODUCT MODEL CODE 6
4. GENERAL THEORY OF OPERATION 8
4.1. STANDARD AUTOMATIC TRANSFER SWITCH 8
4.2. TEST MODES 9
5. OVER CURRENT PROTECTION 10
6. GENERAL NOTES ON SERVICING ATS MECHANISM 10
7. TRANSFER SWITCH MECHANISM –125 - 800 AMP (S STYLE) 11
7.1. MANUAL OPERATION 12
8. TRANSFER SWITCH MECHANISM –1000A- 1600 AMP (T STYLE) 13
8.1. MANUAL OPERATION 13
9. RECOMMENDED MAINTENANCE 14
10. FRONT VIEW (TYPICAL) 3 / 4 POLE 125A-250A S-STYLE TRANSFER
MECHANISM 15
11. FRONT VIEW (TYPICAL) 3 POLE 400A-800A S-STYLE TRANSFER MECHANISM
(MECHANISM FRONT COVER REMOVED) 16

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 Thomson Power Systems
12. FRONT VIEW (TYPICAL) 3 / 4 POLE 1000A-1600A TRANSFER MECHANISM 17
13. CABLE TERMINAL INFORMATION 18
14. ELECTRICAL RATINGS 18
15. TROUBLESHOOTING 19
16. REPLACEMENT PARTS 20
17. PRODUCT RETURN POLICY 21
18. NOTES 22

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 1 Thomson Power Systems
1. PRODUCT REVISION HISTORY
The following information provides an historical summary of changes made to this product since the
original release.
Operating & Service Manual Version
Rev 8 11/07/18
Miscellaneous corrections
Rev 7 10/04/05
Revision to add S Style Mechanism 100A-800A
Rev 6 08/05/05
Revision to add HS Style Mechanism 630A-800A
Rev 5 07/10/10
Revision to add HS Style Mechanism 100-400A
Rev 4 07/03/26
Revision to add MEC 310 controller
Rev 3 04/12/21
Revisions to incorporate the new model coding.
Rev 2 04/03/10
Revisions to mechanism style 1000A, 1200A & 1600A.
Rev 1 03/04/15
Revisions to text, dimensions, & cable specifications.
Rev 0 02/12/20
Original release.
Contact Thomson Power Systems, to obtain applicable instruction manuals or if in doubt about any
matter relating to installation, operation or maintenance. Soft copy of the most current version is
available at www.thomsontechnology.com.
NOTE: All information contained in this manual is for reference only and is subject
to change without notice.
1.1. ENVIRONMENTAL CONDITIONS
CAUTION!!!
Failure to store and operate equipment under the specified environmental conditions may
cause equipment damage and void warranty.
1.1.1. EQUIPMENT STORAGE
The transfer switch shall be stored in an environment with a temperature range not
exceeding -4° to +158° Fahrenheit (-20° to +70° Celsius) and a humidity range not
exceeding 5%-95% non-condensing. Before storing, unpack sufficiently to check for
concealed damage. If concealed damage is found, notify the ATS supplier and the
Carrier immediately. Repack with the original, or equivalent packing materials. Protect
from physical damage. Do not stack. Store indoors in a clean, dry, well ventilated

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 2 Thomson Power Systems
area free of corrosive agents including fumes, salt and concrete/cement dust. Apply
heat as necessary to prevent condensation.
1.1.2. EQUIPMENT OPERATING
The transfer switch shall be operated in an environment with a temperature range not
exceeding +5° to +122° Fahrenheit (-15° to +50° Celsius) and a humidity range not
exceeding 5%-95% non-condensing.
2. NOTES TO INSTALLER
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
2.1. ELECTRICAL CONNECTIONS
To ensure satisfactory installation of this equipment be sure to observe "Cable Terminal
Information” regarding power cable connection tightness located in this manual.
All mechanical and electrical connections must be checked for tightness prior to placing this
equipment in service to ensure proper operation and to validate applicable warranty
coverage.
2.2. TRANSFER SWITCHES WITH ADJUSTABLE OVER CURRENT
PROTECTION
Standard models of automatic transfer switches incorporate integral over current protection.
Transfer switches rated 1000A or higher are supplied with adjustable over current protection
trip units. For models of transfer switch with integral over current protection, the over current
protection must be set prior to operation. The equipment will be shipped from the factory
with a long-time current setting of 100% (of the equipment rating) and maximum short-
time/instantaneous current and time delay settings.
WARNING!

