
Owner’s Manual - PTTC/PTTE/PTTH-09/12C-1
8
IMPORTANT NOTE TO THE OWNER
This equipment is to be serviced by professionally trained
personnel only. If this equipment is improperly installed,
adjusted or altered by an unqualified person, a safety
hazard may result.
TRANSPORTATION DAMAGE
All units are securely packed in shipping containers ap-
proved by the National Safe Transit Association. The carton
1.
IMPORTANT NOTE TO THE SERVICER
Read this manual and familiarize yourself with the specific
items which must be adhered to before attempting to
service this unit. The precautions listed in this manual
should not supersede existing practices but should be
considered as supplemental information.
In the event of damage:
2.
should be checked upon arrival for external damage. If
damage is found, immediately make a written request for
inspection by the carrier’s agent.
3.
Note on the delivery receipt any visible damage to
shipment or container.
Notify carrier promptly and request an inspection.
a.
b.
File the claim with the following supporting documents
within the six month statute of limitations.
c.
Original Bill of Lading, certified copy, or indemnity
bond.
Original paid freight bill or indemnity.
d.
Original invoice or certified copy, showing trade and
other discounts or reductions.
Copy of the inspection report issued by carrier’s
representative at the time damage is reported to the
carrier.
1.
UNPACKING THE UNIT
2.
Cut the carton banding and open the carton.
3.
4.
Remove the literature, hardware pack, upper styrofoam
shipping blocks, and styrofoam corner posts.
Remove the front assembly.
5.
The carrier is responsible for making prompt inspection of
damage and for a thorough investigation of each claim.Th e
distributor or manufacturer will not accept claims from
dealers for transportation damage.
Lift the unit from the remaining carton.
Dispose of the cardboard and styrofoam at an approved
Recycle Center. Check all contents for damaged or
missing parts. In case of concealed damage, notify the
carrier as soon as possible—preferably within 5 days.
fi noitces egamaD noitatropsnarT eht fo 3 pets ot refeR
damage or missing parts are noted.
Power Supply Cord
NOTICE:
Your unit’s device may differ from the ones shown.
This room air conditioner is equipped with a power supply cord
required by UL. This power supply cord contains state-of-the-art
electronics that sense leakage current. If the cord is crushed, the
electronics detect leakage current and power will be
disconnected in a fraction of a second.
RESET
TEST
Indicator
1.
To test your power supply cord:
2.
3.
Press RESET.
Plug power supply cord into a grounded 3 prong outlet.
4.
Press TEST (listen for click; Reset button will trip and pop
out).
NOTICE:
The Reset button must be pushed in for proper operation.
Press and release RESET (listen for click; Reset button will
latch and remain in). The power supply cord is ready for
operation.
The power supply cord must be replaced if it fails to trip when
the test button is pressed or fails to reset.
Do not use the power supply cord as an off/on switch. The
power supply cord is designed as a protective device.
A damaged power supply cord must be replaced with a new
power supply cord obtained from the product manufacturer
and must not be repaired.
The power supply cord contains no user serviceable parts.
Opening the tamper-resistant case voids all warranty and
performance claims.
NEMA No. 6-20P NEMA No. 6-20R 250V-20AMP 230/208V rated
over 12 amperes,
but not more than
16 amperes
NEMA No. 6-30P NEMA No. 6-30R 250V-30AMP 208V rated over
16 amperes, but
not more than
24 amperes
wall receptacle is encountered, the customer is required to
contact a qualified electrician and have the two-prong wall
receptacle replaced with a properly grounded three-prong
wall receptacle in accordance with the National Electrical
Code.
Room air conditioners are designed to operate according to
requirements on the nameplate and as shown in Table 1.
Fuse or circuit breaker ratings must be according to the fuse
instruction label and as shown in Table 1. Do not plug models
marked “Use on Single Outlet Circuit Only” into a circuit with
another appliance or light fixture.
Electrical Requirements
Grounding Instructions
This appliance is equipped with a three-prong grounding plug
for protection against possible shock hazards. If a two-prong
NEMA No. 5-15P 115VNEMA No. 5-15R 125V-15AMP
NEMA No. 6-15P NEMA No. 6-15R 250V-15AMP 230/208V rated
less
at 12 amperes or
Unit Plug Type Receptacle
Required
Voltage Rating
On Nameplate
Circuit Rating,
Breaker, Tim
Delay Fuse