PAGE 18 — DCA-300SSK III — PARTS AND OPERATION MANUAL (FEMA) — REV. #1 (05/07/03)
DCA-300SSK III — GENERAL INFORMATION
DCA-300SSK III FAMILIARIZATION
Generator
The MQ Power DCA-300SSK III series generators are
240
kW generators
that are designed as a high quality portable
(requires a trailer for transport) power source for telecom
sites, lighting facilities, power tools, submersible pumps and
other industrial and construction machinery.
Engine Control Panel
The “
Engine Control Panel
” is provided with the following:
z
Tachometer
z
Water Temperature Gauge
z
Oil Pressure Gauge
z
Charging Ammeter Gauge
z
Engine Warning Display Module
z
Engine Speed Switch
z
Pre-Heat Button
z
Pre-Heat Lamp
z
Emergency Stop Button
z
Battery Switch
z
Auto On/Off Engine Controller
Generator Control Panel
The “
Generator Control Panel
” is provided with the following:
z
Output Voltage Adjustment Knob
z
Frequency Meter (Hz)
z
AC Ammeter (Amps)
z
AC Voltmeter (Volts)
z
Ammeter Change-Over Switch
z
Voltmeter Change-Over Switch
z
Panel Light
z
Panel Light Switch
z
Pilot Lamp
Output Terminal Panel
The “
OutputTerminal Panel
” is provided with the following:
z
3 auxiliary 240/139V output receptacles, 50 amp
z
3 auxiliary circuit breakers 240V @50 amps
z
2 120V GFCI receptacles, 20 amp
z
2 GFCI circuit breakers 120V@ 20amps
Control Box
The “
Control Box
” is provided with the following:
z
Main Circuit Breaker 800 amps
z
Over-Current Relay
Open Delta Excitation System
The DCA-300SSK III series generators are equipped with
the state of the art "
Open-Delta
" excitation system. The
open delta system consist of an electrically independent
winding wound among stationary windings of the AC output
section.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a "
fixed ceiling
" and responds
according the demands of the required load.
There are four connections of the open delta A, B, C, and D.
During steady state loads, the power from the voltage regulator
is supplied from the parallel connections of A to B, A to D,
and C to D. These three phases of the voltage input to the
voltage regulator are then rectified and are the excitation
current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the configuration of the open delta to the series
connection of B to C.This has the effect of adding the voltages
of each phase to provide higher excitation to the exciter
section and thus better voltage response during the
application of heavy loads.
Engine
The DCA-300SSK III is powered by a 4 cycle, water cooled,
air to air after cooled, turbocharged KOMATSU Model
SAA6D125E-2
diesel
engine. This engine is designed to
meet every performance requirement for the generator.
Reference Table 2 for engine specifications.
In keeping with Multiquip's policy of constantly improving its
products, the specifications quoted herein are subject to
change without prior notice.
The basic controls and indicators for the DCA-300SSK III
series generators are addressed on the following pages.
Electronic Governor System
The DCA-300SSK III is equipped with an electronic governor
system. It is made up of two parts; an electronic controller
that monitors frequency variation as the load increases and
decreases, and an electronic actuator that controls the engine
throttle. The frequency is regulated at ±0.25 to help protect
sensitive equipment.
Microprocessor Engine Control (MPEC)
The DCA-300SSK III incorporates the use of a
microprocessor
engine controller
unit (MPEC), which monitors basic engine
functions and also allows the generator to operate in an
unattended mode.