MITOS VT6 CONTROL MODES
Several control modes can be selected. MITOS VT6 can
be used to start/stop the motor, change its direction,
modifyits speed, or else, simplyused as a remote
display with no inverter control capability. Refer to
following table for selecting MITOS VT6 control mode
depending on inverter model:
On VF-NC3 e VF-S15, set F802=1 and F829=1
On VF-AS3, set F802=1 and F827=1
CONFIGURATION MENU
Bypressingthesekeystogetherat
startup,theVT6configuration
menuisentered.
MENU CHOICES
Use arrow keys to move inside the Menu. Use the FWD
and REV keys to make the selections and
STOP/RESET keyto exit the configuration menu.
With this menu is possible to select and monitor:
▪Enabling of FWD and REV keys: Use the
FWD/REV keyto enable or disable one or both
keys.
▪Transparent mode: VT6 just used as display
▪Reset Frequency: if ON and frequencycontrol
mode by VT6 is selected then the Set frequency
is not automatically stored and every time
inverter is OFF the frequency value is reset. If
OFF, the last set frequency is always stored.
▪Select language (English, Italian, Spanish,
German, Russian)
▪Unit Selection of standard display suffix (select
between Hz, RPM, m/min, m/sec ---- “none”)
▪C Parameter: The scaling factor of the output
frequency(Freq.) shown on MITOS(0-200)
▪Indication of Software release
MITOS VT6 MONITOR
This is the standard
monitor display for
VT6.
If inverter is in RUN mode (motor running) the standard
monitor display will show an animated arrow () on the
top right-hand corner. The arrow will turn CW if the
inverter receives a RUN FWD command and will turn
CCW if the inverter receives a RUN REV command.
By pressing MON key the second line item can be
changed between several variables:
output frequency, reference frequency, output
current, input voltage, output voltage, last 4
alarms, total working time.
In “standard monitor display”, if the VT6 is in
frequency control mode and transparent mode is not
active, the inverter output frequency can be changed
directly by pressing:
▪Multilanguage capability
▪RS485 and TTY selectable interface
▪Customizable front layout
▪aSuitable for inverter control nd
monitoring