KIOUR FA3F User manual

1
FREEZER CONTROLLER Model FA3F
ATTENTION Firmware V7
Read carefully these instructions before installing and using this device and keep them for future reference. Attention to installation and electrical wiring. Use this device
only as described in this document and never use itself as a security device. The device must be disposed of in accordance with local standards for the collection of
electrical and electronic equipment.
DESCRIPTION
FΑ3F is a temperature controller for freezer cabinets with defrost control; room and evaporator temperature is controlled with NTC/PTC sensors; 3 indication digits with resolution
0.5°C and 4 buttons; one serial input for controlling the cabinet’s door; 3 relays: compressor 30Α250VAC, fan 10Α250VAC, defrost 10Α250VAC; defrosting may be electric
or by hot gas; a buzzer in case of an alarm; the device is mounted on a panel hole and it is restrained with plastic side brackets; it can connect to the monitoring and controlling
network CAMIN via serial input using an interface with MODBUS protocol.
INDICATIONS AND BUTTONS FUNCTION
For more indications regarding the alarms please see the alarm’s table at page 3.
1. Press to display the first parameter SPo.
2. Press to display its value. With or change its value.
3. Press to save the new value. The device is working properly with the new adjustment.
1. Press to display SPo. Press 3 times and the parameter Cod is displayed.
2. Press to display its value and press
to enter the value 31. Press to store the value to parameter Cod.
3. Press again to exit the parameter menu. All appropriate factory settings are now stored in the device.
1. To deactivate the device, press at the same time for more than 3 seconds.
2. To activate the device, press for 3 seconds .
Press for 3 seconds to start a manual defrost with duration based on the parameter dd2.
For more information regarding the defrost check the description of parameter dt6(parameter Νο 11 - page 2).
PROGRAMMING A PARAMETER
ATTENTION: to gain full access to the parameter’s menu, the 4th parameter Cod must be adjusted to 22 (see parameter table page 2).
1. Press to enter the parameter menu.
2. Choose the parameter you want to adjust by pressing or and press to display its value.
3. Press or to change its value and then press to store the new value.
4. Press to exit the parameter menu.
Power supply: 230VAC 50/60Hz / Maximum power consumption: 3W / Firmware: V7
It is recommended using a power supply safety fuse: 0.5Α(not included)
Room and evaporator temperature sensors NTC 10K 1% 25°C ΙΡ68 and temperature range -37÷+110°C (-34÷+230°F) (or PTC 1Κ25oC and temperature range
-50÷+110°C (-58÷+230°F) not included) / Accuracy: ±0.5°C
Alarm buzzer / Serial input with 5pin connector / Digital input door
Compressor relay 30Αres. 250VAC normally open contact / Fan and defrost relays 10A res. 250VAC normally open contact / Max current load 16Α
Connections: cable cross section 2.5 mm² for all relays / cable cross section from 0.25 to 1.0 mm² for the sensors and door switch
Connections with terminal blocks 18A using cable with cable cross section up to 2.5 mm²/ It is recommended using a torque wrench with maximum torque 0.4Nm
Operating temperature: -15÷+55°C / Storage temperature: -20÷+80°C
Dimensions 37x79x81mm / The device is mounted on panel hole 29x71mm and restrained with plastic side brackets / Protection IP65 front
FA3F can connect to the memory key or to data logger model Mini Logger or to CAMIN network:
Memory key: parameter’s values can be downloaded to the memory key or can be uploaded to the thermostat from it.
Mini Logger: the thermostat can connect to a data logger and store temperatures, relay status and alarms to a microSD. A cable is used to connect the data logger with the
thermostat and parameter Add must be adjusted to 1.
Display indications
compressor ON
fan ON
defrost ON
alarm ΟΝ
malfunction ON
Keyboard
enter/exit the parameter’s menu
display the parameter’s value
enter parameter’s value
manual defrost or manual heating with
countdown
up arrow
display evaporator temperature Τ2
OFF device (check below)
down arrow
mute buzzer
ON/OFF device (check below)
ADJUSTING TEMPERATURE –SET POINT
INDUSTRIAL FACTORY SETTINGS
ON/OFF DEVICE
MANUAL DEFROST
TECHNICAL SPECIFICATIONS
SERIAL INPUT

