Mitsubishi FX3U-485ADP(-MB) User manual

JY997D26301A
Safety Precaution
(Read these precautions before use.)
This manual classify the safety precautions into two categories:
and .
Depending on circumstances, procedures indicated by may also be
linked to serious results.
In any case, it is important to follow the directions for usage.
Associated Manuals
How to obtain manuals
For the necessary product manuals or documents, consult with the Mitsubishi
Electric dealer from where you purchase your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specification details for I/O,
wiring, installation, and
maintenance.
FX3U/FX3UC Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming
for basic/applied instructions
and devices.
FX Series User’s
Manual
- Data Communication
Edition
JY997D16901
MODEL CODE:
09R715
Explains N:N link, parallel
link, computer link, no
protocol communication by
RS instructions/FX2N-232IF.
FX3U Series User’s
Manual
- MODBUS Serial
Communication Edition
JY997D26201 Explains the MODBUS serial
communication network.
Certification of UL, cUL standards
The FX3U-485ADP-MB unit supports UL and cUL standards.
UL, cUL file number :E95239
Compliance with EC directive(CE Marking )
This document does not guarantee that a mechanical system including this product will
comply with the following standards.
Compliance to EMC directive of the entire mechanical system should be checked by
the user / manufacturer. For more details please contact the local Mitsubishi Electric
sales site.
Requirement for Compliance with EMC directive
The FX3U-485ADP-MB is compliant through direct testing (of the identified standards
below) and design analysis (through the creation of a technical construction file) to the
European Directive for Electromagnetic Compatibility (89/336/EEC) when used as
directed by the appropriate documentation.
Caution for compliance with EC Directive
Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and used
within conductive control boxes. Please use the FX3U Series programmable logic
controllers while installed in conductive shielded control boxes. Please secure the
control box lid to the control box (for conduction). Installation within a control box
greatly affects the safety of the system and aids in shielding noise from the
programmable logic controller.
1. Outline
The FX3U-485ADP-MB communication special adapter (hereinafter called 485ADP-
MB) is a special adapter for RS-485 communication with a terminal block (European
type).
485ADP-MB is an isolated signal exchange unit of RS-485 serial data communication
between the PLC and RS-485 device.
The FX3U-485ADP-MB features all functionality that is available with the FX3U-
485ADP, except that it also has MODBUS communication available.
1.1 Communication Function
Standard Remark
EN61131-2:2003
Programmable controllers
- Equipment requirements and
tests
Compliance with all relevant aspects of the
standard.
•Radiated Emissions
•Mains Terminal Voltage Emissions
•RF immunity
•Fast Transients
•ESD •Surge
•Voltage drops and interruptions
•Conducted
•Power magnetic fields
Communication type Function
N:N network Data transfer between up to eight FX Series PLCs by the
simple program.
Parallel link Data transfer between two FX Series PLCs specifying
master/slave station.
Computer link Data transfer via dedicated protocol between PLC and
computer (specified as the master station).
Non-protocol
communication
Serial communication via non-protocol between PLC and
RS-485 device.
Inverter
communication
Controlling Mitsubishi's FREQROL inverter using inverter
communication instruction.
MODBUS
communication Data transfer for up to 16 slaves controlled by one master.
1.2 Incorporated Items
Check if the following product and items are included in the package:
The label should be applied on the front of 485ADP-MB for checking station numbers
in N:N network, computer link, MODBUS Communication, etc.
1.3 External Dimensions, Part Names and Terminal Layout
1.4 Terminal Configuration
The terminal configuration of the RS-485 terminal on the 485ADP-MB is shown
below.
1.5 Terminal Resistor Selector Switch
485ADP-MB has a built-in terminal resistor.
A terminal resistor may be required depending on the communication type. Refer to
the following manual for the terminal resistor setting.
→ Refer to FX Series User's Manual - Data Communication Edition, and FX3U
Series User’s Manual - MODBUS Serial Communication Edition.
2. Channel Allocation
Up to two communication ports can be added to the main unit.
Communication port channels are automatically allocated. The closer
communication special adapter to the main unit is ch1.
•Using one communication special adapter + communication expansion board
•Using two communication special adapters
[1] DIN rail mounting groove (DIN rail: DIN46277)
[2] Name plate
[3] Special adapter slide lock:
Used to connect special adapter on left side of this special adapter.
[4] Special adapter connector cover:
Remove this cover for connecting special adapter on the left side.
