Millenium MAS 6 RCA User manual

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 1/8
Table of contents
1. INTRODUCTION 1
2. HARDWARE DESCRIPTION 2
3. INSTALLATION 5
4. CONNECTION 6
5. USER SAFETY AND PROTECTION OF EQUIPMENT 8
1. Introduction
The MILLENIUM series has been designed for use in domestic, office and industrial applications. Each module
can be used to manage all the sensors and actuators in the installation. A display on the front panel can be used
to check the state of your system at any time.
The MILLENIUM series is characterised by :
• Ease of programming and parameter entry
• WINDOWS-based programming software
• Compact size
• EEPROM module backup
• Realtime clock as standard
• Output with high breaking capacity
The MILLENIUM series has been designed for simple automation control modules (examples : lighting, air
conditioning, irrigation, doors, barriers, simple safety systems, greenhouses, ventilation). The realtime clock
allows equipment to be programmed in hours or minutes.

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 2/8
2. Hardware description
2.1 Part numbers
Codes Part numbers Power supply Inputs Outputs Dimensions Weight
Type No. Type No. mm kg
89 750 001 MAS 6 RCA 100 - 240V AC 100 - 240V AC 4 RELAY 2
89 750 002 MAS 10 RCA 100 - 240V AC 100 - 240V AC 6 RELAY 4 71.2 x 90 x 55 0.2
89 750 003 MAS 10 RCD 24V DC 24V DC 6 RELAY 4
89 750 004 MAS 20 RCA* 100 - 240V AC 100 - 240V AC 12 RELAY 8 124.6 x 90 x 55
89 750 005 MAS 20 RCD* 24V DC 24V DC 12 RELAY 8
* Available from Q4/1999.
2.2 Description of power supplies
Description Code Specification
Power supply MAS x RCA 100 - 240V AC, +10% -15%, 50/60 Hz
MAS x RCD 24V DC, +20% -15%
Micro-cuts MAS x RCA 10ms
MAS x RCD 5ms
Current peak 240V AC ≤1.5 A t < 0.3 ms
24 V DC ≤7 A t < 0.2 ms
MAS 6 RCA, 264V AC 3 VA
Maximum consumption MAS 10 RCA, 264V AC 4 VA
MAS 10 RCD, 28.8V DC 3 W
MAS 6 RCA, 240V AC active I/O : 2.5 VA, deactivated I/O : 1.5 VA
MAS 6 RCA, 120V AC active I/O : 2 VA, deactivated I/O : 1.2 VA
MAS 10 RCA, 240V AC active I/O : 3 VA, deactivated I/O : 1.5 VA
Typical consumption MAS 10 RCA, 120V AC active I/O : 2 VA, deactivated I/O : 1.2 VA
MAS 10 RCD, 24V DC active I/O : 2 W, deactivated I/O : 0.3 W
MAS 20 RCA, 240V AC
MAS 20 RCA, 120V AC

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 3/8
2.3 Description of inputs
Description Description of AC inputs
Input voltage 100 - 240V AC, +10% -15%, 50/60 Hz
Input impedance ≥800 k Ohms
Level 0 ≤40V AC
Level 1 ≥80V AC
Response time 25 ms min, 130 ms max.
Galvanic isolation No
Status indication LCD display
Description Description of DC inputs
Input voltage 24V DC +20% -15%
Current consumption 5 mA
Level 0 ≤4V
Level 1 ≥18V
Response time 15 ms
Galvanic isolation No
Status indication LCD display
Description Description of analogue inputs
MAS 10 RCD 6 Inputs: I 01 – I 06
MAS 20 RCD 8 Inputs: I 01 – I 08
Number of bits 8
Resolution (10000 / 250) mV
Conversion time 15 +/- 5ms
Input voltage 0 - 10V DC
Input impedance 150 k Ohms max.
Precision +/- 5%
Default Offset/ Gain Offset = 0
Gain = 1
These values can be changed by the program
Temp. dependent derating +/- 3 LSB on the authorised range
2.4 Description of relay outputs
Description Description of relay outputs
Max. operating voltage 250V AC, 30V DC
Max. operating current 8A / point
Minimum load 10mA at 5V DC
Response time ≤10ms
Type of contact Gold-plated silver
Status indication LCD display
Category
of use
Max. operating
voltage
Power consumption
in steady state
Durability
(number of operations)
Max. ops /
hour
AC15 (electromagnet) 250V AC 450 VA 100000 600
DC13 (electromagnet)
(L/R = 150 ms)
30V DC 10 W 100000 360
AC14 (electromagnet) 250V AC 750 VA 100000 600
AC12 (resistive) 250V AC 2000 VA 100000 1800
DC12 (resistive) 30V DC 192 W 100000 1800

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 4/8
2.5 General description
Description Specification
Programming Logic block or function block
Program capacity 64 blocks or 1500 bytes
Program backup Via internal EEPROM or optional external EEPROM module
Data backup 20 days at 25° C (via capacitor)
Clock backup 20 days at 25° C (via capacitor)
LCD display Display unit with 4 lines of 10 characters.
Climatic conditions :
Type Standard Amplitude
Operating temperature 0/55 °C
Storage temperature -30/70 °C
Humidity 35 - 85% relative humidity, without condensation
Degree of protection IP 20
Environment No corrosive gases. Minimum dust
Mechanical protection :
Type Standard Amplitude
Resistance to vibrations
Direct mounting
JIS C0040 10- 57 Hz: 0.15 mm Constant amplitude
Acceleration 57- 150 Hz 9.8 m/ s²
X, Y, Z : 10 times (80 minutes in each direction)
Resistance to vibrations
Mounted on DIN rail
JIS C0040 10- 57 Hz: 0.07 mm Constant amplitude
Acceleration 57- 150 Hz: 4.9 m/s²
X, Y, Z : 10 times (80 minutes in each direction)
Resistance to shocks JIS C0041 Acceleration : 147m/s², duration: 11 ms
X, Y, Z : 3 times in each direction
Type Standard Amplitude
Dielectric strength EN 60730-1 3750V AC > 1 min between the following points :
Power supply terminals / input / output terminals
Between the relay outputs
Between the terminals and the DIN 43880 control box or
equivalent
Insulation resistance EN 60730-1 7 Mohm at 500V DC between the following points :
Power supply terminals / input / output terminals
Between the relay outputs
Between the terminals and the DIN 43880 control box or
equivalent
Safety class II
Certifications CE Low Voltage directive 73/23/EEC
EMC directive 89/336/EEC
UL/ cUL
Conformity UL 508
EN60730- 1
EN61010- 1
EN50081- 1
EN50082- 1
EN50082- 2