2
CAMIN network: the thermostat can connect via a network interface NET-INS-485 to the CAMIN network. CAMIN is a software application designed to collect data, monitor
and fully control a network of up to 250 thermostats using cable wiring. It can also send SMS and emails in case of an alarm.
ATTENTION: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it cannot
be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before proceeding to
any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges and sharp objects
from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables.
ATTENTION: Read carefully the technical specifications and make sure that the working conditions are appropriate. According to safety standards, the device must be fastened in such a way that
it cannot be removed without the use of tools.
Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets.
PARAMETER’S TABLE
No
description
min
max
FA3F
UOM
1
SΡo
SET POINT: room temperature setting
LSP
HSP
-21.0
°C/°F
2
ΑLο
Low alarm room threshold
-50.0
+110
-25.0
°C/°F
3
AHi
High alarm room threshold
-50.0
+110
0.0
°C/°F
4
Cod
Access code to the following parameters Cod = 22.
0
255
0
-
5
dFr
Defrost duration (manual and automatic), where 0 = defrost is deactivated.
0
100
6
hours
6
diF
Differential of room temperature SPo (thermostat delay)
0.1
25.5
3.0
°C/°F
7
dd2
Defrost duration (manual and automatic)
1
120
30
minutes
8
dP3
Dripping time, where the compressor is OFF after defrost.
The fan starts based on the parameters Fd3 and Fd4.
0
15
2
minutes
9
dY4
Display indication during defrost
-2 = SPo + diF value is displayed when room temperature is greater than SPo + diF
-1 = “dFr”is displayed when room temperature is greater than SPo + diF
0 = room temperature is displayed
1 to 40 minutes = “dFr”is displayed from 1 to 40 minutes from the initiation of defrost
-1
40
-1
minutes
10
dE5
Defrost end temperature
In case of deactivated evaporator sensor, defrost end temperature is the room temperature.
In case of evaporator’s sensor malfunction (LF2), there is no check of defrost end temperature and defrosting
is completed after time adjusted in parameter dd2 elapses.
0.0
100
30.0
°C/°F
11
dt6
Type of defrost
0 = electrical: compressor OFF, resistance ΟΝ
1 = hot gas: compressor ON, resistance ON
- - - - - - - - - - - -
Defrost with the evaporator’s temperature sensor ON
Automatic or manual defrost ends either with time adjusted from the parameter dd2 or with defrost end
temperature dE5, whatever comes first. Automatic or manual defrost does not start if the evaporator
temperature is greater than the defrost end temperature dE5.
Defrost with the evaporator’s temperature sensor OFF
Defrost end temperature is the room temperature.
Automatic defrost ends either with time adjusted from the parameter dd2, or with defrost end temperature
dE5, whatever comes first.
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2
elapses.
0
2
0 =
electrical
-
12
ΑF1
Alarm setting
0 = automatic OFF, where the alarm stops once the cause of the alarm disappears.
1 = manual OFF, where the alarm indication remains even if the cause of the alarm disappears and it’s
cleared only by pressing .
In any case, by pressing the buzzer stops and turns on to state that the cause of the alarm still
exists. Muting the alarm buzzer by pressing once is valid until all alarms disappear.
0
1
0 = auto
-
13
At2
Time delay in activating “AΗi”, “ΑLo” and the buzzer among them.
This setting does not apply to sensor failure and door alarm.
-01 = OFF buzzer
0 = immediately buzzer is ON
1 to 120 min = delay in buzzer activation
-01
120
0=
instant
activation
minutes
14
Fo1
Evaporator’s temperature controlling the fan operation during defrost and normal operation.
If the evaporator’s sensor is OFF, the parameter does not operate.
For more information check the parameters Ft2, Fd3 and Fd4.
-50.0
+100
-2.0
°C/°F
15
Ft2
Evaporator’s fan operation
-2 = continuously ON for evaporator’s temperature smaller than Fo1
-1 = continuously ON
0 = parallel operation with the compressor
1÷15 min = parallel operation with the compressor and when the compressor is OFF, the fan stops after the
selected minutes
-2
15
-1= ΟΝ
continuo
usly
minutes
ELECTRICAL DIAGRAM - DIMENSIONS

