Designation unction Comment
9...28V Su ly voltage with olarity reversal
rotection
U/I Out Negative bridge excitation (AGND) 9...28V or 2V over the
maximum out ut signal;
Scale Control lead for Scale or "ENTER" High Active; duration as
for GSV-6CPU
Tare Control lead for "Tare" or "UP" High Active; duration as
for GSV-6CPU
TEDS In ut for TEDS as GSV-6CPU
unctions
The functions can be adjusted using the "Tare" and "Scale" control cables.
A simulator to configure the GSV-6 via control cables is also available via
htt ://www.me-systeme.de/click/click. h
unction Settings
Analogue out ut "Ty e" 0...10V, ±10V, 0...5V, ±5V, 4...20mA, 0...20mA
Analogue out ut "Offset" 0%, 10%, 12.5%, 20%, 25%, 30%, 37.5%, 40%, 50%
Exam le: an offset of 50% with an analogue out ut 0...10V shifts
the zero oint at 0 mV/V to 5V. With an out ut of 4...20mA, the
zero oint is shifted to 12mA with an offset of 50%. The in ut
sensitivity is shown at all times on the remaining "End Value -
Offset" area.
Data frequency in Hz
(U dating of measurement
values at the analogue out ut
or interface)
0.1, 0.2, 0.5, 1, 2, 10, 20, 50, 100, 200, 500, 1k, 2k, 5k, 10k, 20k,
25k;
The smallest data frequency at the out ut is 10Hz. At levels below
10Hz, a second-order IIR filter is used.
In ut sensitivity in mV/V 0.1, 0.2, 0.3. 0.4, 0.5, 1, 2, 3, 4, 5, 8 (standard mode)
0.1, 0.2, 0.3, 0.4, 0.5, 1, 2, 3, 4, 5, 8 (high-res. mode)
In high-res. mode the hysical measuring range is restricted,
which means there is less "reserve" available for a zero
adjustment with the Tare function.
Available hysical measuring ranges: 8 mV/V, 4 mV/V, 2 mV/V, 1
mV/V
The in ut sensitivity can also be set to 5-digit recision using the
Tare and Scale cables in the ClickRClackR menu ("seamless").
Adjust autoscale level The autoscale level allows the out ut signal to be defined as a %
of the end value, which is shown by im lementing "Scale" with the
current weight limit. Default setting: 100% (a weight limit of 100%
is ex ected).
The autoscale level can be adjusted in stages, from 5% within the
range 0 to 100%. When "0%" is set, the autoscale function is