
5
SURFACE POTENTIAL READINGS
This type of survey employs two copper sulfate electrodes and is applicable to bare pipelines. No connection to the pipe
is required. The survey is conducted with both electrodes directly over the line at a fixed spacing of 10 or 20 feet.
Readings are taken of potential between electrodes at intervals matching the electrode spacing. The same electrode is
always kept in front as the survey progresses. The front electrode is connected to the positive terminal. The readings
will change polarity from + to –as an anode area is passed. Supplementary side drain readings
(one electrode over the pipe, the other electrode 5 ft to one side) are taken at suspected anode
points. The reading is often repeated on the opposite side of the pipe as a double check.
The use of the LC Adapter Plate and Intermediate electrode extension along with an electrode
extension for the rear electrode will make the job simpler. It is important that the survey be
conducted directly over the pipeline. For this reason, a pipe locater is usually employed.
USE OF THE PUSH-TO-HOLD BUTTON
The push-button, located on the right side of the panel below the display, functions to freeze
whatever is being displayed. The holding or freezing action continues until the button is released.
This feature is especially useful in areas varying stray currents are encountered, since it is difficult
to interpret a digital read-out which is continually changing.
Some of the companies take coordinated readings at a number of locations at the same instant,
using a network of two way radios. The push-to-hold button provides an excellent way to insure
simultaneous readings. The group leader instructs each person to read this meter when he says
“mark”, at which time each person depresses his push-to-hold button until he has had time to
enter the reading on a data sheet.
Another increasingly important use for the push-to-hold button is for obtaining so-called “instant
off readings of polarized potentials on a structure. (See “Instant Off Potential Measurements).
INSTANT-OFF DC POTENTIAL MEASURMENT The criterion for adequate cathodic protection involves the
measurement of structure-to-soil potential immediately after cathodic protection is turned off. This potential
measurement is called an “instant off”, or polarized potential, since the structure has not yet had time to lose its
polarization.
The push-to-hold button enables instant measurements to be made quite easily. Just depress and hold down the button
as soon as it is perceived that the cathodic protection has been turned off. With a little practice, you can freeze within
approximately .5 seconds after cathodic protection is de-energized.
When there are several sources of cathodic protection current for a structure, all should be turned off at the same
instant if meaningful “instant-off” readings are to be obtained. This normally means that a crystal controlled current
interrupter must be installed at each cathodic installation. These should be synchronized within a fraction of a second.
IR DROP MEASUREMENTS
Because the 20mV DC range of the LC-4.5 has a resolution of .01mv, it is ideally suited for measuring IR drops on
metallic structures such as pipes, cables, guide wires, or structural members.
Before taking an IR drop reading, the circuit should be tested for continuity by use of the 200 ohm resistance range. For
accurate results on the 20mv range, the external circuit resistance should be less than 100 ohms. This should rarely
present a problem since test station wiring normally measures less than 1 ohm. The positive test lead must be on the
center terminal for the resistance test and must be moved over to the 20mV terminal for the actual IR drop
measurement. In order to avoid thermally produced errors, both of your test leads should be at the same temperature.
Do not attempt to measure IR drops in the soil using the 20mvVrange. Use the 200mV or 2mV range instead.