MITOS VT6 HVAC User manual

CONTROLMODESMITOSVT6HVACterminalcanbeusedtosettheSET
POINTofinverterPIDblockandtocontrolmotorRUNandSTOP,elseitcanbe
usedassimpledisplayonly.Byusingcmodandfmod parametersitis
possibletoestablishthelevelofcontrolasfollowing:
ModelVF‐Nc3VF‐S15VF‐Mb1VF‐FS1VF‐AS1VF‐PS1
Controlstart/stopby
MITOSVT6HVAC
Cmod=2
Fmod≠3
Cmod=2
Fmod≠4
Cmod=2
Fmod≠4
Cmod=2
Fmod≠4
Cmod=2
Fmod≠5
Cmod=2
Fmod≠5
SetthePIDSetpoint
byVT6HVAC
Cmod≠2
Fmod=3
Cmod≠2
Fmod=4
Cmod≠2
Fmod=4
Cmod≠2
Fmod=4
Cmod≠2
Fmod=5
Cmod≠2
Fmod=5
TotalcontrolbyVT6
HVAC
Cmod=2
Fmod=3
Cmod=2
Fmod=4
Cmod=2
Fmod=4
Cmod=2
Fmod=4
Cmod=2
Fmod=5
Cmod=2
Fmod=5
CONFIGURATION MENU
CONFIGURATIONMENUOPTIONS
RotatiopnsenseForwardRUN
ReverseRUN
Selectthemotorrotationdirection
whenSTARTkeyispressed
ReleaseDisplaythefirmwarerelease
SetKparameter20‐5000Itselectaconvertingfactorbetween
Pressure(variousunits)andFLOW
(m3/h)tobedisplayedinAUTOmode
SetCparameter0‐5000Itsetthepressure/temperature
transducermaxvalue
Speedunit4Hz,RPM,m/min,
‐‐‐
Selectsthespeedunittobedisplayed
inmodeMAN(useF702forscaling)
Manualvariable3Real,h,AmpereInMANmodeselectsthesecond
variabletobedisplayed
Unitselection1BAR,mBAR,PA,kPA,
mmH2O,m3/h,m3/min,
l/h,l/min,°C,°F,‐‐‐
SelectthemainUNITinAUTOmode
SelectLanguageITALIAN,ENGLISH,
SPANISH,GERMAN
StorageSetON/OFFIfON,afterswitchingoffthelastSet‐
pointvalueisstored.IfOFF,thevalueis
alwaysresetted.InMANmodethis
parameterconcernsthespeedset.
Transparent
mode
ON
OFF
IfON,MITOSVT6isusedasasimple
displayonlywithnopossibilityto
controltheinverter
SETTINGOFCONFIGURATIONMENUValuesonconfigurationmenucanbe
selectedthrougharrowkeys.ValuescanbechangedbyusingSTARTand
MAN/AUTOkeys.ToexitconfigurationMENUuseSTOP/RESETkey.
AUTOMODE
InAutoModethefirstlineofdisplayalwaysshowthePIDSetpointintheunitthat
hasbeenselected(1).Secondlineshowsthefeedbackvariable.Ifthesetpointis
expressedaspressurevariable,thefeedbackcanbeeitherpressureorflowand
calculatedbymultiplyingthesquarerootofpressurefortheparameterK(2).IfK
isdifferentfromzero,thefeedback(REAL)willbedisplayedasFLOW.
CHANGINGTHEPIDSETPOINTIfMITOSVT6HVACisusedforchangingthesetpoint
ofPID,byusingarrowskeysitwillbepossibletomodifythesetpoint.Ifanother
method(selectedbyFmod)isusedforchangingthesetpoint,thedisplayedvalue
willbeonlyreadone.
MONITORMODEPressingtheMONkeyitcouldbeshownalternativelyto
SETPOINTadifferentvariablechoosingfromPower(powerrequestedfromline),
Freq.(actualfrequency),Iout(outputcurrent),Vin(inputvoltage),Vout(output
voltage),Et1‐4(lastalarms),Cnt(totalworkinghours)
EMERGENCYMANUALMODE
WhenmotorisnotrunningitispossibletoswitchfromAUTOto
MANUALmodebypressingtheMAN/AUTOkeyandkeepitholdfor3
sec..Inthismode,independentlyfromcmodandfmodsetting,
VT6HVACcompletelycontrolsthemotor;startandstopismanaged
throughSTARTandSTOP/RESETkeysandmotorspeedischangedby
arrowkeys.Thevariabletobeshowninsecondlineofdisplaycanbe
selectedbythe“manualvariable”(3)fromconfigurationmenu.The
measureunitforspeedcanbeselectedthroughthe“Speedunit”(4)
variableinconfigurationmode.Thedisplayedvalueofspeedcanbe
convertedbyamultiplyingfactorusingf702 inverterparameter.
Advancedcontrolterminal
forTOSHIBAinvertersinHVAC
applications
Multilanguage
RS485orTTLinterfaceselectable
Customizablefrontlayout
Pressuresandtemperaturesselectableunits
Emergencymanualmode
Accesstosettingmenuisdoneby
contemporarypressingofthesekeysat
switchingon.
MITOSVT6HVAC