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 5/8
3. Installation
3.1 DIN rail mounting
The modules can be mounted on a 35 mm DIN rail (DIN EN 50022).
3.2 Panel mounting
Recommended diameter of fixing screws : M4.
3.3 Screw terminal connection
The end of the wire should be fitted with a ferrule.
3.4 Mounting instructions
The MILLENIUM series can be installed anywhere, but the following points should be taken
into consideration.
Do not install if : the atmosphere is excessively dusty, conductive, corrosive, gas-laden,
damp, wet or inflammable, or subject to excessive heat*, excessive shocks or vibrations.
Do not install the module in water or near any possible leaks.
Protect the module from external debris during installation.
Separate the cables and power equipment as far as possible. The MILLENIUM series module should be installed
in cabinets which adhere to standard DIN 43880.
* For sufficient module ventilation, allow a space of 10 mm between the front of the module and the cabinet door,
and likewise between the base of the cabinet and the bottom of the module.
Ref. Description of front panel
1Programming port
EEPROM backup module
2Fixing holes, ∅: 4.2 mm
3Power supply terminals
4Input terminals
5LCD display
6Menu keys
7Output terminals
8DIN rail mounting
!
MAS 10 RCA
RELAY OUTPUT
OK
AC INPUT
NC
POWER
AC 100/240V
LNNC
ESC
12 IN
3456
10
4
6
10
4
6
55 71
90
ESC
OK
REF:
MODEL:
SERIAL:
MADEINJAPAN
MAS10RCA
89750002
CROUZETAUTOMATISMES
IN 456321NCNCNL
MAS 10 RCA
RELAY OUTPUT
AC INPUTPOWER
AC 100/240V

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 6/8
4. Connection
4.1 Connection instructions
The MILLENIUM series has been designed with ease of connection in mind. A technician or
engineer with experience of national and local electrical standards should be able to connect
MILLENIUM series modules to the sensors and actuators without difficulty.
• The input and output cables should not be in the same wiring harness.
• Keep the input/output wiring harnesses well away from the power wiring harnesses.
• Use cables which are suitable for the application.
4.2 Conductor cross-section
For the inputs / outputs use conductors : 0.13 mm²- 3.31 mm² (26 - 12 AWG).
Strip back the conductor by 7 ±0.5 mm.
Undo the terminal screw to its maximum before inserting a conductor.
To be sure of correct connection, insert the wire fully in the terminal and tighten the screws.
Maximum tightening torque 0.5 Nm (5kgfcm).
Do not coat the conductor ends with tin to prevent them breaking.
4.3 Power supply
For an AC power supply, the phase should be connected to the L terminal and the
Neutral to the N terminal. Never connect the phase to the N terminal, as the user could
receive a dangerous electric shock.
For a DC power supply, the positive conductor should be connected to the ‘+’ terminal
and the negative conductor to the ‘-’ terminal.
The power supply terminals should not be connected to the other module terminals.
!
!

MAS NTR 735 A
INSTALLATION MANUAL
Simple Automation Control Module (MAS)
ntr_735a_e_mas_installation_manual.doc 07/1999 - 8/8
5. User safety and protection of equipment
• This manual contains all the diagrams and explanations which will guide the user in installing and using
MILLENIUM products correctly. This manual should be read and understood prior to use or installation.
• If you have any doubts while installing MILLENIUM products or require any further information, consult your
Crouzet distributor.
• This manual may be amended without prior notification.
This manual is intended for use by competent personnel trained in installation of this equipment as defined in the
following European directives :
Machinery (98/37/EEC)
Low voltage (73/23/EEC)
EMC (89/336/EEC).
Installation and electrical connections must be performed by a qualified technician.
This manual uses the symbols below to highlight information relating to the safety of personnel and the protection
of equipment. Where these symbols appear, the associated comments should be read and understood.
The symbols are :
• In no circumstances can Crouzet Limited be held responsible for damage arising as a result of installing or
using this equipment.
• All examples and diagrams in this manual are intended to aid comprehension. Their application is entirely the
responsibility of the user. Crouzet Limited will not accept any responsibility for actual use of this product based on
these examples.
• It is up to the user to assess the suitability of this product for his applications.
• In the event of product malfunction, the integral safety features should prevent dangerous situations.
• Never modify or repair MILLENIUM products.
• Check that MILLENIUM products comply with existing national and local standards.
The identified danger will cause material damage.
!The identified danger is liable to cause material damage.
This manual suits for next models
9
Table of contents
Popular Controllers manuals by other brands

Minleon
Minleon Multifunction Mini Controller instruction manual

Toro
Toro TMC-424 Series user guide

Bray Controls
Bray Controls 92 Series Technical manual

Siemens
Siemens SIMATIC FM 452 manual

Marshall Excelsior
Marshall Excelsior MEGR-253 Installation and operation instructions

Bosch
Bosch AMC2 Series installation manual