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 3 Thomson Power Systems
Do Not Energize this equipment until
device settings have been verified to
ensure proper system protection &
coordination. Failure to do so may
result in equipment failure.
Refer to Section 5.1.3 of this manual for additional information on operation of the Transfer
switch following an over current trip condition.
Refer to information supplied with the transfer switch documentation package for adjustment
procedures on the power switching units over current protection trip unit. Contact the factory
if any additional information is required.
2.3. TRANSFER SWITCHES WITH MULTI-TAP VOLTAGE CAPABILITY
If the transfer switch has programmable multi-tap voltage capability confirm the transfer
switch has been configured for the correct system voltage prior to installation.
WARNING!
Failure to confirm and match transfer
switch voltage with the system voltage
could cause serious equipment damage.
The voltage selections and connections are shown on the engineered drawings attached to
each transfer switch. The factory default settings will be indicated on the calibration label
attached on the inside of the enclosure door (supplied loose on open style models). A blank
label is included to record the applicable settings if the configuration is changed from the
factory default settings.
To change the transfer switch configuration the following must be accomplished:
Change voltage taps on potential transformers (PT’s) to correct system voltage (refer
to drawings)
Change program setting in the applicable controller used on the transfer switch (e.g.
TSC 80E, MEC 310) for nominal system voltage. Refer to the applicable controller
instruction manual for further information.
Once the PT voltage taps and controller has been re-programmed to correct
operating voltage, the “control circuit isolation plug” on the mechanism, may be
reconnected, prior to voltage energization.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 4 Thomson Power Systems
2.4. SYSTEM PHASING-HIGH LEG DELTA SYSTEMS
For systems using high leg delta 240V 3 phase 4 wire systems, connection of supply
conductors must have the correct phasing as shown below.
WARNING!
Failure to match correct system phasing
will result in serious damage to the
controller.
208V
B
(Orange)
(High Leg)
C
(Yellow)
A
(Red) N
(White)
PH A
(UA)
Automatic Transfer
Switch (Utility Supply)
PH B
(UB) PH C
(UC) Neural
(N)
120V 120V
240V 240V
CAUTION!!!
All installation and/or service work performed must be done by qualified
personnel only. Failure to do so may cause personal injury or death.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 5 Thomson Power Systems
Where transfer switches are supplied without power isolation transformers (PT1 &
PT2) for ATS control logic it is essential that the orientation of phase conductors of
the supply source be arranged such that the phase of highest potential with respect to
ground is not connected to the power supply inputs to the controller (The A Phase for
both supplies). Failure to do so will result in equipment damage.
Per NEC Article 384-3 (f) “The B phase shall be that phase having the higher voltage
to ground on a 3-phase, 4-wire delta connected systems.”
2.5. REMOTE START CONTACT FIELD WIRING
For applications using TSC 80e controllers, as a minimum, the remote engine start
control field wiring shall conform to the local regulatory authority on electrical
installations. Field wiring of a remote start contact from a transfer switch to a control
panel should conform to the following guidelines to avoid possible controller
malfunction and/or damage.
3.5.1. Minimum #14 AWG (2.5mm2) wire size shall be used for distances up to 500ft
(150m)1). For distances exceeding 500 ft. (150m) consult Thomson Power
Systems.
3.5.2. Remote start contact wires should be run in a separate conduit.
3.5.3. Avoid wiring near AC power cables to prevent pick-up of induced voltages.
3.5.4. An interposing relay may be required if field-wiring distance is excessively
long (i.e. greater than 500 feet (150m) and/or if a remote contact has a
resistance of greater than 5.0 ohms.
3.5.5. The remote start contact must be voltage free (i.e. dry contact). The use of a
“powered” contact will damage the transfer controller.
2.6. DIELECTRIC TESTING
Do not perform any high voltage dielectric testing on the transfer switch with the
controller connected into the circuit, as serious damage will occur to the controller. All
AC control fuses and/or control circuit breakers or control circuit isolation plugs
connected to the controller must be removed if high voltage dielectric testing is
performed on the transfer switch.
2.7. INSTALLATION OF OPEN TYPE TRANSFER SWITCHES
Please contact Thomson Power Systems for additional information.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 6 Thomson Power Systems
3. GENERAL DESCRIPTION
Thomson Power Systems TS 830 series of Automatic Transfer Switches employ two mechanically
interlocked enclosed contact power switching units and a microprocessor based controller to
automatically transfer system load to a generator supply in the event of a utility supply failure.
System load is then automatically re-transferred back to the utility supply following restoration of the
utility power source to within normal operating limits. Transfer switches with MEC 2, MEC 20 or MEC
310 controllers installed have integral engine-genset auto start control & monitoring features and
therefore these applications do not require an engine-mounted auto start control panel.
The standard TS 830 series Automatic Transfer Switch is rated for 100% system load and does not
require upstream over current protection. Refer to Section 6 of this manual for detailed information
on over current protection.
The TS 830 series transfer switch may be supplied with type TSC 80e, TSC 800, MEC 310 or MEC
20 controllers as specified at equipment order. All controllers are microprocessor based which
provides all necessary control functions for fully automatic operation. The controllers are mounted
on the door of the transfer switch enclosure and operating status is shown via LED lights and/or LCD
display dependent upon controller type. For further information on the controller utilized, refer to
separate instruction manuals.
The power switching devices used for the Utility and Generator sources are operated by an
electrically driven motor mechanism in the transfer switch. The transfer switch motor utilizes the
power from the source to which the electrical load is being transferred. The mechanism provides a
positive mechanical interlock to prevent both power switching units from being closed at the same
time, which allows an interrupted “break-before-make” transfer sequence.
Note: For the purpose of this manual, the following standard nomenclature is utilized:
Utility: to indicate the source of primary power
Generator: to indicate the source of standby power
Power switching device: to indicate the transfer switch power switching device
3.1. PRODUCT MODEL CODE
The type of TS 830 series transfer switch supplied is identified by way of a 21 digit product
code which appears on the equipment rating plate (MODEL) on the door of the transfer
switch, and on the transfer switch drawings. The model code structure and definitions are as
follows:

