Programming
Program all parameters as per the programming guide,
see page 3. Start from the top (and go down) accordingly.
During the programming, the fan must not receive any
start signal. This means that DI1, DI3 and +24 (8) cannot
be a closed circuit.
Note! The green parameters can be changed, to optimise
current system. The red parameters can be found on the
motor. The blue parameter ”LSP” indicates selected lowest
fequency (step 1), and parameter ”SP2” indicates selected
maximum frequency (step 2).
ConF
drC-
S1 -
S1 -
S1 -
S1 -
S1 -
S1 -
S1 -
S1 -
S1 -
S1 -
FUn-
FUn-
drC-
drC-
drC-
I_0-
Fun-
Access to configuration
Variable torque
Motor frequency (Hz)
Nominal motor voltage (V)
Nominal motor frequency (Hz)
Nominal motor current (A)
Nominal motor speed (rpm)
Acceleration (s)
Retardation (s)
Step 1, set min. frequency (Hz), (! Not lower than 15)
Max. frequency (Hz)
Thermal motor protection (A) = motor current
Activates logical input LI3 = Terminal DI3
Step 2, set max. frequency, (! Not lower than LSP)
Motor parameter choice
Motor’s Cos Phi
Switch frequency (kHz)**
2 wire type
Stop type
U
PROGRAMMING GUIDE
Menu
Submenu
Parameter
Function
Recommended
value
Chosen value
Factory
settings
** Only to be changed when there is unusual noise from the motor.
"
FULL
Ctt
PSS-
PSS-
ASy-
ASy-
Stt-
bFr
Uns
FRs
nCr
nSP
ACC
DeC
LSP
HSP
ItH
PS2
SP2
PC
COS
SFr
tCt
Stt
U
-
Std
50
-
60.0
-
1400
3.0
3.0
0.0
60.0
-
nO
10.0
nPr
-
4.0
trn
Stt
-
UF9
5.0
5.0
15.0-60.0
60.0
L13
59.0
COS
16
LEL
nST
Varies
Varies
Varies
Varies
Varies
Varies
Varies
Programming manual
MOVEX SFC for rotary switch
3
U
U
U
U
U
U
U
U
U
Default reset
When resetting to the factory settings, please proceed as
below:
If the display doesn’t show rdy, press ESC until it does.
Enter menu ConF and select parameter FCS-. Change the
value from FCS1 to Fry-, confirm with ENT. Change ALL,,
to ALL" by pressing ENT. Go back one step in the menu
with ESC and change from FrY- to 6FS. Press ENT and
change nO to yES by pressing and holding ENT for 5 s.
The frequency converter will now have the initial factory
settings and is ready for programming again.