In the Secure menu the value of
PPSSFF
is programmed for the action of the MPC
based on the condition of a seal failure. If set to "
AAUUttOO
", when pump moisture
sensor indicates that there is a seal failure condition then the corresponding pump
seal failure lamp is lit on the controller. The pump will remain in service with only the
lamp indication of failure. The lamp will be turned off automatically when the seal
failure condition has ceased.
If
PPSSFF
is set to “
rrEESS
”, when pump moisture sensor indicates that there is a seal
failure condition then the corresponding pump seal failure lamp is lit on the con-
troller. If the MPC is only being used with one pump or being used with two pumps
with the lead/lag function turned off then no action is taken by the MPC with the
operation of the pumps. The failure indication lamp will be manually reset as
described in the next paragraph. If the MPC is being used with two pumps with the
lead/lag function turned on then the failed pump will automatically become the lag
pump, the remaining pump will become the lead pump, and the alternation will be
discontinued. The lamp indication and pump alternation can be manually reset as
described in the next paragraph.
Once the pump has been repaired the seal failure action can be reset with the val-
ues of
PP11SSFF
and
PP22SSFF
in the Secondary menu. The item
PP11SSFF
or
PP22SSFF
will
display
FFAAIILL
if the corresponding pump has met the condition of a seal failure.
Press the ENTER key to reset. If the pump moisture sensor is still in the fail
condition then the control will not reset. If the moisture sensor is no longer in the fail
condition then the display will revert to “----“.
OVER TEMPERATURE OPERATION
Most pumps have an installed normally closed thermostat for over temperature pro-
tection of the pump. The thermostat has a preset value from the pump manufactur-
er at which point the pump needs to be shut down. The Mercoid MPC detects
when the thermostat signal changes to open and shuts down the pump.
In the Secure menu the value of
PPOOTT
is programmed for the action of the MPC
based on the condition of the over temperature. When the pump temperature sen-
sor indicates that there is an over temperature condition the pump will be held out of
service and the corresponding pump over temperature lamp is lit on the controller. If
using the MPC with two pumps with the lead/lag function turned on then the failed
pump will automatically be taken out of service, the remaining pump will become the
lead pump, and the alternation will be discontinued. When controlling two pumps
with the lead/lag function off the failed pump will automatically be taken out of service
and the remaining pump will be controlled by the
SSPP11HH
and
SSPP11LL
set points.
If
PPOOTT
is set to "
AAUUttOO
" then the pump will be automatically placed back into serv-
ice and the lamp turned off when the over temperature condition has ceased. If set
to “
rrEESS
” then the pump will remain out of service and the lamp lit until the corre-
sponding manual reset
PP11OOtt
or
PP22OOtt
is reset in the Secondary menu (described
in the next paragraph). The pump cannot be brought back into service until the
12