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 7 Thomson Power Systems
12 4 678910 11 12 13 14 15 17 18 19 20 21
T S 8
1-3. SERIES 15 . VOLTAGE 18. UTILITY SWITCHING DEVICE CONTINUED
TS - TRANSFER SWITCH
1f3 WIRE
R - INSULATED CASE, FIX-MOUNT SWITCH
D - 120/240 C/W ELECTRONIC TRIP (800-3200A)
4 & 5. MODEL
3f4 WIRE (GROUNDED NEUTRAL) U - INSULATED CASE DRAW-OUT SWITCH
83 - 830 SWITCH E - 120/208
(800 - 3200A)
F - 127/220 V - INSULATED CASE DRAW-OUT SWITCH
6. POLES
G - 120240 (DELTA)
C/W ELECTRONIC TRIP (800 - 4000A)
2 - 2 POLE
H - 220/3802
W - INSULATED CASE, DRAW-OUT SWITCH
3 - 3 POLE
J - 240/415 2C/W ELECTRONIC & GF TRIP (800-3200A)
4 - 4 POLE M - 277/480 X - SPECIAL
S - 230/400 2
7. CONFIGURATION TYPE
3f3 WIRE 19. GENERATOR SWITCHING DEVICE
A - ATS P - 208 K - MOLDED CASE SWITCH (100 - 1200A)
X - SPECIAL Q - 220 M - MOLDED CASE SWITCH C/W THER-MAG
R - 240 TRIP (100-800A)
8 - 11. AMPERAGE U - 415 N - MOLDED CASE SWITCH C/W ELECTRONIC
0100 V - 480 TRIP (250-1200A)
0250 Y - MULTIVOLTAGE P - MOLDED CASE SWITCH C/W ELECTRONIC
0400 X - SPECIAL & GF TRIP (250-1200A)
0630
Q - INSULATED CASE, FIX MOUNT SWITCH
0800 16. CONTROLLER
(800A-3200A)
1000 2 - TSC800
R - INSULATED CASE, FIX-MOUNT SWITCH
1200 3 - TSC80e C/W ELECTRONIC TRIP (800-3200A)
1600 6 - PGC4000 U - INSULATED CASE DRAW-OUT SWITCH
2000 7 - NONE (MANUAL)
(800 - 3200A)
2500 8 - MEC 310 (PCC) V - INSULATED CASE DRAW-OUT SWITCH
3200 9 - MEC 320 C/W ELECTRONIC TRIP (800 - 4000A)
W - INSULATED CASE, DRAW-OUT SWITCH
12. APPLICATION 17. ENCLOSURE TYPE C/W ELECTRONIC & GF TRIP (800-3200A)
A - STANDARD ATS A - NEMA1, ASA #61 GREY X - SPECIAL
C - DUAL SOURCE B - NEMA2, ASA #61 GREY
P - POWER CONTROL CENTRE (PCC) C - NEMA12, ASA #61 GREY 20. POWER CONNECTIONS
S - PEAK PLUS D - NEMA3R SD, ASA #61 GREY
A - STANDARD
X - SPECIAL E - NEMA3R DD, ASA #61 GREY X - SPECIAL
F - NEMA4X DD, STAINLESS STEEL
13. OPERATION TYPE G - NONE (OPEN STYLE) 21. ATS CONNECTION CONFIGURATION
1 - OPEN TRANSITION
J - NEMA1, BEIGE 1
A - STANDARD
2 - MANUAL ELEC. OP. X - SPECIAL B - ALTERNATE B (1000-1600A)
4 - CLOSED TRANSITION (SOFT LOAD) C - ALTERNATE C (1000-1600A)
X - SPECIAL 18. UTILITY SWITCHING DEVICE D - ALTERNATE D (1000-1600A)
K - MOLDED CASE SWITCH (100-1200A) E - ALTERNATE E (800-3200A)
14 . SAFETY STANDARD M - MOLDED CASE SWITCH C/W THER-MAG F - ALTERNATE F (800-3200A)
X - NOT APPLICABLE TRIP (100-800A) G - ALTERNATE G (800-3200A)
N - MOLDED CASE SWITCH C/W ELECTRONIC X - SPECIAL
TRIP (250-1200A)
P - MOLDED CASE SWITCH C/W ELECTRONIC
NOTES
& GF TRIP (250-1200A)
1FOR PCC APPLICATION
Q - INSULATED CASE, FIX MOUNT SWITCH
2FOR 50 Hz APPLICATION
(800A-3200A)
5
16
3

