Mission Power Solutions Badger II User manual

Badger II Power Supply Operator’s Manual
Power Factor Corrected AC-DC Power Supply
Operator’s Manual
and
―Quick Install‖ Instructions
www.mpwrs.com
Badger
II

Badger II Power Supply Operator’s Manual
Badger II Power Supply
AC-DC Switcher
―Quick Install‖ Instructions
The Badger can be mounted on either of two sides. Use #8-32 mounting screws. Maximum penetration
should not exceed 0.18″ (4,5 mm).
Maintain 2″ (50,8 mm) clearance at either end for airflow.
Output Connections
Installing ring lugs and/or bus bars on single output card studs:
The right stud is Positive and the left stud is the Return on single output
cards.
Remove the nut and place ring lug over output stud.
Replace and tighten the nut to a torque of 10 in/lbs. Do not over-
tighten nuts.
Installing power connectors on dual output cards:
J3-A1 is Positive for output 1 (lower connector); J3-A2 is the Re-
turn. J4-A1 is Positive for output 2 (upper connector); J4-A2 is the
Return. For complete pin assignment, see page 9.
Use ITT/Cannon mating receptacle P/N DAM7W2PK87 with pins
P/N DM53745-1 or equivalent.
Installing power connectors on quad output cards:
J3 is a 16-pin Positronics power connector. For complete pin
assignment, see page 9.
Use Positronics mating connector P/N PLB16M7000 with pins
P/N MC112N.
Attach 12 AWG wire.
Output
Return
Output
J3
1
8
16 9
J3
Figure 1. Single (Maxi Module)
Output Terminals
Figure 2. Dual (Mini Modules) Output
Connector
Figure 3. Quad (Micro Modules)
Output Connector
J3/J4
Mounting the Badger II Power Supply

Badger II Power Supply Operator’s Manual
Remote Sense Connections
Sense Connections on single (Maxi Module) output cards:
The Badger II is shipped with Local Sense installed.
If Remote Sense is desired, remove jumpers JMP1 and JMP2,
located behind the sense connector. (See Fig. 4)
Connector pin J3-1 is the +Sense and J3-3 is the –Sense. (See
Fig. 6)
Use Molex mating receptacle P/N 50-57-9403 with P/N 16-02-
0103 terminals.
Attach terminals to 22-24 AWG stranded twisted pair wire.
Attach opposite end of sense lines to point where regulation is
desired.
Sense Connections on dual (Mini Module) output cards:
The Badger II is shipped with Local Sense installed.
If Remote Sense is desired, remove jumpers on JMP1 and JMP2
for output #1 (lower connector) and jumpers on JMP3 and JMP4
for output #2 (upper connector). (See Fig. 5)
Connector pin J3-3 is the +Sense and J3-5 is the –Sense for out-
put 1. J4-3 is the +Sense and J4-5 is the –Sense for output 2.
(See Fig. 7)
Use ITT/Cannon mating receptacle P/N DAM7W2PK87.
Remote Sense Connections are not available on quad (Micro
Module) output cards.
Trim Connections
Trim Connections on single (Maxi) output cards:
J3-2 provides Trim access. (See Fig. 6)
Use Molex mating receptacle P/N 50-57-9403 with P/N 16-02-0103 ter-
minals.
Attach 22-24 AWG stranded wire using Molex tool P/N 11-01-0118.
Trim Connections on dual (Mini ) output cards:
J3-4 provides Trim access for output 1 (lower connec-
tor), and J4-4 provides Trim access for output 2 (upper
connector). (See Fig. 7)
Attach 22-24 AWG stranded wire.
J3
Remove Jumpers for
Remote Sense
Output 1
Remove Jumpers for
Remote Sense
Output 2
J3
Remove
Jumpers
for
Remote
Sense
Trim Connections are not available on quad (Micro) output
cards.
Figure 4. Single (Maxi Module) Remote
Sense Jumpers
Figure 5. Dual (Mini Module) Remote
Sense Jumpers
Figure 6. Single (Maxi Module)
Trim Connections
Figure 7. Dual (Mini Module) Trim
Connections
Pin
1 N/C
2 N/C
3 +Sense
4 Trim
5 –Sense
J3/J4
J3
3 2 1
Pin
1 +Sense
2 Trim
3 –Sense

