
MVSV 2V Gel Cells –User and Installation Manual 
 
 
3 INSTALLATION 
 
3.1 BEFORE YOU START 
Installation, connection and protection must be 
executed in accordance with the locally applicable 
regulations. 
Check the contents of the delivery. See section 6.1 on 
page 13 for an overview of components that are 
standard included with the delivery. 
After unpacking, check each battery for mechanical 
damage. Do not use the product if it is damaged. If in 
doubt, contact your supplier. 
Check the batteries for correct polarity: 
Check each cell separately by measuring the open 
circuit voltage. U ≥ 2.07V. 
Control of insulation resistance: New batteries: > 1MΩ 
Used batteries: > 100 Ω/Volt. 
3.2 LOCATION TO INSTALL 
3.2.1 General 
Standards referring to installation, cabinets, equipment or 
battery rooms are: EN 50091-1-2, IEC 896-2 (/3/) (draft 
IEC 60896-21 (/4/)) and EN 50272-2 (/1/). 
Obey the following stipulations when choosing a location 
to install the batteries: 
Keep batteries away from heat sources. Allowed 
operating temperature: –20 to 45ºC / –4 to 113ºF. 
Nominal operating temperature: 10 to 30ºC / 50 to 
86ºF. Recommended at 20ºC / 68ºF. The battery life 
is halved for every 10ºC of rise in temperature. Lower 
temperatures will reduce the available capacity. 
Battery installation should be made such that 
temperature differences between individual units do 
not exceed 3ºC / 5ºF. 
Keep at least 1cm / 0.5 inch space between the 
batteries. Mastervolt can supply dedicated cooling 
plates for this purpose (Part No. 67909014). 
All models of the MVSV range are suitable for both 
horizontal and vertical mounting. All cells should be 
mounted either vertically or horizontally. 
Please note that models MVSV 2000 (67162000) and 
MVSV 2500 (67202500) which were delivered before 
January 1st 2006 are only allowed to be installed in 
upright (vertical) position. See also chapter 2.2. If in 
doubt, contact your supplier. 
3.2.2 Ventilation 
DO NOT install the batteries in airtight enclosures. Under 
overcharging conditions, lead acid batteries can vent an 
explosive mixture of hydrogen gas. 
The ventilation of battery rooms and cabinets must be 
carried out according to EN 50272-2. Under normal 
conditions the minimum air flow rate for ventilation of a 
battery location or compartment for Mastervolt MVSV gel 
batteries shall be calculated by the following formula (up to 
40° C operating temperature). 
Q = 0.05 x n x Cnom x 10-3 [m3/h] 
Where n = number of cells 
Cnom = Nominal capacity (see Specifications) 
With natural ventilation (air convection) the minimum inlet 
and outlet area (A) is calculated as follows (Air convection 
speed = 0.1 m/s): 
A = 28 x Q [cm²] 
Example: 
Given: 24V battery bank consisting of 12 pieces Mastervolt 
MVSV 800 gel batteries, Cnom = 998 Ah, 
Calculation of fresh air necessary: 
Q = 0.05 x n x Cnom x 10-3 [m3/h] 
 = 0.05 x 12 x 998 Ah x 10-3 [m3/h] 
 = 0.5988 [m3/h] 
A = 28 x Q [cm²] 
 = 28 x 0.5988 [cm²] 
 = approx. 16.8 [cm²] 
Potential sources of ignition must have a safety distance to 
the pressure valves of the batteries as specified in EN 
50272-2. 
3.2.3 Use of battery racks 
When batteries are installed horizontally, use of a battery 
rack is obligatory. Obey the following recommendations: 
Each cell should be supported separately by the rack 
over its full length. Never stack a battery on another 
battery. 
Check that the battery racks are stable and horizontal. 
For the shelf assemblies with 4 levels of 2 rows or 5 
levels of 3 rows, the assembly should anchored to the 
floor. 
Precautions must be taken if batteries are being 
installed in metallic cabinets or on racks. Keep an air 
safety distance of at least 10mm / 0.5inch between 
insulated cables and electrically conductive parts, or 
use additional insulation.