
3
Fire-Link 3 Wireless Overview
2.2 ZC-301W Zone Controller (ZC)
The Zone Controller relays messages between the Wireless Input/Output unit and the Fire
Alarm Control Panel. It plugs into any 120/240 VAC receptacle and has battery backup.It
should be installed one per floor or zone and wired through either the Notification Appliance
Circuit (NAC) or Addressable Loop (SLC) connection to the Fire Alarm Control Panel. The
Zone Controller is NOT an annunciator.
Operating Frequency: 2.4 GHz
Maximum number of Zone Controllers per system: 16
2.2.1 WR-3001R/W Wireless Input/Output unit (WIO)
The Wireless Input/Output unit communicates wirelessly with the Zone Controller and drives
one notification appliance. Synchronization is NOT available between WIOs and only one WIO
shall be installed in any notification area, such as a suite within a multi-residential building. The
Authority Having Jurisdiction (AHJ) shall have the final say as to the synchronization
requirements of the particular situation. Notification devices can be audibly silenced, but
strobes may continue to flash as set-up in the system configuration. Supported notification
appliances are as follows:
•2 wire notification appliances manufactured by Mircom, System Sensor, Cooper (two
stage is not supported), and Gentex.
The Wireless Input/Output unit is powered by 120 or 240 VAC and has a backup battery.
Broadcast Frequency: 2.4 GHz
Maximum number of Wireless Input/Output units per Zone Controller is 49.
Maximum number of Wireless Input/Output units per system is 784.
2.2.2 Input Module and Relay Module
The MIX-M500MAP(A) input module connects the Zone Controller to the SLC in order to
deliver signals from the Zone Controller to the Fire Alarm Control Panel (FACP).
The MIX-M500RAP(A) relay module connects the Zone Controller to the SLC in order to
deliver signals from the Fire Alarm Control Panel to the Zone Controller. One relay module is
required, but additional modules permit trouble and further reporting.
Mircom or Secutron FACP with SLC loop do not require any Monitor or Relay Modules for
connection to the Zone Controller.
Notes: (1) The Zone Controller should be connected directly to the Fire Alarm Control
Panel.
(2) The Zone Controller is compatible with any Fire Alarm Control Panel brand
for dry contact relay connection and Mircom FleX-Net, FX-2000, FX-3500,
FX-3318 and Secutron MMX, MR-3500 and MR-3318 for addressable SLC
loop connection.
(3) The Zone Controllers should be installed one per floor and wired through
either the NAC or Addressable Loop connections to the Fire Panel.