Badger II Power Supply Operator’s Manual
Input/Customer Interface Connections
Input Power Connector (J1) - See Fig. 8
Input AC power is applied to connector J1 using 3W3 Power Con-
nector
Use ITT/Cannon mating receptacle P/N DAM3W3SA197 with pins
P/N DM53744-6
A fault clearing device, such as a fuse or circuit breaker, with a
maximum 15 A rating should be used at the power supply input
Customer Interface Connector (J2) - See Fig. 9
J2-1 to 3 are Enable/Disable for output card locations 1-3,
respectively
J2-4 is Signal Ground.
J2-5 is +5 VDC
J2-6 is AC Power OK
J2-7 is General Shutdown
Use ITT/Cannon mating plug P/N DE9PK87 with Amp cover
shell P/N 205729-1
Attach terminals to 22-24 AWG stranded wire
Figure 8. Input Connector
Figure 9. Customer Interface Connector
J1 Pin Out
A1 Line
A2 Line 2/Neutral
A3 Ground
J2 Pin Out
1 E/D-1
2 E/D-2
3 E/D-3
4 Signal Ground
5 +5V Vcc @ 100 mA
6 AC Power OK
7 GSD (General Shutdown)
8 Spare
9 Spare

Badger II Power Supply Operator’s Manual
Badger II Power Supply
Power Factor Corrected AC-DC Switcher
Overview
The Badger II is a ruggedized, extremely low-profile AC-DC power supply that combines the advantages of
power factor correction, high power density, and user-selected isolated outputs. Accepting input voltages of 85
to 254 VAC, and 85 to 380 VDC, the Badger II can provide up to 1,800 watts in a package size of 2.55″H x
7.0″W x 13.75″L. The Badger II can provide up to 12 isolated outputs and is factory configured to meet user
requirements. Its inherent flexibility comes from its use of Vicor Maxi, Mini and Micro DC-DC converters.
Standard Features
Power Factor Correction: 0.99 at 115 VAC; 0.95 at 230 VAC
Universal Input: 85-254 VAC, 47-500 Hz, or 85-380 VDC
Power Output @ 45°C: up to 1,500 W at 220 VAC; 800 W at 110 VAC
Up to 12 isolated outputs
Fan cooled
Up to 1,800 W @ 35°C; 1,500 W @ 45C; 750 W @ 65C
Soft start for limiting inrush current
Conducted EMI Compliance: FCC Class B, EN 55022 B; MIL-STD-461E, CE101 & CE102
Transient Protection: MIL-STD-704E
-20, -40, or -55°C operating temperature
Active Power Factor Correction .95 min @ 120/230 Full Load
AC Power OK status signal
Output Sequencing and General Shutdown
Local Sense standard on all outputs. Remote Sense available with the removal of two jumpers
Output overcurrent protection on all outputs
Output overvoltage & overtemperature protection
Ride-through (holdup) time: 20 ms at 1,200 W
Size: 2.55″H x 7.0″W x 13.75″L
Heavy-duty rugged enclosure designed for a high shock and vibration environment
Extra cooling provided for higher output with increased altitude capability
“D” shell connectors for input and output connections; bus bars provided for output currents greater than
40 Amps
Optional conformal coating
Technical Description
The Badger II consists of an off-line single phase, power-factor-corrected front end, EMI filter, cooling fan,
customer interface, associated housekeeping circuits, and a selection of Vicor’s DC-DC converters.
Input AC mains voltage is applied to a 3-pin power connector. The input current is passed through an EMI
filter to meet conducted noise limits.

