Meaco LAE 2 stage controller
Control Principles
For the purposes of these instructions we are assuming that you wish to
achieve 55%RH ±5%RH.
If you require a different set point then you can changes the settings in steps
4and 9. If you require closer control then simply change the settings
accordingly in steps 6and 11.
The humidifier will come on at 50%RH and below and turn off at 55%RH.
The dehumidifier will come on at 60%RH and above and turn off at 55%RH.
This is known as the hysteresis.
If you find that either unit keeps on turning on and off too quickly you can put
in a time delay of between 1 and 30 minutes at, stages 7, 8, 12 and 13. In
the procedure below, this is set as 1. The relays within this controller can
switch loads up to 12 amps for relay 1 and 7 amps for relay 2. Larger loads
should be switched using this controller with a contactor in line.
Controller Set-up
1. Plug controller in and switch on the power.
2. Press both and buttons for 5 seconds.
3. "SCL" should now be displayed, you are ready to begin.
4. Press three times to display "1SP", then press and hold and use the buttons to enter 55.0 for the
set point. When you release 1cñ will be displayed.
5. Press button once, 1ch should be displayed, press and hold and use to select ‘ref’. When you
release 1hy will be displayed.
6. Press and hold and use to enter 5 for the hysteresis.
7. When you release 1tO will be displayed, press and hold and use to set to 1 and this is the
minimum off time in minutes.