3
16
Fd3
Evaporator’s fan operation during defrost the with evaporator’s sensor ON (parameter οS2 = 1)
0 = OFF and starts with the compressor if the evaporator’s temperature is smaller than Fo1
1 = ON when the evaporator’s temperature is smaller than Fo1
2 = always ON in both types of defrost (electrical / hot gas)
If the evaporator’s sensor is OFF (parameter οS2 = 0), the fan is OFF during defrost and starts after timer
Fd4 has elapsed.
0
2
0
-
17
Co1
Compressor’s minimum time ON
0
15
0
minutes
18
CΡ2
Compressor’s minimum time OFF
0
15
2
minutes
19
CF3
Compressor’s operation in case of room’s sensor malfunction
-1 = compressor OFF
0 = compressor ON while defrost starts based on timer dFr and ends based on timer dd2 or temperature
dE5, whichever comes first.
1 to 150 min = compressor time ON while defrost starts based on timer dFr and ends based on timer dd2 or
temperature dE5, whichever comes first.
-1
15
3
minutes
20
CF4
Compressor time OFF in case of room’s sensor malfunction
1
150
3
minutes
21
SE1
Room sensor offset
-10.0
+10.0
0.0
°C/°F
22
SE2
Evaporator sensor offset
-10.0
+10.0
0.0
°C/°F
23
dLd
Door switch operation
0=OFF / 1=ΝCcontact.
If cabinet’s door is open during defrost for more than time tdo, defrost relay turns OFF and resumes once
door is closed. Defrost duration based on timer dd2 keeps counting from the beginning of defrost.
0
1
1= NC
-
24
LSP
Lower setting limit of SPo
-50.0
+110
-21.0
°C/°F
25
HSP
Maximum setting limit of SPo
-50.0
+110
-10.0
°C/°F
26
C_F
Temperature measurement unit: toggling between °C/°F do not adjust the SPo automatically, it must be
changed by the user
0 = °C / 1 = °F
0
1
0=°C
°C/°F
27
oS2
Evaporator’s sensor operation
0 = OFF sensor
1 = ON sensor
When the sensor is OFF, by pressing it is displayed “S--”.
For more information regarding the defrost without the evaporator’s sensor, check parameters dE5, dt6 and
Fd3.
0
1
1=
activated
-
28
tdo
Time delay in deactivating the compressor once the door is open
1
250
120
sec
29
dEC
Temperature indication as integer or decimal, where 0 = integer / 1 = decimal
0
1
1=
decimal
-
30
SEn
Sensor type NTC/PTC
0 = PTC / 1 = NTC
0
1
1=NTC
-
31
dt5
Time delay in restraining indication “dFr” (parameter dY4=-1) or indication SET POINT + diF (parameter
dY4=-2) on screen after defrost ends
Indication “dFr” disappears once room’s temperature is smaller than SET POINT + diF.
0
150
0
minutes
32
Add
Device address on network. To connect with Mini Logger enter Add=1.
0
255
1
-
33
trE
Response time of the device on network
5
100
40
msec
34
tAd
Time delay in activating door alarm “dor” once the door is open
tdo
99
0
minutes
35
tEd
Time delay in refreshing room temperature on screen once the door is open
0
255
0
minutes
36
Fd4
Time delay in activating the fan after defrost ends
and only if evaporator’s temperature is smaller than temperature Fo1 (check parameter Fd3).
0
255
0
minutes
ALARM’S TABLE
1
LF1
Room sensor malfunction
2
LF2
Evaporator sensor malfunction
3
ΑLo
Low room temperature
4
ΑHi
High room temperature
5
dοr
Open door alarm (when the cabinet’s door opens, the fan stop)
6
EEr
Error in memory RAM: re-enter the SPo (see ADJUSTING TEMPERATURE –SET POINT page 1)
The alarms are automatically deactivated once the cause of the alarm disappears.
Made in Greece.
The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician.
The guarantee covers only the replacement or the service of the device. KIOUR preserves the right to adjust its products without further notice.
392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331 [email protected] www.kiour.com
V1.0.190719
Table of contents
Other KIOUR Controllers manuals
Popular Controllers manuals by other brands

Victron energy
Victron energy BlueSolar MPPT 100/30 user manual

PENGWYN
PENGWYN 485-1P-JS Technical manual

Exalto
Exalto CT3N user manual

Wilkerson
Wilkerson R30 Series Installation & service instructions

Canon
Canon ColorPASS-GX400 INSTALLATION PROCEDURE

IFM Electronic
IFM Electronic ecomot100 ExtendedController CR0253 installation instructions