Badger II Power Supply Operator’s Manual
At start-up, inrush current is limited by a PTC thermistor. The PTC is shunted out shortly after initial power-up
by a DC bus voltage sense circuit driving a thyristor. After rectification, the input voltage is put through a boost
converter that keeps the AC input current sinusoidal and synchronized with the input AC voltage. The boost
converter delivers a regulated input to the hold-up capacitors and a high voltage backplane. The backplane sup-
plies power to the DC-DC converters that provide the desired low voltage, regulated outputs.
Voltage conversion is achieved by Vicor’s family of Zero-Current-Switching (ZCS) DC-DC converters. These
are forward converters in which the main switching element switches at zero current. This patented topology
has a number of unique attributes: low switching losses, high frequency operation (resulting in reduced size for
magnetics and capacitors), excellent line and load regulation, wide output adjustment range, low EMI/RFI
emission, and high efficiency.
At initial power-up, the Badger II outputs are disabled to limit the inrush current and to allow the DC bus po-
tential to settle out to the correct operating level. A low-power flyback converter operating with PWM current-
mode control converts the high voltage DC bus into regulated low voltage to power the internal housekeeping
circuits and DC cooling fans.
The internal housekeeping Vcc comes up within 1 second after the application of input power. Once the high
voltage bus is within operating limits, the AC Power OK signal changes its output to a TTL “1,” indicating the
input power is OK, and allows the power outputs to come up 15-30 ms later. An auxiliary Vcc output of 5 VDC
capable of sourcing up to 0.1 A is provided for peripheral use.
An output Enable/Disable function is provided by using an optocoupler to control Vicor’s DC-DC converters.
If the Enable/Disable control pin is pulled low, the optocoupler turns on and disables the output. The delay for
an output to come up when measured from release of the Enable/Disable pin is 5-10 ms. The General Shut-
down function controls all outputs simultaneously and works in a similar manner.
Power
Output
Line Filter
Rectifier
Soft Start
Circuit
Boost Converter
Output Card#1
Output Card#2
Output Card#3
PFCControl
Customer
Interface
E/DControl
Fan
Housekeeping
Power
Input
Current
Sample
Waveform
Sample
Enable/Disable Control
Power
Output
Power
Output
Figure 10. Badger II Architecture

Badger II Power Supply Operator’s Manual
Interface Connections
Input Terminal (J1)
Input AC Power is applied to connector J1 using a 3W3 power connector. J1-A1 is Line (L1), J1-A2 is Line 2/
Neutral (L2/N) and J1-A3 is Earth Ground (GND) for safety. See Figure 8 (Pg 4).
A fault clearing device, such as a fuse or circuit breaker, with a maximum 15 A rating at the power supply input
is recommended. It should be sized to handle the start-up inrush of 30 A at 115 VAC and 60 A at 230 VAC.
Customer Interface Connector (J2)
Individual outputs for slots 1 through 3 can be disabled with a logic “0” at pins 1, 2 and 3 of J2. Signal Ground
is available at pin 4. Auxiliary +5 Vcc @ 100 mA is available at pin 5. The AC Power OK at pin 6 is a logic
“1” whenever AC input power is within tolerance. All outputs can be disabled by placing pin 7 at a logic “0” by
connecting to signal ground at pin 4. Pins 8 and 9 are not used. See Figure 9 (Pg 4).
Signal Ground (J2-4)
Signal Ground on J2-4 is an isolated secondary ground reference for all J2 interfacing signals. This is not the
same as Earth Ground on input power connector J1.
Enable/Disable (J2-1 to J2-3)
The Enable/Disable control pins allow outputs to be sequenced either on or off. J2-1 through J2-3 are the con-
trol pins for output cards 1 through 3, respectively. For dual or quad output cards, all outputs in that slot are
enabled or disabled with a single control. The Enable/Disable pins should be pulled low to less than 0.7 V with
respect to Signal Ground to disable the outputs. They will source 4 mA maximum. These pins should be open-
circuited or allowed to exceed 4.5 V when enabled. Do not apply more than 5 V to these inputs at any time.
Figure 11. Enable/Disable and General Shutdown
TTL “1” (OFF)
TTL “0” (ON)
1
0
Enable/Disable Control
Badger
Vcc
5
1
7
4
J2
Disable Slot 1
General Shutdown
Signal Ground

