CAMIN network: the thermostat can connect via a network interface NET-INS-485 to the CAMIN network. CAMIN is a software application designed to collect data, monitor
and fully control a network of up to 250 thermostats using cable wiring. It can also send SMS and emails in case of an alarm.
ATTENTION: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it cannot
be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before proceeding to
any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges and sharp objects
from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables.
ATTENTION: Read carefully the technical specifications and make sure that the working conditions are appropriate. According to safety standards, the device must be fastened in such a way that
it cannot be removed without the use of tools.
Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets.
SET POINT: room temperature setting
High alarm room threshold
Access code to the following parameters Cod = 22.
Defrost duration (manual and automatic), where 0 = defrost is deactivated.
Differential of room temperature SPo (thermostat delay)
Defrost duration (manual and automatic)
Dripping time, where the compressor is OFF after defrost.
The fan starts based on the parameters Fd3 and Fd4.
Display indication during defrost
-2 = SPo + diF value is displayed when room temperature is greater than SPo + diF
-1 = “dFr”is displayed when room temperature is greater than SPo + diF
0 = room temperature is displayed
1 to 40 minutes = “dFr”is displayed from 1 to 40 minutes from the initiation of defrost
Defrost end temperature
In case of deactivated evaporator sensor, defrost end temperature is the room temperature.
In case of evaporator’s sensor malfunction (LF2), there is no check of defrost end temperature and defrosting
is completed after time adjusted in parameter dd2 elapses.
Type of defrost
0 = electrical: compressor OFF, resistance ΟΝ
1 = hot gas: compressor ON, resistance ON
- - - - - - - - - - - -
Defrost with the evaporator’s temperature sensor ON
Automatic or manual defrost ends either with time adjusted from the parameter dd2 or with defrost end
temperature dE5, whatever comes first. Automatic or manual defrost does not start if the evaporator
temperature is greater than the defrost end temperature dE5.
Defrost with the evaporator’s temperature sensor OFF
Defrost end temperature is the room temperature.
Automatic defrost ends either with time adjusted from the parameter dd2, or with defrost end temperature
dE5, whatever comes first.
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2
elapses.
Alarm setting
0 = automatic OFF, where the alarm stops once the cause of the alarm disappears.
1 = manual OFF, where the alarm indication remains even if the cause of the alarm disappears and it’s
cleared only by pressing .
In any case, by pressing the buzzer stops and turns on to state that the cause of the alarm still
exists. Muting the alarm buzzer by pressing once is valid until all alarms disappear.
Time delay in activating “AΗi”, “ΑLo” and the buzzer among them.
This setting does not apply to sensor failure and door alarm.
-01 = OFF buzzer
0 = immediately buzzer is ON
1 to 120 min = delay in buzzer activation
Evaporator’s temperature controlling the fan operation during defrost and normal operation.
If the evaporator’s sensor is OFF, the parameter does not operate.
For more information check the parameters Ft2, Fd3 and Fd4.
Evaporator’s fan operation
-2 = continuously ON for evaporator’s temperature smaller than Fo1
-1 = continuously ON
0 = parallel operation with the compressor
1÷15 min = parallel operation with the compressor and when the compressor is OFF, the fan stops after the
selected minutes
ELECTRICAL DIAGRAM - DIMENSIONS