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 8 Thomson Power Systems
4. GENERAL THEORY OF OPERATION
4.1. STANDARD AUTOMATIC TRANSFER SWITCH
4.1.1. NORMAL OPERATION
When utility supply voltage drops below a preset nominal value (adjustable from 70%
to 100% of nominal) on any phase, an engine start delay circuit will be initiated and
the transfer to utility supply signal will be removed (i.e. contact opening). Following
expiry of the engine start delay period (adjustable from 0 to 60 sec.) an engine start
signal (contact closure) will be given.
Once the engine starts, the transfer switch controller will monitor the generator
voltage and frequency levels. Once the generator voltage and frequency rises above
preset values (adjustable from 70% to 95% of nominal), the engine warmup timer will
be initiated. Once the warmup timer expires (adjustable from 0 to 60 sec.), the
Transfer to Generator Supply signal (contact closure) will be given to the transfer
switch mechanism. The load will then transfer from the utility supply to the generator
supply via the motor driven mechanism.
The generator will continue to supply the load until the utility supply has returned.
The retransfer sequence is completed as follows: when the utility supply voltage is
restored to above the preset values (adjustable from 70% to 95% of nominal) on all
phases, a transfer return delay circuit will be initiated. Following expiry of the Utility
Return Timer (adjustable from 0 to 30 min.), the Transfer to Generator Supply signal
will be removed (contact opening), and then the Transfer to Utility Supply signal
(contact closure) will be given to the transfer switch mechanism. The load will then
retransfer the load from the generator supply back to the utility supply.
Note: For transfer switches with TSC 80e/800 controllers, a neutral delay timer circuit
will delay the transfer sequence in the neutral position (i.e. both power switching
devices open) until the neutral time delay period expires (adjustable from 0 to 60
sec.).
An engine cooldown timer circuit will be initiated once the load is transferred from the
generator supply. Following expiry of the cooldown delay period (adjustable from 0 to
30 min.), the engine start signal will be removed (contact opening) to initiate stopping
of the generator set.
Note: For transfer switches with MEC 2/20, MEC 310 controllers, engine start signal
is internal to the controller.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 9 Thomson Power Systems
4.1.2. OVER CURRENT TRIP (TSC 80e/TSC 800 CONTROLLERS)
Should the utility power switching device trip open due to an over current condition,
TSC 80e or TSC 800 transfer controller will initiate an engine start signal and will
permit transfer of the load to the generator supply. The utility source will be locked out
and the load will remain on the generator supply until the TSC 80e/TSC 800 alarm
signal is manually reset.
Refer to the TSC 80e & TSC 800 Instruction Manuals for further details on Transfer
Fail operation.
Should the generator power switching device trip open due to an over current
condition, TSC 80E/TSC 800 transfer controller will initiate transfer of the load to the
utility supply. The generator source will be locked out and the load will remain on the
utility supply until the TSC 80E/TSC 800 alarm signal is manually reset.
4.1.3. OVER CURRENT TRIP (MEC 2/MEC 20/MEC 310 CONTROLLERS)
Should the utility power switching device trip open due to an overcurrent condition,
the generator will not automatically start and transfer on load. The generator must be
started and transferred on load manually.
Should the generator power switching device trip open due to an overcurrent
condition, the generator will shutdown and the load will automatically return to the
utility supply if its voltage is normal. Note: for automatic transfer to utility, the transfer
switch must be factory ordered with a “gen breaker tripped” auxiliary contact inside
the generator power switching device and must be wired to the gen set controllers
shutdown alarm circuits.
Refer to the Gen Set controller instruction manual for further details on manual
operation or shutdown-reset operation.
4.2. TEST MODES
The transfer switch may be tested utilizing the controller pushbuttons or optional test switch.
A simulated utility power failure condition will be activated when the test mode is selected.
The transfer switch will operate as per a normal utility power fail condition.
The transfer switch will remain on generator supply until the test mode is terminated. It will
then immediately transfer back to the utility supply and then continue to operate the
generator set for its cooldown period then stop. Note: The transfer switch will automatically
return to the utility supply (if within nominal limits) if the generator set fails while in the test
mode.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 10 Thomson Power Systems
5. OVER CURRENT PROTECTION
Thomson Power Systems TS 830 series of Automatic Transfer Switches are supplied standard with
integral over current protection.
The type of over current protection utilized is dependent upon ATS amperage size and optional
features specified. For transfer switches rated 125A through 800A, over current protection is non-
adjustable thermal-magnetic type trip units. For transfer switches rated 1000A through 1600A over
current protection is adjustable electronic type with long time & instantaneous trip unit elements with
optional ground fault protection elements.
Note: For models of transfer switch with adjustable integral over current protection trip units, the
over current protection must be set prior to operation. The equipment will be shipped from the
factory with a long-time current setting of 100% (of the equipment rating) and maximum
instantaneous/short-time/ground fault (if supplied) current and time delay settings.
WARNING!
Do Not Energize this equipment until
device settings have been verified to
ensure proper system protection &
coordination. Failure to do so may result
in equipment failure.
6. GENERAL NOTES ON SERVICING ATS MECHANISM
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
When performing any service work on the transfer mechanism, it is imperative that the following be
observed:
7.1. To maintain mechanical integrity, ensure that:

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 11 Thomson Power Systems
All limit switches linkages are correctly adjusted to provide full travel of the power
switching device toggles without exerting unnecessary forces associated with
excessive travel. Ensure that power switching device travel far enough to reset
any internal trip unit (it is more important for the toggle to go fully in the "off"
direction, than in the "on" direction).
Mechanical interlocking is correct when one power switching opens well before
the other should close.
All fasteners are adequately tightened.
The operating linkages are not damaged or bent, and that all bearing points
operate freely.
7.2. To maintain electrical integrity, ensure that:
All electrical connections, especially power connections, are clean and adequately
tightened. Corroded or loose power connections will cause destructive heating,
and may cause premature tripping.
All insulating devices are in place and in good condition.
No moisture or other contamination is present.
Electrical conductors are adequately secured away from moving parts.
On HS style transfer switch mechanisms, check nylock nuts on bolt pivot points.
Operation arms should move freely without excessive play.
7.3. To maintain operational integrity, ensure that:
All control devices are in good condition and correctly calibrated.
All control devices are adequately secured in their plug-in fixtures.
Only qualified personnel should undertake service work. Failure to correctly maintain an
automatic transfer switch may present a hazard to life and equipment. Full operational
testing must be done prior to placing a transfer switch in service subsequent to any
maintenance or repair. Any service work involving electrical components requires high-
potential testing to ensure that required insulation levels have been maintained.
7. TRANSFER SWITCH MECHANISM –125 - 800 Amp (S Style)
The transfer mechanism consists primarily of the transfer gear motor, a drive hub assembly, and two
power switching device operating arms.
The reversible transfer gear motor drives the drive hub assembly, which in turn moves the power
switching device operating arms. The power switching device toggles are set inside the operating
arm slots and are moved by them. There are two limit switches, which are contacted by the
operating arms (one for each power switching device), which disconnect the transfer motor power
supply when the power switching devices have attained full travel. Should limit switch adjustment be
required, it is advisable to consult Thomson Power Systems for further information.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 12 Thomson Power Systems
The transfer switch mechanism has three possible positions:
a) Utility power switching device closed and generator power switching device open;
b) Generator power switching device closed and utility power switching device open;
c) Both utility and generator power switching devices open, but NEVER both utility and
generator power switching devices closed at the same time.
7.1. MANUAL OPERATION
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
Isolate the transfer switch from all sources of supply before opening the enclosure for manual
operation. With all sources of power de-energized to the transfer switch, the control circuit
isolation plug can be unplugged to prevent subsequent operation. The control circuit isolation
plug is located on the inner side of the transfer switch enclosure door.
To operate manually, insert the operating handle into the square hole on the front of the
mechanism and rotate to the desired position. Remove the operating handle once operation
is complete and re-insert into the handle holder on the left-hand side of the transfer switch
mechanism.
Automatic operation may be regained by replacing the control circuit isolation plug. With all
sources of power de-energized to the transfer switch, the control circuit isolation plug can be
re-connected. The drive system will operate the transfer switch to the required position. (See
manual operation instruction on front of transfer switch mechanism.)