Badger II Power Supply Operator’s Manual
General Shutdown (J2-7)
The General Shutdown (GSD) control pin on J2-7 allows simultaneous shutdown of all outputs. This pin must
be pulled down to less than 0.7 V and will source 4 mA maximum to shut down all outputs. The GSD pin
should be open-circuited or allowed to exceed 4.5 V when not in use, or when the outputs are to be enabled.
Do not apply more than 5V to this input at any time. Normal open-circuit voltage is 1.5-3 V with respect to
Signal Ground.
AC OK (J2-6)
AC OK is an active high TTL-compatible signal and provides a status indication of the AC input power. It is
on pin J2-6 and is capable of sinking 16 mA maximum. This signal switches to a TTL “1” when the high volt-
age bus exceeds low-line condition during turn-on. Upon loss of input power, the bus voltage will drop, caus-
ing the AC OK signal to go low. A minimum of 3 ms holdup time is provided for a 1,200 W load following
the loss of the AC OK signal.
+5V
AC OK’ 2.5K
PN2222
J2-6 AC Power OK
J2-4 Signal Ground
Figure 12. AC OK Output Circuit
Auxiliary Vcc +5V/0.1A (J2-5)
The Vcc on J2-5 is an auxiliary 5 V regulated power source. It is +5 VDC ±5% with respect to Signal
Ground and can supply 100 mA maximum. It is short-circuit-proof, but if shorted, all outputs will shut down
through the Enable/Disable circuitry.
J2-5 Auxiliary Vcc
J2-4 Signal Ground
0.1 uF
+5V/100mA
78M05
Figure 13. Auxiliary +5V Vcc

Output/Customer Interface Connections
Figure 14. Output Connections for Single Output Cards
There are three types of output power terminals available in the Badger II. Outputs from Maxi converters
(single output cards) are terminated in two 10-32 stainless steel studs (see Fig. 14). The positive polarity of the
output is the right stud when viewed from the output end. Outputs from Mini converters (dual output cards)
terminate in a 7W2 connector (see Fig.15). Each power output is isolated, so outputs of positive or negative
polarity can be configured through proper selection of the output reference terminals. Outputs from three or
four Micro converters (quad output cards) terminate in a 16-pin Positronics connector (see Fig. 16).
In order to minimize parasitic cable inductance and reduce EMI, the output power cables should be routed in
close proximity to one another, and large current loops should be avoided. To avoid excessive voltage drop, do
not undersize power cables, especially for high current outputs. Excessive cable inductance, coupled with large
capacitive loading, can introduce instability in switching power supplies. This problem can be avoided with
proper system design. Consult Mission Power Solutions’ Engineering Department for assistance with applica-
tions that use long cable lengths and excessive load capacitance.
J3 & J4 (Dual) Pin Assignments
A1 +Output
A2 Output Return
1 N/C
2 N/C
3 +Sense
4 Trim
5 –Sense
Figure 15. Output Connections for
Dual Output Cards
J3 (Quad) Pin Assignments
1 +Out 1 9 +Out 1
2 –Out 1 10 –Out 1
3 +Out 2 11 +Out 2
4 –Out 2 12 –Out 2
5 +Out 3 13 +Out 3
6 –Out 3 14 –Out 3
7 +Out 4 15 +Out 4
8 –Out 4 16 –Out 4
J4
J3 Output 1
Output 2
Pin 1
J3
Pin 9
Output
Return Output
J3
J3 Pin Assignments
1 +Sense
2 Trim
3 –Sense
Badger II Power Supply Operator’s Manual
Sense Connections
The Badger II is shipped from the factory with Local Sense installed. If Remote Sense is desired, the Local
Sense jumpers can be removed for individual outputs. If the Local Sense jumpers are removed, the sense lines
must be connected at the load for Remote Sense. Leaving the sense lines open will prevent proper output
regulation and can result in damage to the unit.
When Local Sense is used, the power supply will regulate the output at the output terminals. The voltage ap-
pearing at the load may drop slightly due to voltage drop in the power cables. If it is necessary to compensate
for voltage drop along the output power cables, the output can be trimmed up or configured for Remote Sense.
Use stranded twisted pair 22-24 AWG wire for the Remote Sense lines. Remote Sense can compensate for a
voltage drop of up to 0.5 V, or 0.25 V on each leg.
Output Connections
Figure 16. Output Connections for Quad Output Cards

