
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.866.823.1631 (toll free)
www.modinehvac.com/schoolsystems
© Modine Manufacturing Company 2015
AIR74-526
Schedule (CONTINUED FROM OTHER SIDE)
Changing Setpoints
vi. The screen to the right will be the rst programmable schedule.
vii. Highlight the elds and adjust as needed to schedule the time and days of desired unit operation.
To move to the next time period, highlight the ‘Schedule #’ eld and adjust this number by
pressing .
b. Customizing Holiday Schedules
i. Scroll to the ‘Holidays’ screen in the ‘Clock/Scheduler’ menu. Use the or arrows to adjust the
number of holidays as needed up to 16.
ii. Press to move the cursor to each date range and use the or arrows to adjust the number as needed. If not all four holiday ranges are
required, the unneeded ranges can be left as ‘0/0-0/0’.
6
a. Enter the main menu by pressing and scroll down to line ‘G. Service’ and press . This menu allows access to several parameters for advanced
setup or control. This includes BMS Setup, Control Settings such as temperature lockouts or stage delays, and Manual Control of controller inputs/outputs.
b. To enter directories of this menu, enter password ‘1500’ when prompted. Reference AIR74-525 for additional information.
Service
7
a.
If you need to change your instance number on a Carel network card (BACnet), perform the following:
i. Enter the main menu by pressing and scroll down to line ‘G. Service’ and press .
ii. Scroll to ‘e.BMS cong’ and press .
iii. Scroll to the page that asks if the unit has a Termconf Plugin, and verify that this is set to ‘YES’.
iv. On the next page, there will be an ‘Instance’ eld referencing a 4-digit number. Press once to edit
the thousand-digit of the number, and press again to edit the remaining digits using the or
arrows.
v. On the next page, verify the BACnet function is set to 'WRITE', and change the update eld to 'YES'.
Press . After seconds, the update eld will automatically change to
‘
NO
’
.
Note: If BMS connectivity is not achieved, consult controls manual AIR74-525 for additional information on BMS setup methods.
BMS Setup - Changing Device Instance and Station Address
8
a. The manufacturer menu provides access to parameters not typically required to be changed in the eld. These parameters include unit conguration,
controller input/output conguration, and reboot sequences. Please contact technical service for assistance if unit operation may be limited by one of
these parameters, or see publication AIR74-525 for more information.
Advanced Information
9
a. If the unit is sending an alarm signal, the alarm icon on the pGD1 display module will ash continuously:
i. Press to display the active system alarms. If there are multiple alarms, they may be viewed by pressing the or arrows.
ii. Details of the unit’s running conditions when the alarm occurred may be viewed by pressing after reaching the end of the alarm list.
iii. Pressing and holding the button will clear the ashing icon and all active alarms, and indicate there are no active alarms in the system.
iv.
The alarm log can be viewed by pressing . Press to return to the main screen. If an alarm is persisting, the alarm light will begin to ash again.
Viewing / Clearing Alarms
10
a. Enter the main menu by pressing and scroll down to line B. Setpoint and press .
b. Occupied Setpoints
i. Press to highlight ‘Cooling Set’. Use the or arrows to adjust the number as needed.
ii. Press to highlight ‘Heating Offset’. Use the or arrows to adjust the number as needed. The heating setpoint is calculated by subtracting
the heating offset from the cooling setpoint automatically updating the heating setpoint (For example, if the cooling setpoint is 74°F, and the
heating/cooling band is 4°F, the heating setpoint will automatically be set to 70°F). The unit uses the offset eld for various control logic and it is not
recommended to adjust this value below 3°F.
c. Unoccupied Setpoints
i. Press until cursor is at the upper left corner of the screen. Use the arrow to scroll to the ‘Unoccupied’ page.
ii. Press to highlight ‘Cooling Set’. Use the or arrows to adjust the number as needed.
iii. Press to highlight ‘Heating Set’. Use the or arrows to adjust the number as needed.
iiii. Press to highlight ‘Humidity Set’. Use the or arrows to adjust the number as needed.
d. Standby Setpoints
i. In standby mode, the clock is calling for the unit to run in occupied mode, but the optional occupancy sensor has detected the room is not occupied.
Press until cursor is at the upper left corner of the screen. Use the arrow to scroll to the ‘Standby’ page.
ii. Press to highlight ‘Cooling Set’. Use the or arrows to adjust the number as needed.
iii. Press to highlight ‘Heating Set’. Use the or arrows to adjust the number as needed.
iiii. Press to highlight ‘Humidity Set’. Use the or arrows to adjust the number as needed.
e.DehumidicationSetpoints
i. If the unit has hot gas reheat with a space humidity sensor, a humidity control page will be visible in
the setpoints menu. Press until cursor is at the upper left corner of the screen. Use the arrow
to scroll to the ‘Dehum Setpoints’ page (shown at right).
ii. Press to highlight desired eld. Use the or arrows to adjust the number as needed.
iii. ‘Differential’ eld sets a requirement to satisfy and demand humidity control.
iv. ‘Temp Low Diff’ eld allows for certain amount of space overcooling if the unit is dehumidifying
the space. This value is calculated above the heating set point (minimum 1° F) with the maximum
being the heating offset value.