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 13 Thomson Power Systems
8. TRANSFER SWITCH MECHANISM –1000A- 1600 Amp (T Style)
The transfer mechanism consists primarily of the transfer motor, a hub assembly, two operating rods
and two power switching device operating yokes.
The reversible transfer motor drives the hub assembly, which in turn moves the operating rods that
are connected to the power switching device operating yokes. The power switching device toggles
are set inside the yokes and are moved by them. There are two limit switches, which are contacted
by the operating yokes (one for each direction of travel), which disconnect the transfer motor power
supply when the power switching devices have attained full travel. The adjuster screws located on
the yoke determines the operating point of these limit switches. Should adjustment be required, it is
advisable to consult Thomson Power Systems for further information.
The transfer switch mechanism has three possible positions:
a) Utility power switching device closed and generator power switching device open;
b) Generator power switching device closed and utility power switching device open;
d) Both utility and generator power switching devices open, but NEVER both utility and
generator power switching devices closed at the same time.
8.1. MANUAL OPERATION
(See CAUTION! on Page #2)
Isolate the transfer switch from all sources of supply before opening the enclosure for manual
operation. With all sources of power de-energized to the transfer switch, the control circuit
isolation plug (PL12) can be unplugged to prevent subsequent operation.
To operate manually, pull the release plunger and operate the handle in the desired
direction.
Automatic operation may be regained by replacing the isolation plug. With all sources of
power de-energized to the transfer switch, the control circuit isolation plug (PL12) can be re-
connected. The drive system is self-engaging and will operate the transfer switch to the
required position. (See manual operation instruction on front of transfer switch mechanism.)

