MEES19K116
PUHY-M-YNW-A1, EM-YNW-A1
2
1. SPECIFICATIONS Y-Series
I.Y-Series1. SPECIFICATIONS
Model PUHY-M200YNW-A1 (-BS)
Power source 3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity *1 kW 22.4
(Nominal) kcal/h 20,000
BTU/h 76,400
Power input kW 4.72
Current input A 7.9-7.5-7.2
EER kW/kW 4.74
SEER kW/kW -
Temp. range of Indoor W.B. 15.0~24.0°C (59~75°F)
cooling Outdoor D.B. -5.0~52.0°C (23~126°F)
Heating capacity *2 kW 25.0
(Max) kcal/h 21,500
BTU/h 85,300
Power input kW 5.08
Current input A 8.5-8.1-7.8
COP kW/kW 4.92
(Nominal) *3 kW 22.4
kcal/h 19,400
BTU/h 76,400
Power input kW 4.33
Current input A 7.3-6.9-6.6
COP kW/kW 5.17
SCOP kW/kW -
Temp. range of Indoor D.B. 15.0~27.0°C (59~81°F)
heating Outdoor W.B. -20.0~15.5°C (-4~60°F)
Indoor unit Total capacity 50~130% of outdoor unit capacity
connectable *8 Model/Quantity M20~M140/1~8
Sound pressure level (measured in anechoic room) *4, 5 dB <A> 58.0/59.0
Sound power level (measured in anechoic room) *4 dB <A> 75.0/78.0
Refrigerant Liquid pipe mm (in.) 9.52 (3/8) Brazed
piping diameter Gas pipe mm (in.) 22.2 (7/8) Brazed
FAN Type x Quantity Propeller fan x 1
Air flow rate m3/min 170
L/s 2,833
cfm 6,003
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92 x 1
*6 External static press. 0 Pa (0 mmH2O)
Compressor Type Inverter scroll hermetic compressor
Starting method Inverter
Motor output kW 3.5
Case heater kW -
Lubricant MEL46EH
External finish Pre-coated galvanized steel sheets (+powder coating for -BS type)
<MUNSELL 5Y 8/1 or similar>
External dimension H x W x D mm 1,858 (1,798 without legs) x 920 x 740
in. 73-3/16 (70-13/16 without legs) x 36-1/4 x 29-3/16
Protection devices High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP./FAN) Over-heat protection, Over-current protection
Compressor -
Fan motor -
Refrigerant Type x original charge R32 x 6.5 kg (15 lbs)
Control LEV and HIC circuit
Net weight kg (lbs) 222 (490)
Heat exchanger Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Defrosting method Auto-defrost mode (Reversed refrigerant cycle, Hot gas)
Drawing External WKL94T604
Wiring WKE94G770
Standard attachment Document Installation Manual
Accessory -
Optional parts Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes: Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B./24°CW.B. (95°FD.B./75°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°C D.B. (68°F D.B.), Outdoor: 7°C D.B./6°C W.B. (45°F D.B./43°F W.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
3.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°C D.B. (68°F D.B.), Outdoor: 7°C D.B./6°C W.B. (45°F D.B./43°F W.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.Cooling mode/Heating mode
5.The sound pressure level measured by the conventional method in JIS for reference purpose.
6.External static pressure option is available (30 Pa, 60 Pa, 80 Pa/3.1 mmH2O, 6.1 mmH2O, 8.2 mmH2O).
Consult your dealer about the specification when setting External static pressure option.
7.R32 is flammable, and certain restrictions apply to the installation of units.
When installing new units, moving the existing units, or changing the layout of the room,
ensure that installation restrictions are observed.
For detail, refer to the section in the Databook on installation restrictions.
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
subject to rounding variation.
0000005519.BOOK 2 ページ 2019年10月25日 金曜日 午前10時53分