6.2.1 Disassembling the trap
1) Secure the body (1) (or cover (3)) in a vise, and remove the cover (3) (or the body (1)).
When the cover (3) and the adjust bolt (6) are removed as a unit without
disassembling them, it will not be necessary to readjust the temperature setting after
reassembly.
2) Remove the bimetal part (the bimetal (11), the shaft (5), the E-ring (10), and the
washer (12)), the valve (7), the spring plate (13), and the spring (14) by hand.
*Do not take apart the bimetal part. If the bimetal discs come off the bimetal part, each
disc has a mark on one face. Place the two marked surfaces facing out, away from
each other, and then put the two bimetal discs with the washer in between them back
into the bimetal part. Treat the two bimetal discs as a set. If this assembly is wrong, the
bimetal part will not function properly.
3) When removing the bonnet (2) from the body (1) or the cover (3), be careful to keep
the bonnet (2) from being deformed or distorted. Use the proper tools to remove the
parts.
4) Remove the valve seat (4) using a socket wrench.
5) Clean and inspect the parts thoroughly.
After repairing the trap, re-assemble the parts in reverse order as follows.
6.2.2 Reassembling the trap
1) Insert the screen (8) into the body (1) and screw the valve seat (4) into the body (1).
2) Reinstall the spring (14) and the spring plate (13) on the valve seat.
3) Put the valve (7) into the center hole in the spring plate (13), and place it on the spring
plate (13) so that the tip of the valve (7) can be inserted into the hole in the valve seat
(4).
4) Reinstall the bimetal part so that the tip of the shaft (5) fits into the hole in the valve (7).
5) Screw the bonnet (2) onto the body (1), and the cover (3) onto the bonnet (2). Then,
tighten the cover (3).
* The proper torque for the Body (1), cover (3), and valve seat (4) are as shown in the
following table.
Parts Tools Across the flats Torque
Body (1) Torque wrench 22 mm (0.86”) 56N・m
Cover (3) Torque wrench 22 mm (0.86”) 56N・m
Valve seat (4) Torque wrench 23 mm (0.91”) 56N・m
* When the adjustment unit is disassembled, after reassembling it set the temperature again,
following the steps shown in the Section 4, “Setting the temperature”.