Badger II Power Supply Operator’s Manual
Installing Remote Sense requires the Local Sense jumpers to be removed (see Figures 4 and 5, Pg 3). On single
output cards, the Local Sense jumpers are located behind the sense connector on JMP1 and JMP2. To remove the
jumpers, make certain the power to the supply is off, and pull them off connectors JMP1 and JMP2. On dual out-
put cards, the Local Sense jumpers are on either side of the card at JMP1and JMP2 for Output 1, and at JMP3
and JMP4 for Output 2.
The sense connector for a single output card is a 3-pin connector providing the +Sense connection on J3-1 and
the –Sense connection on J3-3. The sense connections for a dual output card are incorporated into the 7W2 D-
shell connector(s) that also provide the output and trim connection(s). +Sense is pin 3 of each connector,
and -Sense is pin 5 of each connector.
Figure 17. Remote Sense Connections
+Out
Load
+Sense
–Sense
–Out
Use 22-24 AWG
Twisted Pair
Wire
External Trim
The trim pin at J3-2 (single output) or J3-4, J4-4 (dual output) is referenced to the -Sense pin and can be used
for external control of the output voltage. A 10% increase to the trim pin voltage will result in a 10% increase
in output voltage. Reducing the trim pin voltage by 10% will result in a 10% decrease in output voltage.
Note: Converters are sometimes pre-trimmed at the factory if a nonstandard output voltage is requested. If a
non-standard voltage is requested, or when trimming below 5 V, consult Mission Power for assistance.
Figure 18. External Trim
–Sense
Trim
+Sense
–Out
Use 22-24 AWG Twisted Pair Wire for
Sense Connections
VREF
REF
REF
10-300Ω
To Error
Amplifier
20-200Ω
RTH
+
V2
–
Load
+
V1
–
R1
R2
R3
R5
R4
R8
R6
R7
+Out

Example: 10% trim adjust on a 12 V nominal output.
Figure 18 shows a typical variable trim circuit. Using a 1k trimpot (R7), the resistor values for R6 and R8 can
be calculated as follows:
V1 =Vref + 10% = 1.353V
Given: Vref = 1.23V
IR5 = (1.353V - Vref)/RTH = (1.353V –1.23V)/1k= 122A Given: RTH = 1k
Setting the bottom limit:
VR6 = 1.23V –10% = 1.107V
And since IR5 = IR6 = 122A,
R6 = VR6/IR6 = 1.107V/122A = 9.074k
V2= V1+ VR6 = 1.353V + 1.107V =2.46V
IR7 = V2/R7 = 2.46V/1k= 2.46mA
IR8 = IR7 + IR6 = 2.58mA
VR8 = (Vnom + 10%) –V2= 13.2V –2.46V = 10.74V Given: Vnom = 12V
R8 = VR8/IR8 = 10.74V/2.58mA = 4.162k
Badger II Power Supply Operator’s Manual
Output Module VREF RTH
Standard Vicor Maxi, Mini, Micro 1.23 V 1 kΩ
Special Module 1.23 V Consult MPwrS