[5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw)
[6] POWER LED (green): Lit while 5V DC power is supplied from main unit.
[7] RD LED (red):
Lit while receiving data from connected RS-485 device.
[8] SD LED (red):
Lit while sending data to connected RS-485 device.
[9] Terminal resistor selector switch (330Ω/OPEN/110Ω)
[10] Special adapter connector:
Used to connect this special adapter to PLC main unit or special adapter.
[11] Terminal block (European type) for connecting RS-485 device
Use to connect RS-485 device to 485ADP-MB.
[12] DIN rail mounting hook
[13] Special adapter fixing hook
[14] Special adapter connector:
Used to connect communication special adapter or analog special adapter to
this adapter on left side.
Manual
This
manual
Product Label
Station15
Station12
Station11
Station10
Station9
Station8
Station7
Station6
Station5
Station4
Station3
Station2
Station1
Station0
Station14
Station13
JY818D61301A
Netwrork Stat ion No.
リンク用局番ラベル
Station16
Station
Station
POWER
RD
SD
FX
3U
-485ADP
-MB
74(2.92")
[6]
[5]
[7]
[8]
[9]
[10]
[3]
[12]
[14]
[11]
Weight: Approx. 80g (0.18 lbs)
Special adapter
connector cover
is removed
7(0.28")
15.5
(0.65")
90(3.55")
98(3.86")
106(4.18")
17.6
(0.7")
15.1
(0.6")
FX
3U
-485ADP
-MB
[13]
[2]
[4]
[1]
RDA
RDB
SDA
SDB
SG
Signal
name Function
Signal direction
485ADP-MB RS-485
equipment
RDA(RXD+) Receive data ←
RDB(RXD-)
SDA(TXD+) Send data →
SDB(TXD-)
SG(GND) Signal ground −
Terminal screws
RDARDBSDASDBSG
Setting terminal
resistor to 330
Ω
330
Ω
OPEN
110
Ω
Setting no
terminal resistor
330
Ω
OPEN
110
Ω
Setting terminal
resistor to 110
Ω
330
Ω
OPEN
110
Ω
Analog
special
function
adapter
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
-MB
Analog
special
function
adapter
Main unit
Communication function
extension board (ch1)
(ch2)
Analog
special
function
adapter
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
-MB
Analog
special
function
adapter
FX
3U
-
485ADP
-MB Main unit
FX
3U
-CNV-BD(ch1)(ch2)
FX3U-485ADP-MB
Installation Manual
This manual describes the part names, dimensions, mounting, and
specifications of the product. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
And, store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
Registration
MODBUS®is a registered trademark of Schneider Electric S.A.
The company name and the product name to be described in this manual are
the registered trademarks or trademarks of each company.
Effective April 2007
Specifications are subject to change without notice.
©2007 Mitsubishi Electric Corporation
Manual Number JY997D26301
Revision A
Date April 2007
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
3. Installation
For details of installation/uninstallation, refer to the manual of the PLC main unit to
be used.
→ Refer to the FX3U Series User's Manual - Hardware Edition.
3.1 Connection to the FX3U Series PLC
•Refer to the procedure 2) for configuring a new system.
•Refer to the procedure 1) for adding product to an existing system.
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter.
Dismount the main unit and special adapter mounted on DIN rail or mounted
directly using screws.
2) Install an expansion board to the main unit.
For installation of expansion board, refer to the following manual:
→ Refer to the FX3U Series User's Manual - Hardware Edition.
3) Remove the special adapter connector cover
on the expansion board (Right fig.A).
In case of connecting this product to another
special adapter, please replace the
'expansion board' in the above description
with a 'special adapter' and perform the
procedure as indicated.
4)
Slide the special adapter slide lock (Right
fig.B) of the main unit.
In case of connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated. (Please replace the following
procedures similarly.)
5)
Connect the
special adapter
(Right fig.C) to
the main unit as
shown on the
right.
6) Slide back the
special adapter
slide lock (Right
fig.B) of the main
unit to fix the
special adapter
(Right fig.C).
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
INSTALLATION
PRECAUTIONS
•Cut off all phases of the power source externally before starting the
installation or wiring work, thus avoiding electric shock or damages to the
product.
INSTALLATION
PRECAUTIONS
•Use the product in the environment within the general specifications
described in PLC main unit manual (Hardware Edition).
Never use the product in areas with dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas, vibrations or
impacts, or expose it to high temperature, condensation, or wind and rain.
If the product is used in such a place described above, electrical shock, fire,
malfunction, damage, or deterioration may be caused.
•When drilling screw holes or wiring, cutting chips or wire chips should not
enter ventilation slits.
Such an accident may cause fire, failure or malfunction.
•Do not touch the conductive parts of the product directly, thus avoiding failure
or malfunction.
•Fix the special adapter securely to the specified connector.
