12.2 SAFETY INSTRUCTIONS FOR INSTALLATION IN A HAZARDOUS AREA
READ THE INSTRUCTION MANUAL CAREFULLY BEFORE INSTALLATION
All the operations shall be done by a trained and qualied operator. It is forbidden to use
this equipment in any different way, if not included in the instruction manual.
The installation and maintenance of the high-pressure lter must be realized in accordance with the plant and
maintenance standards for classied area with the presence of potentially explosive gases or dust (i.e. EN 60079-14,
EN 60079-17 or other national standards).
The lter must be connected to the ground through an anti-loosening and anti-rotation device: an earthing kit
is supplied together with the lter, and it can be connected to one of the fastening screws.
The electrical continuity between the two metal parts of the lter is ensured by the electrical continuity of the
components on which the lter is mounted and by the anti-rotation and anti-loosening device.
The electrical resistance measured between the various metal parts of the lter and the reference point must be
veried at the time of initial installation and subsequently during periodic inspections.
The user must check periodically, depending on the type of use and the substances used:
- the state of wear and proper functioning of the lter
- the presence of abnormal vibrations and/or noises, in which case the causes must be identied and contact the
manufacturer.
If the End User installs electrical components (clogging sensors, indicators, etc.), they must have a separate ATEX
certication and suitable for the installation area, gas and dust group, temperature class and maximum surface
temperature, range of ambient temperature.
For use in hazardous area for the presence of combustible dust carry out regular cleaning to avoid the
formation of dust layers; use equipment suitable for the classication of the area.
Filtration of non-ammable liquids or ammable liquids with temperature of auto ignition >50K than the max uid
temperature for the lter. During ltration, depending on oil type (viscosity and electrical conductivity), on uid velocity
and temperature, electrostatic charging on the lter element may occur.
In case of replace of the lter elements Zerospark version shall be installed to mitigate the oil charge building up.
Since it is not always possible to know the environmental installation condition, it is recommended to check the whole
system following the indications given in the guidance IEC/TS 60079-32-1.
Provide routine maintenance according to a period to be determined by the operating conditions, environment,
and temperature.