2 SPECIFICATIONS
2.3 Function List 17
2
2.3 Function List
The following table lists the functions of the multiple input module.
V: Voltage, I: Current, mV: Micro voltage, TC: Thermocouple, RTD: Resistance temperature detector
: Available, : Not available
Item Description Input type Reference
V I mV TC RTD
Temperature conversion function By connecting a thermocouple or resistance
temperature detector, the temperature data is
converted and stored in the remote register.
Voltage/current/micro voltage conversion
function
A voltage of -10 to 10V, current of 0 to 20mA, and
micro voltage of -100 to 100mV are converted and
stored in the remote register.
Input type/range setting The input type and input range that are to be used
can be selected for each channel.
Page 59 Input
Type/Range
Setting
Conversion
method
Sampling processing Analog input values and temperature input values
are converted at every conversion cycle and
stored in the remote register as digital output
values.
Page 61
Sampling
processing
Averaging
processing
Time average The conversion is performed for a set period of
time and averaging processing is performed on the
total value excluding the maximum and minimum
values. The values obtained in averaging
processing are stored in the remote register.
Page 61 Time
average
Count
average
The conversion is performed a set number of times
and averaging processing is performed on the total
value excluding the maximum and minimum
values. The values obtained in averaging
processing are stored in the remote register.
Page 61
Count
average
Moving
average
The average of a specified number of digital output
values that are imported at every conversion cycle
is calculated and stored in the remote register.
Because the target range for averaging processing
is moved in response to every conversion cycle,
the latest digital output value can be obtained.
Page 62
Moving
average
Disconnection detection function This function outputs an alarm at disconnection
detection of the external wiring (resistance
temperature detector, thermocouple, conducting
wire, or auxiliary conducting wire), provided that
the input type is a micro voltage, thermocouple, or
resistance temperature detector.
Page 64
Disconnection
Detection
Function
Input signal error detection function This function outputs an alarm if an analog input
value exceeds a preset range, provided that the
input type is voltage or current.
Page 70 Input
Signal Error
Detection
Function
Cold junction temperature compensation setting
function
By selecting the setting with or without cold
junction compensation using the built-in
temperature sensor in the multiple input module,
two types of cold junction compensation including
a temperature sensor and external (ice bath) can
be conducted.
Page 68 Cold
Junction
Temperature
Compensatio
n Setting
Function
Error notification function When an error, warning, or alarm occurs, the
occurrence of the error, warning, or alarm is
notified to the master station using remote input
signals and remote register.
Page 77 Error
Notification
Function
CC-Link IE Field Network diagnostic function This function allows the presence or absence of a
network error to be checked by accessing the
engineering tool connected to the CPU module.
Page 80 CC-
Link IE Field
Network
Diagnostic
Function