Badger II Power Supply Operator’s Manual
Mechanical Considerations
The Badger II can be mounted on either of two surfaces using standard 8-32 size screws. Maximum allowable
torque is 20 in/lbs., and the maximum penetration is 0.18 in. (4.5 mm).
When selecting a mounting location and orientation, the unit should be positioned so airflow is not restricted.
Maintain a 2″ (50,8 mm) minimum clearance at both ends of the Badger II, and route all cables so airflow is not
obstructed. The power supply draws air in at the fan/AC input side and exhausts air out the load side. If airflow
ducting is used, avoid sharp turns that could create back pressure. The fans move approximately 75 CFM of air.
Avoid excessive bending of output power cables after they are connected to the output terminals. For high-
current outputs, use cable ties to support heavy cables and minimize mechanical stress on connectors. Be care-
ful not to short out to neighboring outputs. The maximum torque recommended on output nuts is 10 in/lbs.
Badger II Do’s and Don’ts
Run the output (+/) power cables next to each other to minimize inductance.
Insert proper fault protection at power supply input terminals (i.e., a fuse).
Use proper size wires to avoid overheating and excessive voltage drop.
Do not attempt to repair or modify the power supply in any manner.
Do not restrict airflow to the unit. The cooling fan draws air into the unit and forces it out at the output
power terminals.
If sense jumpers are removed, do not leave sense lines open. Use twisted pair 22-24 AWG wire when
installing Remote Sense.

Badger II Power Supply Operator’s Manual
Mechanical Drawing
7.00
13.75.19
2.389.000
MOUNTING LOCATIONS
8-32 UNC-2B
.180 MAX. DEPTH
QTY = 2
STATUS/CONTROL
CONNECTOR J2
2.55
AC INPUT CONNECTOR J1
2X .50
.65
J1
L1 L2/N
WARNING
SEE P RO DU CT
LABEL
J2
REAR VIEW
OUTPUT VIEW
TYPICAL
2X 2.382X 9.000
2X 1.00
2X 5.000
(7.00)
(13.75)
(2.55)
OUTPUT
SLOT 1 OUTPUT
SLOT 2 OUTPUT SLOT 3
-OUTPUT STUD
+OUTPUT STUD
OUTPUT
SLOT 1
REAR VIEW
OUTPUT VIEW
OPTIONAL
QUAD OUTPUT SLOT
ACCOMMODATES 3 OR4
MICRO MODULES
OUTPUT
SLOT 2 OUTPUT
SLOT 3
2X .50
9.000 2.38
MOUNTING LOCATIONS
8-32 UNC-2B
.180 MAX. DEPTH
QTY=2
MOUNTING LOCATION
8-32 UNC-2B
.180 MAX. DEPTH
QTY = 4
PIN A1
4-40 JACKSCREW TRIM AND REMOTE
SENSE CONNECTOR J3 PIN 1
4-40 JACKSCREW
+OUTPUT PIN
-OUTPUT PIN
4-40 JACKSCREW
-OUTPUT PIN
+OUTPUT PIN
DUAL OUTPUT SLOT
ACCOMMODATES 1 OR 2
MINI MODULES
J3
AIR BLOCK
J3 PIN 9

Badger II Power Supply Operator’s Manual
(Typical at 25C, nominal line and 75% load, unless otherwise specified)
Number of Outputs 1-12
Efficiency 80%, typical (depends on output V & I)
Safety Approvals None
Maximum Output Power @ 35°C 800 W @ 110 VAC/VDC
1,800 W @ 220 VAC/VDC
Product Weight 10.0 lbs.
Dimensions 2.55"H (64,8mm) x 7.0"W (177,8mm) x 13.75"L (349,3mm)
Warranty 1 Year Limited
General
Input
Input 85-254 VAC, 47-500 Hz
85-380 VDC
Line Regulation 0.2% from 10% load to full load
Inrush Current 30 A rms max @ 110 VAC
60 A rms max @ 220 VAC
Ride-Through Time 20 ms at 1,200 W load
EMI—Conducted Emissions FCC Class B, EN 55022 Class B
MIL-STD-461E CE101, CE102
EMI—Conducted Susceptibility MIL-STD-461E CS101, CS114, CS115, CS116
Power Factor 0.99 (115 VAC, 800 W load)
0.95 (230 VAC, 1,200 W load)
Dielectric Withstand Primary to Chassis GND = 2,121 VDC
Primary to Secondary = 4,242 VDC
Secondary to Chassis GND = 500 VDC
Output
Parameter MIN. TYP. MAX. UNITS NOTES
Setpoint Accuracy 0.5 1 % of VNOM
Load/line Regulation 0.02 0.2 % of VNOM 0% to 100%
Temperature Regulation 0.002 0.005 %C 20 to 65C
Long Term Drift 0.02 %1 k hours
Output Ripple –pp:
≤5 V 100 mV 20 MHz bandwidth
≥12 V 1 % 20 MHz bandwidth
Trim 10 110 % of VNOM
Total Remote Sense Compensation 0.5 Volts 0.25 V max each leg
OVP Set Point 112 135 % of VNOM Recycle power
Current Limit 102 135 % of Imax Automatic restart
Over-Temperature Protection 70 C Varies with power level
Specifications