SAFETYINFORMATIONS
Mandatory
Alwaysreadcarefullythismanualbeforeinstallingand
operatingMITOSVT6HVACcontrolpanels
Warning
Alwaysdeliveryacopyofthismanualtoenduserof
inverterormachine
Danger
MITOSVT6HVACtransfersserialcommunication
commandstoTOSHIBAinverters.Incaseoffailureor
missingcommunication(orforcommunicationcable
breakage)itmightbeimpossibletostopthemotor.
Alwaysuseasafesystemtostopthemotor.
Safetyprecautions
MITOSVT6HVACcan’tbeusedinanydevicethatwould
presentdangertohumanbodyorfromwhichmalfunction
orerrorwouldpresentadirectthreattohumanlife.
Thisproductwasmanufacturedunderthestrictest
qualitycontrolsbutifitistobeusedincritical
equipmentsafetydevicesmustbeinstalledonthe
equipment.
Thismanualmaybechangedwithoutpriornotice.
EXTERNALDIMENSIONS
FITTINGHOLEONCONTROLPANEL
CONNECTION
MITOSVT6HVACcanbeusedwithfollowingTOSHIBAinverters:
VF‐Nc3,VF‐S11,VF‐S15,VF‐Mb1,VF‐FS1,VF‐AS1eVF‐PS1.
ConnectioncanbemadewithastandardRJ458wirescable“pin
topin”.
ForVF‐S11invertersthecommunicationportusedisstandardTTL.
InvertersVF‐Nc3,VF‐S15,VF‐Mb1,VF‐FS1,VF‐PS1eVF‐AS1,canbe
connectedthroughRS485serialportallowinglongdistance
communicationcables.Theconnectionmethodcanbeselectedby
twomicroswitchesonVT6HVACback:
FUNCTIONOFKEYS
120 mm
65 mm
55
31
36
Externaldimensions
ofMITOSVT6HVAC
areexactlysameof
previousmodel
MITOSVT5eco
107 mm
56 mm
Startsthe
motorifmotor
controlis
selected
throughMITOS
VT6HVAC
By3sec.
pressurewith
stopped
motoritcan
switchfrom
AUTOtoMAN
modeandvice
versa
InAUTOmode
arrowssetPID
SETPOINT.In
MANmode
arrowssetthe
outputinverter
frequency.In
MONmodesome
monitorvalues
canbedisplayed
Enterthe
MONitor
mode
Stopthemotorif
controlis
selectedthrough
MITOSVT6HVAC.
Resetinverter
alarms.
ON
1 2
ON
1 2
VF-Nc3
VF-S15
VF-Mb1
VF-FS1
VF-PS1
VF-
A
S1
VF-S11
MITOSVT6HVAC
Other MITOS Control Panel manuals
Popular Control Panel manuals by other brands

Truma
Truma CP plus installation instructions

Wilo
Wilo Control Booster CC Installation and operating instructions

Frick
Frick QUANTUM Operation manual

Haes
Haes ELAN HS-5200 Installation and programming manual

Alde
Alde 3010 613 Operating & installation instructions

American Standard
American Standard ACONT900AC43UA Installer's guide