Incorrect connection may cause malfunction.
RUN
STOP
FX
3U
-48MR/ES
FX
3U
-48M
3)
4)
B
B
A
4)
RUN
STOP
FX
3U
-48MR/ES
-48MR/ES
FX
3U
-48M
POWER
RD
SD
FX
3U
-485ADP
-MB
FX
3U
-48M
6)
C
B
B
5)
5)
5)
6)
4. Wiring
For details of wiring, refer to FX Series User's Manual - Data Communication Edition,
and FX3U Series User’s Manual - MODBUS Serial Communication Edition.
Wiring precaution
•Do not attach the terminal block (replacement European terminal block) for
connecting RS-485 device which is already wired to FX3U-485-BD.
If attached as its left and right are confused, the terminal configuration becomes
upside down and no communication is performed.
5. Specification
WIRING
PRECAUTIONS
•Cut off all phases of power source externally, before installation or wiring work in
order to avoid electric shock or damage of product.
WIRING
PRECAUTIONS
•Never let cutting chips and wire chips enter the ventilation slits of this product or
PLC when performing wiring.
Otherwise, fire, failure or malfunction may occur.
•Make sure to observe the precautions below in order to prevent any damage to a
machine or any accident which might be caused by abnormal data written in the
PLC due to the influence of noise:
1) Do not lay close or bundle with the main circuit, high-voltage power line, or
load line.
Otherwise effects of noise or surge induction are likely to take place.
Keep a safe distance of more than 100 mm (3.94") from the above when
wiring.
2) Ground the shield wire or shield of a shielded cable at one point on the PLC.
However, do not ground at the same point as high voltage lines.
•Observe the following items to wire the lines to the European terminal board.
Ignorance of the following items may cause electric shock, short circuit,
disconnection, or damage of the product.
- The end disposal size of the cable should follow the dimensions described in
this manual.
- Tighten to a torque should follow the torque described in this manual.
- Twist the end of strands and make sure there is no loose wires.
- Do not solder-plate the electric wire ends.
- Connect only the electric wires of regulation size.
- Fix the electric wires so that the terminal block and connected parts of electric
wires are not stressed directly.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the unit.
Doing so may cause failure, malfunction or fire.
* For repair, contact your local Mitsubishi Electric distributor.
•Do not drop the product or do not exert strong impact, doing so may cause
damage.
DISPOSAL
PRECAUTIONS
•Please contact a company certified in the disposal of electronic waste for
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•During transportation avoid any impact as the product is a precision instrument.
Check the operation of the product after transportation.
5.1 Applicable PLC
The version number can be checked by monitoring D8001, as well the last three
digits indicate the version number.
5.2 General Specifications
For general specifications, refer to the PLC main unit manual.
The following items are not equivalent to the PLC main unit.
5.3 Power Supply Specification
5.4 Performance Specification
6. Operation of Terminal Resistor Selector Switch
Use the tip of tweezers, tip of mechanical pencil, minute screwdriver, or the tool
whose tip width is about 0.8mm (0.03") when operating the terminal resistor selec-
tor switch.
Either 'push down' or 'push up' the switch to change the setting as indicated in the
figure above.
Confirm the clicking noise when setting the switch.
Model name Applicability
FX3U Series PLC
Ver. 2.40 and later for MODBUS communication
Ver. 2.20 and later for all communication functions except
MODBUS
Item Specification
Dielectric withstand
voltage 500V AC for one minute Conforming to JEM-1021
Between all external terminals
and ground terminal of PLC
main unit
Insulation resistance 5MΩor more by 500V DC
megger
Item Specification
Current
consumption
20mA/5V DC (fed from the PLC power supply)
Item Specification
Transmission
standard Conforming to RS-485/RS-422
Type of isolation Photocoupler isolation
Transmission
distance
Total extension distance: 500m (1640' 5") or less
[50m (164' 0") or less if FX2N-485-BD, FX1N-485-BD or
FX3U-485-BD is installed to connected equipment]
Connection method
European type terminal block, AWG 22-20 (when inserting
one twisted pair cable), AWG 22 (when inserting two
twisted pair cables)
Tightening torque: 0.22 to 0.25 N•m
Number of occupied
I/O points
0 point (This number is not related to the maximum number
of input/output points of the PLC.)
Communication
method Half-duplex
Baud rate
Computer link, non-protocol communication, and
MODBUS:
300/600/1200/2400/4800/9600/19200 bps
Communication
format
N:N network, Parallel link
Computer link (dedicated protocol: format 1/format 4), Non-
protocol, and MODBUS (RTU, ASCII)
LED display:
LED color Power: green, RD: red, SD: red
330
Ω
OPEN
110
Ω
Pushing down
direction
Pushing up direction
Tool
Switch
330
Ω
OPEN
110
Ω
330
Ω
OPEN
110
Ω
Tool