Badger II Power Supply Operator’s Manual
Environmental
MIL-STD 810E
Storage Temperature
Industrial Grade 55C to 125C
Military Grade 65C to 125C
Commercial Grade 40C to +125C
Operating Temperature
Industrial Grade, Full Power 40C to 45C
Industrial Grade, Half Power 40C to 65C
Military Grade, Full Power 55C to 45C
Military Grade, Half Power 55C to 65C
Commercial Grade, Full Power 20C to +45C
Commercial Grade, Half Power 20C to +65C
Product Weight 7.0 lbs.
Storage Temperature
C-Grade 40C to 125C
T-Grade 40C to 125C
H-Grade 55C to 125C
M-Grade 65C to +125C
Max Operating Temperature Range (See temperature derating chart on next page)
C-Grade 20C to +65C
T-Grade 40C to 65C
H-Grade 40C to 65C
M-Grade 55C to 65C
Humidity 95%, non-condensing (conformal coating available)
Altitude
Operational Full power to 20,000 ft (6,000 m)
Non-operational 40,000 ft (12,000 m)
Shock MIL-STD-810E, Method 516.4, Fig 516.4-4
Functional 40 g, 11 ms
Crash Safety 75 g, 6 ms
Vibration MIL-STD-810E, Method 514.4, Category 10, Figs 514.4-16 & -17
Random 20-1000 Hz @ 0.04 g2/Hz; 2 kHz @ -6 dB/octave; 7.7 grms
Sine 5-14 Hz @ 0.2"; 14-33 Hz @ 2 g;
33-52 Hz @ 0.036"; 52-500 Hz @ 5 g
Badger II Output Power vs. Input Voltage
Do not exceed maximum power rating vs. temperature. See table on next page.

Badger II Power Supply Operator’s Manual
Maximum Output Power vs. Temperature
@ 35°C @ 45°C @ 65°C
Total Badger Power* 1,800 W 1,500 W 750 W
Total Power per Slot 600 W 500 W 250 W
Total Power per Module
Single Output Card (Maxi)
≤5 V 80A 80 A 40 A
≥12 V 600 W 500 W 250 W
Dual Output Card (Mini)
≤5 V 40 A 40 A 20 A
≥12 V 250 W 200 W 100 W
Quad Output Card (Micro)
≤5 V 20 A 20 A 10 A
≥12 V 150 W 150 W 75 W
*Do not exceed maximum power rating vs. input voltage. See graph on previous page.

Badger II Power Supply Operator’s Manual
Notes
Table of contents
Popular Power Supply manuals by other brands

Agilent Technologies
Agilent Technologies 6622A Service manual

Pentair
Pentair C20 installation guide

DeWalt
DeWalt XR FLEXVOLT DCB500-QS Original instructions

Eaton
Eaton MTL 9491-PS instruction manual

TDK-Lambda
TDK-Lambda 802 Series Operator's manual

Oxford Instruments
Oxford Instruments TC948 instruction manual