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 14 Thomson Power Systems
9. RECOMMENDED MAINTENANCE
(See CAUTION! on Page #2)
10.1. DO NOT perform dielectric tests on the equipment with the control components in the
circuit.
10.2. Check if control components are tight in sockets.
10.3. Periodically inspect all terminals (load, line and control) for tightness. Re-torque all
bolts, nuts and other hardware. Clean or replace any contact surfaces that are dirty,
corroded or pitted.
10.4. Transfer switches should be in a clean, dry and moderately warm location. If signs of
moisture are present, dry and clean transfer switch. If there is corrosion, try to clean
it off. If cleaning is unsuitable, replace the corroded parts. Should dust and/or debris
gather on the transfer switch, brush, vacuum, or wipe clean. DO NOT blow dirt into
power switching devices.
10.5. Test the transfer switch operation. While the unit is exercising, check for freedom of
movement, hidden dirt, corrosion or any excessive wear on the mechanical operating
parts. Ensure that the power switching device travel is correct.
10.6. Verify all program settings on the controller as per the calibration label or
programming sheets.
10.7. Transfer Mechanism 100-800A HS Style –lubrication of drive hub/operator arm
interface. Use high viscosity moly lubricant
10.8. Transfer Mechanism 1000A-1600A (T Style) - ensure that the manual handle moves
freely on the hub when the lock pin is disengaged. If lubrication is necessary, apply
medium weight (SAE 20) oil sparingly.
10.9. Transfer Mechanism 1000A-1600A (T-Style) - yoke pivot bearings and rod ends are
permanently lubricated and do not require maintenance.
10.10. The motor and gearbox are permanently lubricated, and should not require attention
under normal operating circumstances.

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 15 Thomson Power Systems
10. FRONT VIEW (TYPICAL) 3 / 4 POLE 125A-250A S-Style TRANSFER
MECHANISM

TS 830 TRANSFER SWITCH
PM059 REV 9 14/01/16 16 Thomson Power Systems
11. FRONT VIEW (TYPICAL) 3 POLE 400A-800A S-Style TRANSFER
MECHANISM (Mechanism Front Cover Removed)
ØC ØB ØA NØCØBØAN
ØCØBØAN
DRAWING/FILE No.
CUSTOMER
SHEET
DWN BY AUTH BY DATE REV
WORK ORDER No.ORDER No.
Table of contents
Other Marathon Switch manuals
Popular Switch manuals by other brands

CYP
CYP CDPS-UH4H1HFS Operation manual

Cisco
Cisco Catalyst 4500 E Series Supervisor Engine 9-E Installation and configuration note

Moxa Technologies
Moxa Technologies EDS-405A Hardware installation guide

Eaton
Eaton GHG 273 operating instructions

ORiNG
ORiNG IPS-1080-24V Quick installation guide

Manhattan
Manhattan 162005 instructions

GarrettCom
GarrettCom Hardened Ethernet Switches P62F Installation and user guide

LevelOne
LevelOne IGP-1061 Quick installation guide

Ross
Ross Synergy 1 SD manual

Bosch
Bosch VSS7390/01T installation instructions

Fore Systems
Fore Systems ES-2810 user guide

OfficeSource
OfficeSource OSF9500 Assembly instructions