This manual suits for next models

1

Other Mitsubishi Controllers manuals

Mitsubishi MELSEC-F FX3U-4AD-PT-ADP User manual

Mitsubishi

Mitsubishi MELSEC-F FX3U-4AD-PT-ADP User manual

Mitsubishi FX3U-232ADP(-MB) User manual

Mitsubishi

Mitsubishi FX3U-232ADP(-MB) User manual

Mitsubishi QD51-R24 User manual

Mitsubishi

Mitsubishi QD51-R24 User manual

Mitsubishi MELSEC-FX0N Series User manual

Mitsubishi

Mitsubishi MELSEC-FX0N Series User manual

Mitsubishi FX-10GM User manual

Mitsubishi

Mitsubishi FX-10GM User manual

Mitsubishi MELSEC QS Series Owner's manual

Mitsubishi

Mitsubishi MELSEC QS Series Owner's manual

Mitsubishi AG-150A User manual

Mitsubishi

Mitsubishi AG-150A User manual

Mitsubishi Q173DSXY User manual

Mitsubishi

Mitsubishi Q173DSXY User manual

Mitsubishi MELSEC-WS0-CPU0 User manual

Mitsubishi

Mitsubishi MELSEC-WS0-CPU0 User manual

Mitsubishi Melsec A User manual

Mitsubishi

Mitsubishi Melsec A User manual

Mitsubishi QCPU Owner's manual

Mitsubishi

Mitsubishi QCPU Owner's manual

Mitsubishi MELSEC iQ-F FX5 series Owner's manual

Mitsubishi

Mitsubishi MELSEC iQ-F FX5 series Owner's manual

Mitsubishi aj65sbt-rps User manual

Mitsubishi

Mitsubishi aj65sbt-rps User manual

Mitsubishi QJ71E71-100 Series User manual

Mitsubishi

Mitsubishi QJ71E71-100 Series User manual

Mitsubishi A Series User manual

Mitsubishi

Mitsubishi A Series User manual

Mitsubishi FX2N-4AD-PT User manual

Mitsubishi

Mitsubishi FX2N-4AD-PT User manual

Mitsubishi AL-232CAB User manual

Mitsubishi

Mitsubishi AL-232CAB User manual

Mitsubishi Q64TD User manual

Mitsubishi

Mitsubishi Q64TD User manual

Mitsubishi Q172CPU User manual

Mitsubishi

Mitsubishi Q172CPU User manual

Mitsubishi Melsec-Q QD75P1 User manual

Mitsubishi

Mitsubishi Melsec-Q QD75P1 User manual

Mitsubishi MELSEC A1SCPUC24-R2 Instructions for use

Mitsubishi

Mitsubishi MELSEC A1SCPUC24-R2 Instructions for use

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Mitsubishi FX3U Series User manual

Mitsubishi

Mitsubishi FX3U Series User manual

Mitsubishi MELSEC System Q User manual

Mitsubishi

Mitsubishi MELSEC System Q User manual

Popular Controllers manuals by other brands

Spring V11M BPC quick start

Spring

Spring V11M BPC quick start

SEW-Eurodrive MOVIPRO PHC2 Series operating instructions

SEW-Eurodrive

SEW-Eurodrive MOVIPRO PHC2 Series operating instructions

FlowCon FN.0.2 Installation and operation instruction

FlowCon

FlowCon FN.0.2 Installation and operation instruction

Newport SMC100CC Command Interface Manual

Newport

Newport SMC100CC Command Interface Manual

Kustom Signals Eyewitness HD ICV System Quick reference guide

Kustom Signals

Kustom Signals Eyewitness HD ICV System Quick reference guide

Haiku L Wired Wall Control installation manual

Haiku

Haiku L Wired Wall Control installation manual

Cypress CY3280-20x66 Universal CapSense quick start guide

Cypress

Cypress CY3280-20x66 Universal CapSense quick start guide

Hayward OmniPL Retrofit Kit Operation manual

Hayward

Hayward OmniPL Retrofit Kit Operation manual

SMSC USB464 datasheet

SMSC

SMSC USB464 datasheet

Unitronics Vision V130J-TR34 user guide

Unitronics

Unitronics Vision V130J-TR34 user guide

ISVT IVC3100 instruction manual

ISVT

ISVT IVC3100 instruction manual

Cypress CapSense AN64846 Getting started

Cypress

Cypress CapSense AN64846 Getting started

ICON NXT Pro user manual

ICON

ICON NXT Pro user manual

Danfoss VLT AQUA Drive FC 202 operating instructions

Danfoss

Danfoss VLT AQUA Drive FC 202 operating instructions

effeff 720-30 Operating and installation instructions

effeff

effeff 720-30 Operating and installation instructions

HANYOUNG NUX HY Series instruction manual

HANYOUNG NUX

HANYOUNG NUX HY Series instruction manual

Go Power DOMETIC GP-BMG quick start guide

Go Power

Go Power DOMETIC GP-BMG quick start guide

Hobby-Wing Xerun XR10 Pro user manual

Hobby-Wing

Hobby-Wing Xerun XR10 Pro user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.