necessary. Both of the additives are non-conductive and will not hurt
the chiller or the tube.
Connecting the water lines:
NOTE: To prevent debris from contaminating the water chamber, the
chiller ships with either a short hose or protective caps (or both) over
the inlet and outlet fittings. Please remove these and recycle or discard
them.
1) Slide two included hose clamps onto each water hose.
2) Connect a water hose from the inlet fitting on the chiller to the
water outlet port on your laser.
3) Connect the 2nd water hose from the outlet fitting on the chiller to
the water input port on your laser.
4) Tighten all four clamps.
Powering on the unit for the first run:
1) With the Power Switch in the OFF position, plug the power cord
firmly into the power socket and make sure it is fully seated. Plug the
other end of the cord into a properly grounded wall outlet.
NOTE: The 5200 series chillers can draw about 4.6 to 6.5A of power depending on whether the
compressor is on or off. It is highly recommended to use a dedicated wall outlet rated at 15A or
better. Using a 15-20A outlet should be fine for both the laser and the chiller. We do not
recommend using a household extension cord!
2) Before turning on the power switch, press and hold both the up and
down arrows on the controller, then turn the power switch to the on
position. You will hear an alarm, and after approximately three
seconds, the controller LED screen will read, rE. Release the up and
down arrows and approximately six seconds later, the chiller will go
into intelligent start up mode with the factory-controlled settings.
NOTE: Do not power off the chiller during the startup mode! Normal startup will take from 2 to
5 minutes, and the compressor will not start immediately. The chiller must operate for at least 5
minutes before you can power it off. Turning the power off during the startup mode may/will
cause damage to the internal components.